• No results found

Low frequency sound pressure fields in small rooms in wooden buildings with dense and sparse joist floor spacings

N/A
N/A
Protected

Academic year: 2021

Share "Low frequency sound pressure fields in small rooms in wooden buildings with dense and sparse joist floor spacings"

Copied!
12
0
0

Loading.... (view fulltext now)

Full text

(1)

Low frequency sound pressure fields in small rooms in wooden

buildings with dense and sparse joist floor spacings

Jörgen Olssona)

Department of Sustainable Built Environment, SP Technical Research Institute of Sweden,Vejdes Plats 3, Växjö, 352 52, Sweden

Andreas Linderholtb)

Department of Mechanical Engineering, Linnæus University, Växjö, 351 95, Sweden

Kirsi Jarneröc)

Department of Sustainable Built Environment, SP Technical Research Institute of Sweden,Vejdes Plats 3, Växjö, 352 52, Sweden

Using wood as the main construction material is a potential solution to achieve sustainable buildings. Previous research has shown that frequencies below 50 Hz are of significant importance for the perception of impact sound by residents living in multi-story buildings having light weight wooden frameworks. The standards used for impact sound

measurements today are developed for diffuse fields above 50 Hz. For instance due to requirements concerning wall reflections, these methods are not applicable for low

frequencies within small rooms. To improve measurement methods, it is important to know the nature of the full sound distribution in small rooms having wooden joist floors. Here, impact sound measurements with microphone arrays are made in two small office rooms having the same dimensions. The rooms represent two extremes in design of joist floors; one with closely spaced wood joists and the other with widely spaced joists. An impact ball is used for excitation the room being measured from the room above. The results show that there are significant variations in the sound pressure, especially in the vertical direction. Here, measurement techniques of impact sound in the low frequency range in small rooms in wooden buildings are evaluated and potential improvements are proposed.

a) email: jorgen.olsson@sp.se b) email: andreas.linderholt@lnu.se c) email: kirsi.jarnero@sp.se

(2)

1 INTRODUCTION

Impact sound measurements according to ISO 140-71 and ISO 717-22 have been shown to give single values that do not correspond well with the user satisfaction in light weight wooden buildings3,4. The AkuLite5 project showed that including frequencies in the range 20-50 Hz improves the correlation between impact sound satisfaction and impact sound measurement results. The methods according to ISO 140-7 and ISO 717-2, are based on diffuse sound theory and are not intended for measurements below 50 Hz in small rooms. According to ISO 140-7 Annex C – Guidance for measurements in low frequency bands, “At least one room dimension should be of one wavelength and another of at least half a wavelength of the lowest band center frequencies”. For the 20 Hz band this will imply at least 17 m in one direction and 8.5 m in another. This is not fulfilled for most office rooms or bedrooms in apartments for instance.

In order to identify the nature of impact sound and its distribution it is valuable to have the full 3D spatial distribution of the sound pressure as a function of time. Practically this implies spatial grid measurements. Simmons6 evaluated spatial sampling methods for low frequency sound measurements for the general improvement of measurement quality. The study covered mainly air borne sound, and included a range of measurement objects. Hopkins7 conducted interesting and detailed low frequency grid measurements of sound insulation between rooms. For instance he suggested that measurements should be taken in corners opposing the sound insulating wall, from where the sound comes. The measurements were due to an air borne sound source, not impact sound with light weight wooden floors.

When it comes to impact sound and grid measurements, Yoo8 et al made detailed sound field analysis of impact sound using an impact ball. The evaluation showed for instance that the Korean standard KS F 2810-2 and Japanese standard JIS 1440-2 in general gives low deviation errors of average values. The flooring in this case was with and without floating floor, on concrete slab with a 62.2 m3 receiving room.

The impact ball (defined in for instance the standard JIS A 1418-29) is used in this study. The impact ball complements the tapping machine in the low frequency range. The impact ball offers good signal to noise ratio in low frequencies for light weight wooden floors with up to 20 dB more signal to noise ratio10 in the lower frequency range 20 – 30 Hz compared to the tapping machine. It offers also excitation characteristics more similar to human feet excitation11,12, compared to for instance the tapping machine.

