Identication for Control: Some Results on Optimal Experiment Design
Urban Forssell and Lennart Ljung Division of Automatic Control Department of Electrical Engineering Linkoping University, S-581 83 Linkoping, Sweden
E-mail: ufo@isy.liu.se, ljung@isy.liu.se URL: http://www.control.isy.liu.se/
February 26, 1998
Abstract
The problem of designing the identication experiments to make them maximally informative with respect to the intended use of the model is studied. A focus will be on model based control and we show how to choose the feedback regulator and the spectrum of the reference signal in case of closed-loop experiments. A main result is that when only the mist in the dynamics model is penalized and when both the input and the output power are constrained then the optimal controller is given by the solution to a standard LQ problem. When only the input power is constrained, it is shown that open- loop experiments are optimal. Some examples are also given to exemplify the theoretical results.
1 Introduction
The validation step in the identication procedure should be devoted to evaluating the model with respect to its intended use simulation, prediction, control, etc. To make fair judgments it is important to know what factors aect the model's performance and how these factors can be manipulated. In this paper we focus on experiment design issues and especially how one should choose the feedback regulator in closed-loop experiments. The aim will be to design the experiments so as to minimize the variance errors in the identied models. This route was also taken in 2] and 4], and the presentation here will be inspired by these papers. See also 7].
The main drawback with the optimal solutions that will be derived is that they typically will depend on unknown quantities, like the unknown system that we are trying to identify.
Clearly this will lead to infeasible designs. This problem is inevitable and shared with any optimal design problem. A way around this is to use iterations and to replace the true system in the optimal solutions with the current estimate of the system.
Despite this problem the optimal solutions derived here give important and useful insights
into questions like \Should open-loop or closed-loop experiments be used?" and \To which
frequency ranges should the input signal power be concentrated?".
The rest of the presentation will unveil as follows. Section 2 contains some background material on the identication method used and the assumptions made on the underlying system. The notation will also be introduced in this section. In Section 3 we provide a motivation for the type of criterion we will consider. A key issue is that the criterion will reect the variance error introduced when using identied models in the control design. Section 4 contains the main results and in Section 5 these results are applied to some well known control design schemes like internal model control and minimum variance control. Conclusions are given in Section 6.
2 Preliminaries
To evaluate a model's performance one needs some notion of the \best" or \true" model. We will assume that the true system is single-input single-output (SISO) and given by
y
(
t) =
G0(
q)
u(
t) +
v(
t)
v
(
t) =
H0(
q)
e(
t) (1)
Here
fe(
t)
gis white noise with variance
0. To simplify the notation we introduce the transfer matrix
T
0
(
q) =
G0(
q)
H
0
(
q)
(2) Given input-output data
ZN=
fy(1)
u(1)
:::y(
N)
u(
N)
gand a parameterized model structure
^
y
(
tj) =
H;1(
q)
G(
q)
u(
t) + (1
;H;1(
q))
y(
t) (3) we can estimate the model by the straightforward t:
^
N
= argmin
V
N
(
) (4)
V
N
(
) =
XNt=1
"
2
(
t) (5)
"
(
t) =
y(
t)
;y^ (
tj) =
H;1(
q)(
y(
t)
;G(
q)
u(
t)) (6) For more details on this identication method see, e.g., 7]. The model structure (3) may also be represented as
y
(
t) =
G(
q)
u(
t) +
H(
q)
e(
t) (7) In the sequel
G(
q) and
H(
q) will be called the dynamics model and the noise model, respectively. Let ^
GN(
q) =
G(
q^
N) and ^
HN(
q) =
H(
q^
N) and also introduce
^
T
N
(
q) = ^
GN(
q)
^
H
N
(
q)
(8) The error between the true transfer matrix
T0and the estimated one ^
TNwill be denoted ~
TN,
~
T
N
(
q) =
T0(
q)
;T^
N(
q) = ~
GN(
q)
~
H
N
(
q)
with an obvious notation for ~
GNand ~
HN. As the number of data tends to innity and the model order
nincreases we have that (cf. 5], 9])
Cov ^
TN(
ei!)
nN
P
(
!) =
nN
v(
!)
u(
!)
ue(
!)
ue(
;!)
