Application of Logical channel in the Profile/timer mode

In document MultiCon CMC-99/141 (Page 144-148)

7. CONFIGURATION OF THE MULTICON CMC-99/141

7.8. LOGICAL CHANNELS

7.8.11. Examples of Logical Channels configuration

7.8.11.9. Application of Logical channel in the Profile/timer mode

Task:

Create the Profile/timer in the logical channel 1 in the edge (once) triggering mode.

The trigger source is the logical channel 2 which is connected to the current input from UI4 module. The profile consists of 4 sections: 1. ramp from 0 to 10 in 5 seconds, 2. constant value 8 in 2 seconds, 3. ramp from 8 to 4 in 3 seconds and 4. constant value 4 in 1 seconds.

The idle value is 0 and looping is disabled.

Solution:

First configure the device as follows. Then connect the current converter to the UI4 module as it is shown in Fig. 7.63 (see also Appendices 8.2. UI4, UI8, UI12, U16, U24, I16, I24 – VOLTAGE and CURRENT MEASUREMENT MODULES).

Fig. 7.79. Example of Profile waveform For the logical channel in the Profile/timer mode:

touch the screen and press the Menu button,press the Device configuration button,enter the Logical channels menu,

using the arrows in the top navigation bar, select any logical channel such as 1,in the Name parameter write Profile,

Mode parameter set as Profile/timer,Source parameter set as P/T1:”Profile 1”,press the Configure source button,

Mode parameter set as edge (once),

Triggering source parameter set as Log.ch.2,

in the Idle value parameter write 0,

press the Section list button,

◦ press the green button at the bottom left side of the screen,

Section num. parameter should be set as 1,in Duration parameter write 0,

Unit parameter set as second,

0 2 4 6 8 10 12

0 2 4 6 8 10 12

Time [s]

Value

Shape parameter set as slope,in the Final value parameter write 10,

◦ press the green button at the bottom left side of the screen,

Section num. parameter should be set as 2,in the Duration parameter write 2,Unit parameter set as second,Shape parameter set as const.value,in the Final value parameter write 8,

◦ press the green button at the bottom left side of the screen,

Section num. parameter should be set as 3,in the Duration parameter write 3,Unit parameter set as second,Shape parameter set as slope,in the Final value parameter write 4,

◦ press the green button at the bottom left side of the screen,

Section num. parameter should be set as 4,in the Duration parameter write 1,Unit parameter set as second,Shape parameter set as const.value,in the Final value parameter write 4,

Looping parameter set as disabled,for Displaying block parameters:

Format parameter set as numeric,

Precision parameter set as 0.0 ,

in Graph low write 0,

in Graph high write 10,

Configuration of logical channel 2 (Triggering source) in the Hardware input mode for the current input is shown in 7.8.11.1. Application of the Logical channel in the Hardware input mode for the UI4 module (for this mode we configure logical channel 2 in this task).

Another method is shown in 7.12.4.1. Application of the Profiles/timers.

7.8.11.10. Application of Logical channel in the Hardware input mode and Data from other channel for FT4 module

See also: Chapter 8.5. FI2. FI4, FT2, FT4 – FLOWMETER MODULES.

Task:

The task is to connect the PNP type sensor, read the measurement from the FT4 Flowmeter hardware input and to display the current Flow and Total flow. The sensor gives 512 pulses per liter of liquid.

Solution:

Before configuring the device according to Fig. 7.80, configure the device as it is shown below.

Fig. 7.80. FT4 module and PNP type sensor connection scheme For the logical channel in the Hardware input mode:

touch the screen and press the Menu button,press the Device configuration button,enter the Logical channels menu,

using the arrows in the top navigation bar, select any logical channel, in this example it will be channel 1,

in the Name parameter write Measurement,

Mode parameter set as Hardware input,

Source parameter set as Inp.A1 : Tacho,

press the Configure source button,

in the Base unit parameter write dm3,

Mode parameter set as Flow/Tacho (1/sec.),

PNP

Power supply

(depending on version)

1 2

8 5 6 7 3 4

SERVICE

+24V DC ±5% (Imax. = 200mA) digital input 0/15..24V DC

RS-485

GND

GND

A+

isolated

FT4 4 pulse inputs + 4 current inputs

n15 n16 n17 n04 n05

n13 n14 n01 n02 n03 n04 n05 n01 n02 n03

n06

n10 n11 n07 n08 n09

n12

GND IN5 IN6 IN7 IN8

4 x 0-20mA

COM4 Inp42 Inp41 COM3 Inp32 Inp31 COM2 Inp22 Inp21 COM1 Inp12 Inp11

in Low Limit parameter write -50000 1/sec.,

in High Limit parameter write 50000 1/sec.,

Counting mode parameter set as with direction input,

Filter parameter set as disable,

Zero time parameter set as 0.1 sec.,

press the Totalizer button,

Reset mode parameter set as from log. channel,Reset source parameter set as Logical channel 3,Hold mode parameter set as from log. channel,Hold source parameter set as Logical channel 4,Counting direction parameter set as from log. channel,Direction source parameter set as Logical channel 5,

Scaling parameter set as linear,

press the Configure scaling button,

in Output unit parameter write dm3/s,

in Input value in Point 1 label write 0 1/sec.,

in Output value in Point 1 label write 0 dm3/s,

in Input value in Point 2 label write 512 1/sec.,

in Output value in Point 2 label write 1 dm3/s,

Format parameter set as numeric,

Precision parameter set as 0.00,

in Graph low parameter write 0 dm3/s,

in Graph high parameter write 100 dm3/s, To display the Total flow:

using the arrows in the top navigation bar, select logical channel 2,

in the Name parameter write Total flow,

Mode parameter set as Data from other channel,

Source parameter set as Log.ch.1:”Measurement”,

Quantity parameter set as totalizer,

Precision parameter set as 0.00,

in Graph low parameter write 0 dm3,

in Graph high parameter write 1000 dm3,

using the arrows in the top navigation bar, select logical channel 3,

in the Name parameter write Reset,

Mode parameter set as Set point value,

Edit button parameter set as enabled,

Format parameter set as binary,

using the arrows in the top navigation bar, select logical channel 4,

in the Name parameter write Strobe,

Mode parameter set as Set point value,

Edit button parameter set as enabled,

Format parameter set as binary,

using the arrows in the top navigation bar, select logical channel 5,

in the Name parameter write Direction,

Mode parameter set as Set point value,

Edit button parameter set as enabled,

Format parameter set as binary,

– all the other parameters should be set on default settings,