Here is the sound level norm according to for instance standard ISO 10140-313,14, for impact ball is used. I.e. the average of the Maximum Fast weighted (125 ms), linear (Z) levels (dB ref. 20μPa) denoted LZF,Max, gives the sound pressure level value. Maximum levels are given for

each 1/3 octave. The measurements are corrected for background noise. The results are not corrected against reverberation time; due to it is not a steady state measurement. The principle is that the maximum value should not differ in transient measurement even though the

reverberation after excitation differs. However, there are measurement discrepancies15 stemming from different reverberation times that motivate corrections also when using an impact ball16.

In this study, the focus is to identify the nature of impact sound in small office rooms, having light weight wooden floors which not fulfill the wavelength requirements according to ISO 140-7. The measurements here are made in two office rooms in two different buildings representing the “extremes” in design of light weight joist floors. The first (M-building) has very densely spaced light joists in the flooring. The second (N-building) has sparsely optimized stiff T-shaped beams. The M-building´s rooms have fixed walls with light sound absorbing

suspended ceilings. The rooms in the N-building have light removable walls and heavy suspended ceilings. By having virtually all design parameters different in the “extremes”

(3)

between the two test objects except from the rooms’ sizes makes them suitable for analyzes of the sound field nature and the potential differences.

In this study parallel FRF-measurements with impact hammer were made but are not yet analyzed, for correlation with impact ball. The potential benefits are that the measurement will include a Frequency Response Function (FRF), besides the measured sound insulation. In a potential future were simulation of sound insulation is also simulated in let say a design stage, FRF may be a suitable common language for analyze, correlate and presenting results of sound insulation. By measuring with for instance impact with the tapping machine, this is not possible today, since it is not offering any force spectrum of the excitation.

2 MEASUREMENT OBJECT

The office buildings measured in this investigation are within the buildings named M and N, located at the Linnæus University in Växjö, Sweden. The M-house was built in 2002 and has a wooden joist floor and a few frame parts in steel. The N-building was finished in January 2011.

The plan layouts of the buildings do not differ much with respect to the rooms’ sizes and mutual room locations but the structural design concepts differ with respect to stiffness, separating walls, ceiling and junctions between structural parts.

The M building office’s joist floor has densely standing plank with straight slice cut outs in the middle of the beams as its main load carrying structure. The N house has stiff T shaped joists made of laminated veneer lumber (LVL) as its main load carrying structure of the joist floor. The principles of the joist floors in buildings M and N are shown in Table 1. In both cases, the M and N rooms, the joist floor spans cover the same length as the room lengths.

The building M ceilings are covered with light suspended 20 mm sound absorbing boards and mineral wool between the joists in the ceilings. Building N has 2 x 13 mm gypsum boards in the ceilings. The reverberation time requirement for building N is a maximum of 0.6 s within in the range 160 – 4000 Hz and a maximum of 0.8 Hz in the 125 Hz 1/3 octave. The ceiling in the building M office should fulfill ISO 11654, Class B. Both office rooms are empty during the measurements.

Fig. 1 – Building M has walls going from the floor to the structural ceiling. Building N has walls going up to a suspended ceiling.

(4)

Table 1 – Floor layers build up in buildings M and N, from above and downwards.

M buiding N building

Plastic carpet + gypsum board 13 mm + joist floor + distance crossbar + gypsum board 13 mm + 568 mm airgap + suspended 20 mm sound insulation ceiling board.

Plastic carpet + gypsum board 13 mm + impact sound insulation board + joist floor + 13 mm gypsum board + 480 - 800 mm airgap + suspended ceiling of 2 x 13 mm gypsum boards.

M buiding joist floor N building joist floor

Cross section of joist floor in builing M. The section shows the cut outs locations on the beams. Between the beams there is mineral wool. The load carrying beams are 45 x 220 mm intersection.

Josit floor cross section in builing N. Length of spans up to 7.2 m

M buiding N building

Connection of non-load carrying walls to the joist floor in building M

Typical joint of endings to beam of joist floors in building N.

Non load carrying inner wall

(5)

3 METHOD 3.1 Measurements

The ball excitation was made with an impact ball (standard JIS A 1418-29). The signal evaluated from each microphone point is the max values using the Fast constant of 125 ms time weighing and un-weighted (Z) frequency spectra13. Besides some sensitivity tests, the excitation was made in the middle of the room above each office being measured. The rooms’ dimensions and grid set up are presented in Table 2.

