Monitoring air quality indicators and energy consumption in Dalarnas Villa during operation of a demand-controlled exhaust ventilation system

N/A
N/A
Protected

Academic year: 2022

Share "Monitoring air quality indicators and energy consumption in Dalarnas Villa during operation of a demand-controlled exhaust ventilation system"

Copied!
3
0
0

Loading.... (view fulltext now)

Full text

(1)

Student Thesis

Master’s level

Monitoring air quality indicators and energy

consumption in Dalarnas Villa during operation of a demand-controlled exhaust ventilation system

Author: Ian Garman and Ahmad Haj Ahmad

Supervisor: Jonn Are Myhren

Examiner: Jingchun Shen

Subject/main field of study: Energy Efficient Built Environment

Course code: EG3020

Credits: 15

Date of public presentation/examination: 2019-06-04

At Dalarna University, you are able to publish your student thesis in full text in DiVA.

The publishing is Open Access, which means your work will be freely accessible to read and download on the internet. This will significantly increase the dissemination and visibility of your student thesis.

Open Access is becoming the standard route for spreading scientific and academic information on the internet. Dalarna University recommends that both researchers as well as students publish their work Open Access.

I give my/we give our consent for full text publishing (freely accessible on the internet, Open Access):

Yes ☒ No ☐

Dalarna University – SE-791 88 Falun – Phone +46 23-77 80 00

(2)

Abstract:

A real-world study was undertaken of the indoor air quality in a recently-built single family home in central Sweden, to establish whether demand controlled ventilation provided superior interior conditions, when compared with other air supply strategies, including the standard used by the Swedish buildings regulator.

The property was highly airtight, with ventilation achieved using a forced exhaust system.

Extraction was possible from all rooms of the house, and using a Renson Healthbox air handling unit, the rates of air flow from each room could be adjusted either according to a time schedule, or under demand control according to the unit’s sensing of the air quality in individual rooms.

Five ventilation modes were evaluated, each for a period of 24 hours. Occupancy of the house was standardised, with test participants. Two separate air quality monitors were deployed to verify whether measurements made at the air handling unit were

representative of the conditions that occupants experienced. Key measurements were the stable level of carbon dioxide overnight in an occupied double bedroom and the time taken for that room to refresh to background CO2 level the following day. The time taken for a kitchen/living room to similarly refresh was also examined.

The study found that demand controlled ventilation achieved indoor air quality – assessed on carbon dioxide concentration – comparable with rates of fixed ventilation far greater than the regulated standard. In doing so, the air volume exchanged over a representative day was 33 % less than that standard, providing for significant energy savings.

The parallel monitoring of air quality inside the room and via the air exhaust duct showed noticeable variation, but indicated the air handling unit under demand control would never ventilate insufficiently, based on its internal CO2 sensors.

Keywords:

Ventilation, demand control, airflow, frånluft, exhaust, carbon dioxide, CO2, indoor air quality, IAQ, air monitoring, villa, single family house, småhus, energy efficiency

(3)

Anything beyond this, the teacher’s directives apply.

References

Related documents

Since many epidemiological studies of health effects from ambient levels of nitrogen dioxide or PM10 build on one-pollutant models (did not control for other components), the

The natural division of the underground train station is into three zones: the two ticket halls and the platform area.. In each of the ticket halls only tracer gas B was emitted

Further, the main difference of 3DkNN algorithm is that data mule is both the centre point for query origination and the point-of-interest, in opposite to the algorithms described

This confirms the findings of Fu and Wu (2015), where it was stated that a hybrid ventilation system normally includes three major components: an acquisition component

In view of this, the indoor air quality (IAQ) and the occurrence of selected organic compounds were investigated in newly built low-energy preschools in order to evaluate whether

In the worst case, twenty minute intervals between sensor control signals, the total amount of poor IAQ during the investigated time period adds up to approximately 87 hours

Support processes in industrial energy systems, such as ventilation, heating and cooling systems, are important issues in industrial premises as they are related both to energy

To have the largest impact on the buildings energy consumption the simulated living filter or filters should be placed in a conference room which is often used by many people at