Luftkonditionering
(Kyla och Värme)
INSTALLATION MANUAL
Kassett 1-väg
SHEAV
CAC
Installation inomhusdel...3,4,5 Kvävgasfylld...5 Installation dränering...6,7 Elanslutning...8 Felsökning display...9,10 Felsökning trådbunden fjärrkontroll...11,12
Innehåll
Space requirements for indoor
Avoid installing the air conditioner:
In areas where it is exposed to direct sunlight. Close to heat sources.
In damp areas or locations where it could come into contact with water.
(for example rooms used for laundry)
In areas where curtains and furniture could affect the supply and discharge of air.
Without leaving the required minimum space around the unit. (as shown in the drawing)
In scarcely ventilated areas.
On surfaces that are unable to support the weight of the unit without deforming, breaking or causing vibrations during the use of the air conditioner.
In a position that does not enable the condensate drainage pipe to be correctly installed. (at the end of the installation. It is always essential to check the efficiency of the drainage system)
Läs noga igenom denna manual innan installation.
¿Installationen av aggregatet måste utföras av ett ackrediterat kylföretag för att garantin skall gälla.
¿Gör en testkörning av aggregatet tillsammans med brukaren och förklara hur aggregatet fungerar.
¿All yttre elanslutning och avsäkring måste vara utförd enligt lokala föreskrifter.
¿Aggregatet måste installeras med hänsyn till serviceutrymmen som visas nedan.
¿Kontrollera att aggregatet ej har fått några skador under transporten.
¿Var noga med att kontrollera att dräneringen blir rätt utförd och att kondensatet dräneras ur aggregatet.
Installation av inomhusdel
Erforderligt utrymme för aggregatet
Installation av inomhusdel (fortsättning)
Ritning
Unit : mm
Nr. Namn Beskrivning
1 Vätskeledning ø6.35
2 Sugledning ø9.52
3 Dränering OD 29, ID 25
4 Elanslutning -
5 Tilluft -
6 Frånluftsgaller -
Dimension och vikt
Dimension
Inomhusdel
mm
970x135x410
Storlek Panel 1180x25x460
Utomhusdel 790x548x285
Vikt Inomhusdel+Panel
kg 13
Utomhusdel 32.6
Dränering
135 1036
1074 970
280 410
15025 460
1180
Installation inomhusdel (fortsättning)
1 Placera mallen för kassetten där aggregatet skall installeras och märk ut var hålen skall göras.
Note Innan hålen borras bör en kontrollmätning göras så att markeringen stämmer med angivna dimensioner enligt ritning (se föreg sida).
2 Beroende på typ av tak montera erf upphängningsanordning enl bif
Ceiling support Betong
Upphängningsbult(M8)
Gummi
Mutter
Upphängnings- Mutter Sido vy
Inlopp Utlopp 15mm
15mm
Innertak exempel eller likvärdigt.
Ansl sugledning
Ansl vätske- ledning.
Inomhusdelen levereras från fabrik skyddsfylld med kvävgas.
Kvävgasfylld
Installation av dränering
Var noga med att kontrollera att dräneringen blir rätt utförd och att kondensatet dräneras ur aggregatet.
1 I aggregatet ingår ett anslutningsrör för anslutning till ett PVC-rör (ingår ej) med en utv diam av ø32mm.
Kontrollera att anslutningsslangen ej läcker.
2 Anslut röret till dräneringsanslutningen.
Kontrollera att dräneringsanslutningen är försedd med en o-ring.
3 Gör rördragningen så kort som möjligt.
Se till att röret lutar från aggregatet.
4 Isolera och fixera röret enligt bild.
Inom- husdel
Band Isolering
Isolering Isolering
Band(Ingår ej)
Lim Band
Dräneringsrör Flexibel
slang Dräne- rings
ansl
Dräneringen får ej dras uppåt då detta orsakar att dränaget rinner tillbaka och kan orsaka läckage.
Luftning
Undertak Kontrollera att aggregatet är i våg med undertaket.
Installera en luftning enl nedan.
Dräneringsröret skall ej belasta aggregatet utan förses med egen upphängning.
Undertak
300mm eller mindre
Undertak 20mm el mer Om det är nödvändigta att öka höjden på dräneringen, gör detta inom 300 mm från dräneringsanslutningen enl nedan. Max höjd 550 mm, om högre kan detta orsaka läckage.
1~1.5m
Undertak 1/100 el mer
1/100 el mer
550mm el mindre
Drän.rör Flexibel slang
Dräneringsansl.
Drainpipe and drain hose installation
Test av dränering
Testa dräneringen efter att installatinonen är klar.