Table 2 – Room dimensions and measurement details.

Room M Room N X - Length of room [m] 4.08 4.075 Y – Width of room [m] 2.25 2.33 Z - Height of room [m] 2.7 2.7 Area [m2] 9.18 9.49 Volume[m3] 24.8 25.6 Grid spacing X 0.30 0.30 Grid spacing Y 0.29 + 0.25 x 7 + 0.29 0.25 Grid spacing Z 0.25 + 0.275 x 8 + 0.25 0.25 + 0.275 x 8 + 0.25 No of grid points X, Y, Z 13, 8, 9 13, 8, 9

Total No of grid points 936 936

Number of measurements per grid point1)

5 5

First calculated room modes Nx Ny Nz _ 1 0 0 0 1 0 0 0 1 41.7 Hz 75.6 Hz 63.0 Hz 41.7 Hz 73.0 Hz 63.0 Hz Reverberation time for center

frequencies [Hz], RT 60 dB2) RT 60 dB2) 16 2.9 4.0 31,5 1.8 1.2 63 1.2 0.7 125 1.1 0.8 250 0.8 0.5 500 0.9 0.6

1- Some measurements with unwanted background noise disturbances or obvious abnormalities removed. 2- Indicative non-standard measurement of reverberation time, made by analyzing band passed impact decays.

4 RESULTS 4.1 Signal quality

The measurements stemming from repeated excitations with 95 % Confidence Intervals (CI 95%) average for all microphone locations are presented in Fig. 2.

(6)

M-building N-building

Fig. 2 – Average 95 % confidence interval in dB (dB ref 20μPa), for 5 consecutive excitations at the same point for all measurements in buildings M and N with an impact ball.

4.2 Sound fields

The average results of impact ball measurements are presented in Table 3 and Fig. 3.

Table 3 – Average results and total CI 95% limit values for impact ball measurements.

M N

LZF,Max 103.0 89.5

2,5 % CI 100.0 84.9

97,5 % CI 105.1 92.2

Fig. 3 – The averages of the measurements in all locations within rooms M and N due to excitations with an impact ball

40 60 80 100 5 50 500 Fq [Hz]

LZ

F,Max M 95% CIN 95% CI M AverageN Average

(7)

3D sliced plots of sound fields stemming from excitations using an impact ball are presented in Fig 4 a and Fig 4 b below. In order to increase the visibility of the sound field characteristics, the scalings are not normalized.

Fig 4a. – Sound fields in the measured offices within the buildings M and N, given in the octave bands of 16, 31.5, 63, Hz. The excitations are made using an impact ball.

(8)

Fig 5b. – Sound fields in the measured offices within the buildings M and N, given in the octave bands of 125, 250 Hz and the total LZF,Max for the range 8-1000 Hz. The excitations are made using an impact ball.

(9)

Fig. 6 – Average LZF,Max values in intersections of the measured rooms. The left figure shows the intersection average level along (X) the room. The right figure shows the average LZF,Max for the interscetion sideways (Y) of the room.

Fig. 7 – Average LZF,Max values in intersection surfaces going from a floor up to the ceiling, for the M and N offices. The blue lines show the total average level values for each room corresponding to intersection averages at 1.2 m height from floors.

4.3 Sampling methods

Simmons6 and also Hopkins7 are proposing a weighting method based on the highest corner sound pressure togheter with the room average as:

𝐿𝑝 = 10 ∙ 𝑙𝑜𝑔10(𝑝𝑐𝑜𝑟𝑛𝑒𝑟 2 + 2 ∙ 𝑝 𝑟𝑜𝑜𝑚 𝑎𝑣𝑒𝑟𝑎𝑔𝑒2 3 ∙ 𝑝𝑟𝑒𝑓2 ) (1) 80 85 90 95 100 105 110 0 1 2 3 4 Room length [m] LZF Max [dB] M M 95% CI N N 95% CI 80 85 90 95 100 105 110 0 0,5 1 1,5 2 Room width [m] LZF Max [dB] M M 95% CI N N 95% CI 80 85 90 95 100 105 0 0,5 1 1,5 2 2,5 Room height [m] LZF Max [dB] M M 95% CI

(10)

