Systematic Control Configuration Selection of Secondary Heating Systems: A Case Study

N/A
N/A
Protected

Academic year: 2022

Share "Systematic Control Configuration Selection of Secondary Heating Systems: A Case Study"

Copied!
1
0
0

Loading.... (view fulltext now)

Full text

(1)

Systematic Control Configuration Selection of Secondary Heating Systems - A Case Study.

Contact: Miguel Castaño (miguel.castano@ltu.se)

Wolfgang Birk (wolfgang.birk@ltu.se) Funded by:

sourceforge.net/projects/promovis

Analysis of the subsystem formed by the tank of warm water

• The recovery of energy from secondary sources is essential for the operation of modern pulp & paper mills.

• An efficient secondary heating system reduces the dependency on primary heating with fossil fuel.

• Secondary heating has important influence on costs and the environmental impact.

• The topological complexity of such a process hinders the achieving of control goals, being operation often far from optimal.

Conclusions

• The cause of the oscillations exhibited by the

system were found, and the control structure was redesigned.

• This case-study validates the analysis methods introduced in [1] .

• This study illustrates the potential of the software tool ProMoVis, introduced in [2].

The secondary heating system at BillerudKorsnäs Karlsborg AB

Analysis of the secondary heating system

Miguel Castaño Arranz Wolfgang Birk

Petter Asplund

Johan Karlsson Rönnberg

Luleå University of Technology Luleå University of Technology Optimation AB

K.Al.Des

Motivation

• The system exhibited oscillations in certain

operating conditions where the root cause was hard to identify.

• The methods introduced in [1] for the structural analysis of complex processes have been used.

• These methods are integrated in the software tool ProMoVis, recently introduced in [2].

• Conclusions from the analysis:

1. The level at the tank (Level_WT) should be controlled with the valve u_1.

2. The temperature at the exit of the tank

(Temp_WT) should be controlled with the valve u_5.

3. There are significant perturbations coming from the loops which are using the valves u_2 and u_7.

Validation of the analysis with plant experiments

• The change of certain setpoints in the plant revealed loop interaction predicted by the analysis.

[1] M. Castaño, W. Birk, New methods for interaction analysis of complex processes using weighted graphs, Journal of Process Control, Volume 22, Issue 1,

[2] W. Birk, M. Castaño, A. Johansson, An application software for visualization and control configuration selection of interconnected processes, Control Engineering Practice, Volume 26, May 2014, Pages 188-200.

Control structure at the secondary heating system prior to the studies.

References

Related documents

The data used for calibration and validation of the load model was supply temperature, return temperature, mass flow and volume flow out from the CHP-plant Idbäcken in Nyköping to the

The aim of this paper is to report new results on recently suggested methods for the analysis of complex processes. These methods aid the designers in comprehending a process

- combine both theories in order to obtain methods for the analysis of industrial processes which show up causal and functional relationships describing the propagation of energy in

Following a stepwise procedure, the control configuration has been designed for the Secondary Heating System and a controller synthesized and tested: i) a decentralized

A new Interaction Measure for Control Configuration Selection is introduced under the name Prediction Error Index Array (PEIA), which aids in the selection of a structurally

Considering the adaptive translational thrust vector RBFN control system and the globally persistent exogenous unmatched uncertainty, from Figure 6.21 it can be observed that

192 There is no information about commercial support, any discussion forums for users or any companies currently using the software. 193 It is possible to subscribe to a few

By applying a control strategy where the ground source heat pump is used to cover the full space heating demand instead of only being operational during a period between 1 st