1 Tag bort panelen.
2 Häll i vatten i kondensvattentråget (vit frigolit) enligt figur.
3 Kontrollera att vattnet rinner ut genom kondensledningens utlopp Obs! kondensvattenpumpen fungerar endast i kylläge.
4 Sätt tillbaka panelen
ANM:Om en gemensam dränering skall göras, se nedanstående.
100mm el mer 1/100 el mer lutning
Luftning
Luftutlopp
Installation av dränering (fortsättning)
Elanslutning 230V / 1-fas / 50Hz
Anslut elkablarna till plintarna enligt nedanstående bild.
Elschema
Inomhusdel
Utomhusdel
Kommunikation Kraftmatning
230V / 1-fas / 50Hz CAUTION Always remember to connect the refrigerant pipes before performing the electric connections.
When disconnecting the system, always disconnect the electric cables before disconnecting the refrigerant pipes.
Always remember to connect the air conditioner to the grounding system before performing the electric connections.
All elanslutning måste utföras i överensstämmelse med lokala regler
Felsökning display
Felindikering
LED Display inomhusdel
Felindikering
LED lampor
Anmärkning
Återställning kraftmatning
X X X
Sensor inomhusdel felaktig
X X X
Sensor värmeväxlare inomhusdel felaktig
X X
Fel på fläktmotor:
(I drift under 450RPM i 15 sekunder)
X X X
Bekräfta ansl av CN73 och CN44Fel på temperatursensor utomhusdel Fel på temperatursensor kondensor
Fel på temperatursensor hetgasledning
X X
Kommunikationsfel från utomhusfel
X X
Till Blinka X Från
Om ett fel uppstår under drift, kommer en eller fler LED-lampor att blinka och aggregatet stannar.
Troubleshooting
LED Display
Felindikering
LED lampor
Anmärkning
Visar självdiagnosfel
1. Sluten EEV* fel 2. Öppen EEV fel
X
3. Köldmedieläckage 2:a gången 4. Hög kondenseringstemperatur 2:a
5. Hög hetgastemperatur 2:a gången
6. Kompressorstopp pga frysning 6:e gången
X
Hög kondensvattennivå
X X
Fel inställning av switchar
X X
Kontrollera inställning(DIP S/W)
EEPROM fel
X
Kontrollera anslutningEEPROM tillva fel Reset tillval
Till Blinka X Från
Felsökning display (fortsättning)
gången
* EEV = Elektronisk expansionsventil
Display Förklaring Anmärkning
Indoor unit Communication Error
Communication Error Indoor/Outdoor unit Communication Time Out Error
60 Packet Over data Indoor unit is not connected
Communication Error between Outdoor Main and Inverter Micom (Occurred after 1 minute detection in Main and Inverter) Indoor Temp. Sensor (Open/Short Error)
Indoor Sensor Error Indoor Unit Eva in Sensor (Open/Short Error)
Indoor Unit Eva in Sensor Separation
Outdoor Temp. Sensor Error (Open/Short Error)
Outdoor Sensor Error COND Temp. Sensor Error (Open/Short Error)
Inverter Compressor Discharge Temp. sensor Error (Open/Short Error)
Power cable miss connection error Indoor Float S/W 2nd Detection
Self Diagnosis Error Outdoor unit - indoor unit communication wire miss connection
(Connected to Power terminal)
Outdoor unit refrigerant Full leakage (Gas leak) Outdoor Fan 1 Error
Outdoor Fan 2 Error Discharge over temperature
Outdoor Unit Protection Control Error
[Inverter] Compressor starting error Primary Current Over Trip error [Inverter] DC PEAK error(O.C) [Inverter] Compressor Rotation error [Inverter] Current Sensor error [Inverter] DC LINK Sensor error [Inverter] EEPROM Read/Write Error
Trådlös fjärrkontroll
Om ett fel uppäcks visas i fjärrkontrollens display.
Om man vill avläsa ev felkoder, tryck på Testknappen.
Utomhusdel
Felsökning trådbunden fjärrkontroll
Troubleshooting (Continued)
Display Förklaring
Indoor unit communication reception error
Communication error between the outdoor and indoor unit Indoor unit temperature sensor (Short/Open)
Indoor unit Eva In sensor (Short/Open) Indoor unit Eva Out sensor (Short/Open) Indoor unit Eva In sensor secession Indoor unit Eva Out sensor secession Indoor Eva In and Out sensor secession error Secondary(Electronic)heater sensor 1 error Secondary(Electronic)heater sensor 2 error Secondary(Electronic)heater sensor 3 error Indoor Float S/W 2nd Detection
Indoor fan error Mixed operation error EEPROM error
EEPROM option setting error Error regarding special sales taxes
Electronic heater discharge temperature protection error Electronic heater windless error
Indoor unit number setting error(The outdoor unit informs the error)