0
;T
(9)
In this paper we will assume that the input is generated as
u
(
t) =
r(
t)
;K(
q)
y(
t) (10) and that the reference signal
ris uncorrelated with the disturbance
e, i.e., that the cross spectrum
re= 0 . We can then split the input spectrum into two parts, one that is due to
rand one that is due to
e:
u(
!) =
ru(
!) +
eu(
!) (11) By combining (1) and (10) we see that the input can be written
u
(
t) =
S0(
q)
r(
t)
;K(
q)
S0(
q)
H0(
q)
e(
t) (12) Consequently
ru(
!) =
jS0(
ei!)
j2r(
!)
eu(
!) =
jK(
ei!)
j2jS0(
ei!)
j2jH0(
ei!)
j20(13)
ue(
!) =
;K(
ei!)
S0(
ei!)
H0(
ei!)
0(14) With these denitions we may rewrite
Pas
P
(
!) =
v(
!)
u(
!)
ue(
!)
ue(
;!)
0
;T
=
v(
!)
0
u(
!)
;jue(
!)
j2 0 ;ue(
!)
;
ue(
;!)
u(
!)
T
=
jH0(
ei!)
j2 ru(
!)
0 ;ue(
!)
;
ue(
;!)
ru(
!) +
eu(
!)
T
(15)
Here we have used the fact that
v(
!) =
0jH0(
ei!)
j2(16) A remark regarding (15) is that this result holds not only for the direct method, considered here, but also for the so called indirect and joint input-output approaches to closed-loop identication. See, e.g., 3] and 1]. Therefore all the results below will also apply to these approaches as well.
For future use we also note that the output spectrum can be written
y(
!) =
jG0(
ei!)
j2ru(
!) +
jS0(
ei!)
j2v(
!) (17)
3 Measuring the Performance Degradation
Our focus here will be on model-based control. It is then natural to evaluate the model's performance by comparing the outputs of the closed-loop system resulting from control design using the \true" models and the estimated ones, respectively. In general this output will be a function of both
Gand
Hand some driving signal
w:
y
(
t) =
f(
T(
q))
w(
t) (18) The \true" or \best" signal is
y
0
(
t) =
f(
T0(
q))
w(
t) (19) while the one resulting from the estimated models is
^
y
N
(
t) =
f( ^
TN(
q))
w(
t) (20) A measure of the performance degradation can be obtained by computing the mean square error
Ey
~
2N(
t) =
E(
y0(
t)
;y^
N(
t))
2(21) Using rst-order approximations we may write
~
y
N
(
t) = ~
TNT(
q)
F(
q)
w(
t) (22) where
F
(
q) =
@@T f
(
T)
T=T0(q)
(23) From the denition of the spectrum it follows that
Ey
~
2N(
t) = 12
Z; ~yN(
!)
d!= 12
Z;tr !(
!)
C(
!)]
d!(24) where
!(
!) =
ET~
N(
e;i!) ~
TNT(
ei!) (25)
C
(
!) =
F(
ei!)
w(
!)
FT(
e;i!) (26) Thus, if we want to minimize the performance degradation due to the use of identied models, a natural criterion to minimize would be
"
J
=
Z
;
tr !(
!)
C(
!)]
d!(27)
Let us comment on the matrix functions ! and
C. First, if the bias errors are negligible then
! will be the (transpose of the) covariance matrix of the estimate ^
TN,
!(
!) =
hCov ~
TN(
ei!)
iT(28)
The error made in this approximation should be small if the model structure is reasonably
exible. Using the standard result (9) we thus have
!(
!)
nN P
T
(
!) =
nN
v(
!)
u(
!)
ue(
!)
ue(
;!)
0
;1
(29)
Second, the weighting function
Cshould reect the relative importance of a good t in
Gand
H
, respectively, for dierent frequencies. We shall assume that
Cis Hermitian and positive semi-denite as in (30). In general we may write
C
(
!) =
C11(
!)
C12(
!)
C
12
(
;!)
C22(
!)
(30) If we neglect the scaling
n=N(which will have the aect that the prejudice against high order models is reduced), the criterion (27) simplies to
J
=
Z
;
tr
P(
!)
