UIE WG 2 POWER QUALITY: FURTHER WORK AND RESEARCH ON VOLTAGE DIP IMMUNITY OF EQUIPMENT AND INSTALLATIONS

(AFTER THE CIGRE/CIRED/UIE JOINT WG C4.110)

S. Djokic

(1)

, M. Bollen

(2)

, K. Van Reusel

(3)

, R. Neumann

(4)

, K. Stockman

(5)

, J. Milanovic

(6)

(1)

The University of Edinburgh, UK

(2)

Luleå University of Technology and STRI AB, Sweden

(3)

Katholieke Universiteit Leuven, Belgium

(4)

Qualitrol, UK

(5)

Howest, Belgium

(6)

The University of Manchester, UK

ABSTRACT: In October 2009, UIE established Working Group 2 (WG2) to work in the area of Power Quality and to continue with the dissemination and further development of the results produced by the former joint CIGRE/CIRED/UIE WG C4.110. The final results of the work in UIE WG2 will be presented in May 2012 at the XVII UIE Congress in St. Petersburg, including the delivery of a Tutorial on Voltage Dip Immunity of Equipment and Installations, as well as the presentation of the three papers on relevant topics. This abstract briefly summarizes one of the considered topics – the identified areas where further work and research on voltage dip immunity of equipment and installations is needed. Full paper will discuss this subject in more detail.

INTRODUCTION

The Joint Working Group (JWG) C4.110, which was jointly sponsored by CIGRE, CIRED and UIE, was active between 2006 and 2009. The JWG C4.110 has considered and discussed a number of aspects of immunity of equipment and installations against voltage dips, and produced a Technical Report/Brochure, which is distributed by both CIGRE and UIE, [1]. In order to continue with the dissemination and further development of the results produced by the JWG C4.110, the UIE established Working Group 2 (WG2) in the area of Power Quality in October 2009. The final results of the work in UIE WG2 will be presented at the XVII UIE Congress in St. Petersburg in May 2012, for which three papers and a tutorial are planned and submitted. This abstract briefly summarizes one of the proposed papers, which will discuss the general need and specific areas where further work and research on voltage dip immunity of equipment and installations is needed.

NEED FOR FURTHER WORK

The JWG C4.110 and its successor, UIE WG2, produced a number of important results

related to the assessment and improvement of voltage dip immunity of equipment and

installations, including a methodology for a detailed description of voltage dips, an overview

of the voltage dip immunity of typical equipment and devices, a world-wide voltage dip

statistics database, a discussion of the economics of voltage dip immunity, the

recommendations for testing the equipment against voltage dips, a systematic method for

quantifying the immunity of an industrial process, and a practical specification of voltage dip

immunity classes, criteria and labels, [1]. Although much has been achieved, some issues

have not been fully addressed (mainly due to the lack of the required resources), other issues

have not been successfully resolved and, additionally, a number of new issues arose from the

performed work. Accordingly, the proposed paper will discuss those issues and topics related

to voltage dips and assessment of dip immunity of equipment/processes that should receive

more attention in the future. Some of the suggested work is most appropriate for academic

studies, while in other cases practical contributions from industry are advised.

(2)

CHARACTERISATION AND CLASSIFICATION OF VOLTAGE DIP EVENTS The JWG C4.110 introduced “Dip Segmentation Method” as a more detailed approach for the description and characterisation of voltage dips, in which a general dip event is divided into transition segments and event segments. The characteristics of event segments are well understood, while further work is needed to develop methods for automatic detection of transition segments and for quantifying their characteristics. The JWG C4.110 also proposed three general types of voltage dips: Type I, Type II and Type III, corresponding to dips with a significant drop in rms magnitude in one, two and three phase-to-neutral voltages, respectively. Further work is needed in order to include additional dip characteristics into the proposed methodologies for description and classification of voltage dips, as well as to identify typical relationships between voltage magnitude unbalance and voltage phase angle unbalance from the statistics on different types (and different causes) of voltage dips.

ASSESSMENT OF EQUIPMENT AND PROCESS DIP IMMUNITY

More information is needed on the impact of repetitive dips (e.g. dips due to successful reclosing operation) on equipment immunity. Further work is needed to quantify the impact of pre-dip voltage and source impedance on equipment dip immunity, as well as on equipment malfunction criteria and restarting mechanisms/times after dip-caused tripping. The concept of Process Immunity Time (PIT) should be validated for various industrial applications, particularly how the PIT analysis may help to quantify the economic losses due to voltage dips. Further work is also needed to assess typical immunity levels of well-designed industrial installations and to understand equipment/process immunity to other power quality disturbances, such as voltage swells and long duration overvoltages and undervoltages.

TESTING AND REPRESENTATION OF EQUIPMENT/PROCESS DIP IMMUNITY The JWG C4.110 and UIE WG2 made a careful distinction between characterisation testing and compliance testing. For characterisation testing of three-phase equipment, "Voltage Tolerance Curves" are recommended as a suitable “format” for the representation of equipment dip immunity. For compliance testing, it is recommended that testing procedures include only remaining/residual voltage and duration (representing typical expected voltage dips). It is also suggested to include Type III dips in compliance tests, as the world-wide dip statistics confirmed that a significant number of recorded dips are balanced Type III dips. The economic consequences of including Type III dips in the compliance testing is another important issue, which should be considered in future together with the analysis of suitability of different test voltage vectors for representing Type I and Type II dips in tests. Further work and research is also needed in order to assess the errors made by applying a set of simplified test vectors that are approximations of actual voltage dips, and to devise new testing procedures for multiple/repetitive dip events, multistage dips and dips due to motor starting.

OTHER SUGGESTIONS FOR FURTHER RESEARCH ON VOLTAGE DIPS

Due to the space limitation for this abstract, the other suggestions for further research on voltage dip immunity will be presented and discussed in the full version of the paper.

CONCLUSION

The proposed paper will provide an in-depth analysis of the areas for further work and research on voltage dip immunity of equipment and installations suggested by JWG C4.110 and UIE WG2, including their discussion in the context of the future “Smart Grids”.

REFERENCES

1.

CIGRE/CIRED/UIE Joint Working Group C4.110 Voltage dip immunity of equipment and installations// CIGRE Technical Brochure TB No. 412. April 2010. [Available Online]

http://www.uie.org/powerquality, http://www.e-cigre.org/

References

Related documents

The following main recommendations are formulated by the UIE WG2 to the equipment manufacturers: a) voltage dip immunity should be considered at an early stage of design and

Starting with the nominal process parameter value p nom (controlled by the device), a supply voltage interruption is assumed to occur at t 1. As a result, the process

46 Konkreta exempel skulle kunna vara främjandeinsatser för affärsänglar/affärsängelnätverk, skapa arenor där aktörer från utbuds- och efterfrågesidan kan mötas eller

The increasing availability of data and attention to services has increased the understanding of the contribution of services to innovation and productivity in

Syftet eller förväntan med denna rapport är inte heller att kunna ”mäta” effekter kvantita- tivt, utan att med huvudsakligt fokus på output och resultat i eller från

Närmare 90 procent av de statliga medlen (intäkter och utgifter) för näringslivets klimatomställning går till generella styrmedel, det vill säga styrmedel som påverkar

• Utbildningsnivåerna i Sveriges FA-regioner varierar kraftigt. I Stockholm har 46 procent av de sysselsatta eftergymnasial utbildning, medan samma andel i Dorotea endast

Industrial Emissions Directive, supplemented by horizontal legislation (e.g., Framework Directives on Waste and Water, Emissions Trading System, etc) and guidance on operating