In Simmons proposal, 6 samples should be used for precision measurements. Hopkins is using sampling according to ISO 140-4 for air borne sound. Here the tests are made with Simmons6 method with samples having minimum 0.5 m from walls and the range 0.5 - 1.5 above the floors. The corner positions were aiming at 0.5 from walls and floors similar to for instance Hopkins. Due to the discrete grid spacing it implies grid points starting at 0.5 – 0.6 m from the walls and a grid array within 0.525 – 1.35 m in height. The average and six sample average, 95% CI, with maximum corner level according to formula [1] are shown in Figure 8. Yoo et al showed that the Japanese and Korean standards for the impact ball have low deviation errors compared to the room average. Here is the sampling similar to the Japanese standard JIS 1440-2 which was tested, by using samples in the middle of the room and half way to the corner at various (all) heights. The standard is here not fully adapted since the excitation is fixed violating the requirement of different excitation positions. The five sample average, CI 95%, and the deviation errors for the populations are plotted in Figure 8.

4 DISCUSSION AND CONCLUSIONS

The signal quality and repeatability are good for the impact ball within the low frequency range. From 10 – 100 Hz the CI 95% is below 1 dB for 1/3 octaves. This indicates good signal to noise ratio for impact ball excitations for the measured objects. The decrease in the confidence interval within the high frequency of the impact ball measurement data is likely due to less excitation force within the high frequencies.

Figure 8. The left figure is showing the deviation from room average according to Equation 1 for 6 room samples. The right figure is showing the correspondig sampling population according to JIS 1440-2 sample locations, 5 sample average.

In the range higher than 100 – 200 Hz the impact ball gradually loses signal to noise ratio quality. The decrease of CI 95% in low frequencies, below 10 Hz, might be due to that the microphones are not made for measurement in that range.

The total average CI 95% between the 1/3 octave bands with center frequencies at 16 Hz and 250 Hz are 11.9 dB and 12.9 dB respectively for M and N. The spatial differences in LZF,Max

are wide in low frequencies. The spatial parameter that affects the results most here is where in -8 -6 -4 -2 0 2 4 6 10 100 1000 Frequency [Hz] DeviationLZFMax [dB] M M 95% CI N N 95% CI -8 -6 -4 -2 0 2 4 6 10 100 1000 Frequency [Hz] Deviation [dB] M M 95% CI N N 95% CI

(11)

the vertical direction the samples are taken. Around 1.2 m above the floor is the intersection surface having an average value that is the same as for the entire room which is valid for both rooms. The results have similarities to the results by Hopkins7. He observed that the wall corners opposing to the separating wall, when measuring sound insulation in low frequencies, gave the highest values. Here also the highest values are observed in the floor corner opposing to the separating ceiling.

When looking for simplified field measurement values, it seems as a number of samples in the range of 1.0-1.5 m of height would be representative in the office rooms measured (the height of 1.2 m would be close to where a sitting person would have the head in an office room).

However due to the risk of having nodal points in the same height level, it seems, as Yoo8 et al, showed, that the Japanese and Korean standard for average sampling would give better values compared to a room average. The Simmons’ sampling method for precision measurements, offer narrow CI 95% range for low frequency measurements of average values. In this measurement the deviation error was slightly on plus side compared to the room average, while the JIS 1440-2 inspired sampling gave a slightly negative estimation. By taking the average from the four corner positions at the floor (0.5 m from walls and floor) and increasing the sampling height for the room average values to the range 0.8 – 1.9 m above floor, the value according to Equation (1), gives a deviation to the room average value of 0.0 dB for the M measurements and 0.2 dB average for the N measurements. The CI 95% increases here 0.3 dB (average 8 – 500 Hz, octaves, five averages) with this modification.

Since the spatial variation is significant, it might be valuable to have the maximum values as benchmark values by themself. The maximum values are in all measurements found, in one of the floor corners. In small bedrooms of similar design, these corner values would be of more interest than the average values. This is since at sleeping, the head tend to be close to a wall and a corner and mostly rather low in the room. The distance approximately 0.5 m from the walls and floor as suggested by Hopkins and Simmons would probably be suitable field sampling points for corners. It would also correspond to what a sleeping person might be exposed to in similar rooms.