C(
!)]
d!(31)
The route taken here follows the one in 2].
4 Main Results
In this section we will consider experiment design problems where the goal is to minimize
Jwith respect to the design variables, which we take as
Kand
r. Other equivalent choices are also possible, e.g.,
uand
ueor
Kand
ru. To make the designs realistic we will also impose constraints on the input power or the output power, or both. We will also discuss the case where power of the reference signal is bounded. Without loss of generality we will take the upper bounds to be unity. This is done to simplify the notation and can always be achieved by suitable scaling. In the sequel we also will omit the arguments
!and
ei!whenever there is no risk of confusion.
First consider the case where penalty only is put on the mist in
G. This corresponds to
C
12
=
C22= 0 . We then have the following result which to our knowledge is new.
Theorem 1. The solution to the problem min
K r
Z
;
tr
PC]
d!:
C12= 0
C22= 0
Z;
f
u+ (1
;)
ygd!1
20
1]
(32) is
K
opt
= arg min
K Z
;
jKj
2
+ (1
;)
j
1 +
G0Kj2 vd!(33)
optr=
pvC11 j1 +
G0Koptj2p
+ (1
;)
jG0j2(34) where
is a constant, adjusted so that
Z
;
f
u+ (1
;)
ygd!= 1 (35)
Remark: It should be noted that equation (33), dening the optimal controller
Kopt, is a standard LQ problem. If
G0and
vwere known this could be easily solved to give an explicit expression for
Kopt.
Proof. Replace the design variables
Kand
rby the equivalent pair
Kand
ru. Then, by using (15), (11), and (17), problem (32) can be rewritten as
min
K
r
u
Z
;
v ruC11d!:
Z;
f
(
+(1
;)
jG0j2)
ru+
jKj2+ (1
;)
j
1 +
G0Kj2 vgd!1
20
1]
(36) The criterion function is independent of
Khence the optimal controller
Koptcan be found by solving the LQ problem
min
K Z
;
jKj
2
+ (1
;)
j
1 +
G0Kj2 vd!(37)
(Here it is implicitly assumed that
y(
t) =
G0(
q)
u(
t)+
v(
t)
u(
t) =
;K(
q)
y(
t), and
20
1].) This proves (33). Dene the constant
as
= 1
;Z
;
jK opt
j
2
+ (1
;)
j
1 +
G0Koptj2 vd!(38) Problem (36) now reads
min
r
u f
Z
;
v ruC11d!:
Z
;
(
+ (1
;)
jG0j2)
rud! g(39) This problem has the solution (cf. 7], p. 376)
ru=
s
vC11(
+ (1
;)
jG0j2) (40)
where
is a constant, adjusted so that
Z
;
((
+ (1
;)
jG0j2)
rud!=
(41) or in other words so that
Z
;
f
u+ (1
;)
ygd!= 1 (42) Consequently the optimal
ris
optr=
pvC11 j1 +
G0Koptj2p
+ (1
;)
jG0j2(43)
which ends the proof.
We stress that the optimal controller
Koptin (33) can easily be found by solving the indicated discrete-time LQ problem (if
G0and
vwere known). Among other things this implies that the optimal controller
Koptis guaranteed to stabilize the closed-loop system and be linear, of the same order as
G0. This is a clear advantage over the results reported in, e.g., 4] and also over the results in Theorem 3 below. Furthermore, the optimal controller is independent of
C11which also is quite interesting and perhaps somewhat surprising. This means that whatever weighting
C11is used in the design criterion, it is always optimal to use the LQ regulator (33) in the identication experiment.
From Theorem 1 we also see that closed-loop experiments are optimal as long as the is a constraint on the output power, i.e., as long as
6= 1. If
= 1 then
Kopt= 0 and the optimal input spectrum
optu(=
optr) becomes
optu=
pvC11(44)
This side result can in fact be strengthened 7]:
Theorem 2. The problem min
K r
Z
;
tr
PC]
d!:
Z
;
ud!1
C12= 0
(45) has the solution
K
opt
= 0 (open-loop operation) (46)
optr=
optu=
pvC11(47)
where
is a constant, adjusted so that
Z
;
ud!= 1 (48)
Consider now the case where the power of the reference signal is constrained. The following theorem, which we believe is new, then states what the optimal controller and reference spectrum are. The expression for the optimal controller also holds for the case where the reference signal is xed and pre-specied (which would be the case if data were collected under normal (controlled) operation of the plant).
Theorem 3. The problem min
K r
Z
;
tr
PC]
d!:
Z
;
rd!1
(49) has the solution
K
opt
=
; C11G0+
C12H0C
11 jG
0 j
2
+ 2Re(
C12G0H0) +
C22jH0j2(50)
optr=
s
vdet
CjH0j2C
11 jG
0 j
2
+ 2Re(
C12G0H0) +
C22jH0j2(51) where
is a constant, adjusted so that
Z
;
rd!= 1 (52)
Remark: Note that
Koptin (50) only is a feasible design if
Koptis proper and stabilizes the closed-loop system. Unfortunately no such guarantees can be given, which is a clear disadvantage compared to the result in Theorem 1. The optimal solutions derived in 4]
suer from the same type of problems, as mentioned earlier. To circumvent this problem it was suggested in 4] that the so called Youla parameterization 8] should be used. This idea could lead to interesting extensions of the results in Theorem 3 also, although we will not study it any further here.
Proof. Introduce the following square-root factorization of
C:
C
=
C0
1 CC23
C
1 C
0
C23
(53)
Clearly we have the relations
C
11
=
jC1j2+
jC2j2(54)
C
12
=
C2C3(55)
C
22
=
jC3j2(56)
With
Pgiven by (15) we have that
tr
PC] =
C22jH0j2+ # (57)
where
# =
vru
C
11
+ 2Re(
C12 KS0H0) +
C22jKj2jS0j2jH0j2(58)
=
vru
jC
1 j
2
+
jC2+
C3KS0H0j2(59)
=
vr
jC
1
(1 +
KG0)
j2+
jC2(1 +
KG0) +
C3KH0j2(60)
=
vrk
C
1 C
2
+
KC1G0 C2G0+
C3H0k2(61) There is no constraint on
Kso to minimize the criterion function we should, at each frequency, choose
Kas the least-squares estimate
K
opt
=
;
C
1 C
2
C
1 G
0 C
2 G
0
+
C3H0k
C
1 G
0 C
2 G
0
+
C3H0k2(62)
=
;(
jC1j2+
jC2j2)
G0+
C2C3H0(
jC1j2+
jC2j2)
jG0j2+ 2Re(
C2C3G0H0) +
jC3j2jH0j2(63)
=
; C11G0+
C12H0C
11 jG
0 j
2
+ 2Re(
C12G0H0) +
C22jH0j2(64) With this choice of
Kit can be shown (by straightforward but tedious calculations) that
tr
PC]
K=K
opt
=
C22jH0j2+
vrdet
CjH0j2C
11 jG
0 j
2
+ 2Re(
C12G0H0) +
C22jH0j2(65)
The rst term is independent of
r, hence we get (cf. 7], p. 376)
optr=
s
vdet
CjH0j2C
11 jG
0 j
2
+ 2Re(
C12G0H0) +
C22jH0j2(66) where
is a constant, adjusted so that
Z
;
optr d!= 1 This proves the theorem.
Note that if
Cis singular the optimal
rin (51) can be chosen at will, as long as
Z
;
optr d!= 1 (67)
This is due to the factor det
Cin (51) which vanishes when
Cis singular. Furthermore, when
C
is singular the optimal
Kin (50) simplies to
K
opt
=
; C12C
12 G
0
+
C22H0(68)
We have thus established the following theorem which is a variant of a result given in 6]. See also 2].
Theorem 4. If
Cis singular then the problem min
K
r
Z
;
tr
PC]
d!: any constraint
(69) has the solution
K
opt
=
; C12C
12 G
0
+
C22H0(70)
optrarbitrary (71)
as long as
ugiven by
u
(
t) =
r(
t) +
C12(
q)
C
12
(
q)
G0(
q) +
C22(
q)
H0(
q)
y(
t) (72) is an admissible input.