5 ACKNOWLEDGEMENTS

The measurements have been funded by the European Regional Development Fund within the Interreg IV A Project, Silent spaces. The analysis of the results was conducted within the ProWOOD-program, in this project funded by the Swedish Knowledge foundation, Linnæus University and SP Technical Research Institute of Sweden. The Internoise participation was funded by Bo Rydins forksningsstiftelse.

6 REFERENCES

1. ISO 140-7: Acoustics – Measurement of sound insulation in buildings and of building elements – Part 7:Field measurements of impact sound insulation of floors (1998).

2. ISO 717-2: Acoustics – Rating of sound insulation in buildings and of building elements – Part 2: Impact sound insulation (1996).

3. Acoustics in wooden buildings, State of the art 2008. SP Rapport 2008:16.

4. K. Hagberg, P. Thorsson: Uncertainties in standard impact sound measurements and evaluation procedure applied to light weight structures. Proc. 20th Int. Cong. on Acoustics, ICA 2010.

(12)

5. Simmons, Christian, Fredrik Ljunggren, and Klas Hagberg. "Findings from the AkuLite project: New single numbers for impact sound 20-5000 Hz based on field measurements and occupants’ surveys." INTER-NOISE and NOISE-CON Congress and Conference

Proceedings. Vol. 247. No. 3. Institute of Noise Control Engineering, 2013.

6. Simmons, Christian. "Measurement of sound pressure levels at low frequencies in rooms.

Comparison of available methods and standards with respect to microphone positions." SP

Report 1997:27.

7. Hopkins, Carl, and P. Turner. "Field measurement of airborne sound insulation between

rooms with non-diffuse sound fields at low frequencies." applied acoustics 66.12 (2005): 1339-1382.

8. Yoo, Seung Yup, et al. "Measurement of sound field for floor impact sounds generated by

heavy/soft impact sources." Acta Acustica united with Acustica 96.4 (2010): 761-772.

9. JIS A 1418-2: Acoustics Part 2: Method using standard heavy impact sources. Japanese

Industrial Standards Committee, Tokyo, Japan, 2000.

10. Olsson, Jörgen et. al. Low frequency Measurements of Impact Sound Performance in Light Weight Timber Frame Office Buildings. Conference Paper Euronoise 2012.

11. Jeon, Jin Yong, et al. "Review of the impact ball in evaluating floor impact sound." Acta

Acustica united with ACUSTICA 92.5 (2006): 777-786.

12. Späh, Moritz, et al. "Subjective and Objective Evaluation of Impact Noise Sources in

Wooden Buildings." Building Acoustics 20.3 (2013): 193-214.

13. ISO 10140-3:2010: Acoustics – laboratory measurement of sound insulation of building elements. Part 3: Measurement of impact sound insulation.

14. ISO 10140-5:2010: Acoustics – laboratory measurement of sound insulation of building elements. Part 5: Requirements for test facilities and equipment.

15. Ho, Jeong Jeong. "The effect of receiving room sound field on the impact ball sound pressure

level." The Journal of the Acoustical Society of America 131.4 (2012): 3321-3321.

16. Jeong, JeongHo, JeongUk Kim, and WooJin Yang. "Sound field correction of receiving room

on heavy/soft impact sound." INTER-NOISE and NOISE-CON Congress and Conference

References

Related documents

46 Konkreta exempel skulle kunna vara främjandeinsatser för affärsänglar/affärsängelnätverk, skapa arenor där aktörer från utbuds- och efterfrågesidan kan mötas eller

This result becomes even clearer in the post-treatment period, where we observe that the presence of both universities and research institutes was associated with sales growth

Data från Tyskland visar att krav på samverkan leder till ökad patentering, men studien finner inte stöd för att finansiella stöd utan krav på samverkan ökar patentering

The increasing availability of data and attention to services has increased the understanding of the contribution of services to innovation and productivity in

The aim of this thesis, Wooden objects in historic buildings: Effects of dynamic relative humidity and temperature, was to contribute to the understanding of how indoor envi-

2) Papers II and III aimed to relate damage of painted wooden objects to past and present indoor environments in historic buildings, starting with whether such damage to

To eliminate the dispersion errors from wave propagation a second test is made using the standard courant condition (for a second order FDTD scheme staggered in space and time) as

The EU exports of waste abroad have negative environmental and public health consequences in the countries of destination, while resources for the circular economy.. domestically