5 Examples
5.1 Internal Model Control
In Internal Model Control (IMC) the control law is chosen as
u
(
t) =
K(
q)(
rc(
t)
;y(
t)) =
Q(
q)
1
;G(
q)
Q(
q)(
rc(
t)
;y(
t)) (73)
where
Qis some stable transfer function and
Ga model of the true plant
G0. Here
rcdenotes the reference signal to be used in the control application, not to be mixed up with the reference signal
rused in the identication experiment. Note that the control design will not depend on the noise model. Also note that the designed closed-loop system is
G des
c
(
q) =
G(
q)
K(
q)
1 +
G(
q)
K(
q) =
G(
q)
Q(
q) (74) For this 1-dof regulator
Gccoincides with the complementary sensitivity function. From (74) we see that
Q=
Gc=Gshould be large where a raise in the system's gain is desired.
Ideally, that is when
G=
G0, the \best" or \true" IMC controller results:
K
0
(
q) =
Q(
q)
1
;G0(
q)
Q(
q) (75)
In general the model
Gis obtained through identication using
Ndata samples. In that case
G
= ^
GNand the corresponding controller is
^
K
N
(
q) =
Q(
q)
1
;G^
N(
q)
Q(
q) (76)
Neglecting the response from the noise source
ewe obtain the \true" output
y0as
y
0
(
t) =
G0(
q)
K0(
q)
1 +
G0(
q)
K0(
q)
rc(
t) =
G0(
q)
Q(
q)
rc(
t) (77) The actual output resulting from use of the suboptimal controller (76) is
^
y
N
(
t) =
G0(
q) ^
KN(
q)
1 +
G0(
q) ^
KN(
q)
rc(
t) =
G0(
q)
Q(
q)
1 + ~
GN(
q)
Q(
q)
rc(
t) (78) A measure of the performance degradation can be obtained by studying the error signal
~
y
N
=
y0;y^
N. We have
~
y
N
(
t) =
G0(
q)
Q(
q) 1
;1 1 + ~
GN(
q)
Q(
q)
r
c
(
t) (79)
=
G~
N(
q)
1 + ~
GN(
q)
Q(
q)
G0(
q)
Q2(
q)
rc(
t) (80) Using rst-order approximations we get
~
y
N
(
t)
G~
N(
q)
G0(
q)
Q2(
q)
rc(
t) (81) and it follows that the resulting weighting matrix
Cin this case is given by
C
IMC
=
jG0j2jQj4rc0
0 0
(82) Suppose now that we want to solve the problem
min
K r
E
"
y~
2N(
t) :
Z
;
f
u+
ygd!<1
(83)
where
Kand
rrefers to the set-up (10) used in the identication. Theorem 1 then states that the optimal strategy is to use closed-loop experiments with
Kand
rchosen as
K
opt
= arg min
K Z
;
jKj 2
+ 1
j
1 +
G0Kj2vd!(84)
optr /pvrcjG0jjQj2j1 +
G0Koptj2p
1 +
jG0j2(85)
A remark on this choice of reference spectrum is that (for xed
G0and
v)
optrwill be large where either of
rcor
jQjjGdesc =G0j, is large.
5.2 Generalized Minimum Variance Control
In Generalized Minimum Variance Control (GMVC) the goal is to make the closed-loop system behave like
y
0
(
t) =
R(
q)
e(
t) (86) This can be accomplished by using a regulator of the form
u
(
t) =
;H0(
q)
;R(
q)
G
0
(
q)
R(
q)
y(
t) (87) It can be shown that the degradation signal ~
yNcan be written (neglecting errors of order higher than 2)
~
y
N
(
t) =
G~
N(
q) ~
HN(
q)
"
H
0
(q);R(q)
G
0 (q)
;
1
#
R
(
q)
H
0
(
q)
e(
t) (88) leading to a
C-matrix of the form
C
GMVC
=
0
R
H
0
2
"
jH
0
;Rj 2
jG
0 j
2
; H0;R
G0
; H
0
;R
G
0
1
#
(89) Note that
CGMVCis singular. Hence the choice
K opt
y
=
; ;(
H0;R)
=G0;
(
H0;R) +
H0=
H0;RG
0 R
(90) minimizes
"
Ey