• No results found

PFC-design for frequency converter

N/A
N/A
Protected

Academic year: 2021

Share "PFC-design for frequency converter"

Copied!
74
0
0

Loading.... (view fulltext now)

Full text

(1)

Department of Science and Technology Institutionen för teknik och naturvetenskap

Linköping University Linköpings universitet

g n i p ö k r r o N 4 7 1 0 6 n e d e w S , g n i p ö k r r o N 4 7 1 0 6 -E S

PFC-design for frequency

converter

David Kantzon

2015-11-30

(2)

PFC-design for frequency

converter

Examensarbete utfört i Elektroteknik

vid Tekniska högskolan vid

Linköpings universitet

David Kantzon

Handledare Lars Backström

Examinator Anna Lombardi

(3)

Detta dokument hålls tillgängligt på Internet – eller dess framtida ersättare –

under en längre tid från publiceringsdatum under förutsättning att inga

extra-ordinära omständigheter uppstår.

Tillgång till dokumentet innebär tillstånd för var och en att läsa, ladda ner,

skriva ut enstaka kopior för enskilt bruk och att använda det oförändrat för

ickekommersiell forskning och för undervisning. Överföring av upphovsrätten

vid en senare tidpunkt kan inte upphäva detta tillstånd. All annan användning av

dokumentet kräver upphovsmannens medgivande. För att garantera äktheten,

säkerheten och tillgängligheten finns det lösningar av teknisk och administrativ

art.

Upphovsmannens ideella rätt innefattar rätt att bli nämnd som upphovsman i

den omfattning som god sed kräver vid användning av dokumentet på ovan

beskrivna sätt samt skydd mot att dokumentet ändras eller presenteras i sådan

form eller i sådant sammanhang som är kränkande för upphovsmannens litterära

eller konstnärliga anseende eller egenart.

För ytterligare information om Linköping University Electronic Press se

förlagets hemsida

http://www.ep.liu.se/

Copyright

The publishers will keep this document online on the Internet - or its possible

replacement - for a considerable time from the date of publication barring

exceptional circumstances.

The online availability of the document implies a permanent permission for

anyone to read, to download, to print out single copies for your own use and to

use it unchanged for any non-commercial research and educational purpose.

Subsequent transfers of copyright cannot revoke this permission. All other uses

of the document are conditional on the consent of the copyright owner. The

publisher has taken technical and administrative measures to assure authenticity,

security and accessibility.

According to intellectual property law the author has the right to be

mentioned when his/her work is accessed as described above and to be protected

against infringement.

For additional information about the Linköping University Electronic Press

and its procedures for publication and for assurance of document integrity,

please refer to its WWW home page:

http://www.ep.liu.se/

(4)

Abstract

Department of Science and Technology

Master of Science in Electrical Engineering and Design

by David Kantzon

This thesis deals with power factor correction for three-phase systems. A boost-buck topology was described, modeled and then simulated in MATLAB/Simulink. The sim-ulation results show that the system provides a power factor over 99% over the tested power output range. Moreover, the harmonic injection concept was introduced which reduces the total harmonic distortion to 8.72% at full output power. A prototype system was also built using an FPGA for the control system. The prototype did not provide the performance seen in simulation but showed that the method is valid and does provide a higher power factor when used.

(5)

I would like to thank Syncore Technologies AB for providing this opportunity to apply and expand my knowledge in a wide variety of topics. Without the tip from Elias Olsson I probably would not have ended up here and it is much appreciated. Furthermore, I would also like to thank Lars Backstr¨om, Anna Lombardi and Kjell Karlsson for providing guidance and support during my work. I would also like to thank the people at Heltia AB for a warm welcome and lots of tips and tricks for my future work. My brother has kept my spirits up during the work as well as my friends Rickard Hedlund and Sebastian Lahti. The latter two also made sure I did not go up in smoke during testing.

Last but not least, I highly appreciate the input and help I have received from Daniel Forsberg during my work.

(6)

Abstract i

Acknowledgements ii

List of Figures vi

List of Tables vii

Abbreviations viii

1 Introduction 1

1.1 Introduction. . . 1

1.2 Purpose . . . 2

1.3 Methodology . . . 2

1.4 Scope and limitations . . . 3

1.5 Thesis outline . . . 3 2 Background Theory 4 2.1 Frequency converter . . . 4 2.2 IEC 61000-3-2 Standard . . . 5 2.3 Passive rectifiers . . . 6 2.4 Active rectifiers . . . 8

2.4.1 The single-switch DCM boost rectifier . . . 9

2.4.1.1 Variable frequency PWM . . . 12

2.4.2 Harmonic Injection . . . 13

2.5 The buck converter . . . 18

2.6 Complete system . . . 19

3 Modeling and Simulation 20 3.1 Modeling . . . 20

3.1.1 Boost converter small signal model . . . 21

3.1.2 Boost converter control-loop . . . 24

3.1.3 Buck converter small signal model . . . 27

3.1.4 Buck converter control-loop . . . 28

4 FPGA 30 4.1 Overview . . . 30

(7)

4.2 Fixed point representation . . . 31

4.3 Block description . . . 33

4.3.1 Variable gain controller . . . 33

4.3.2 PI controller . . . 34 4.3.3 Mixer . . . 34 4.4 PC interface . . . 36 5 PCB design 37 5.1 Layout . . . 37 5.2 Hardware choices . . . 38

5.2.1 High power components . . . 38

5.2.1.1 Boost inductance . . . 38

5.2.1.2 Bus capacitance . . . 39

5.2.1.3 Buck inductor . . . 40

5.2.1.4 Buck output capacitor. . . 41

5.2.1.5 Power semiconductors . . . 41

5.2.2 Low power components . . . 42

5.2.2.1 FPGA. . . 42 5.2.2.2 ADC . . . 42 5.2.2.3 Gate Drive . . . 42 5.2.2.4 Voltage sensors . . . 43 5.2.2.5 Current sensors . . . 43 5.2.2.6 OP-amp buffers . . . 43

5.2.2.7 Auxiliary power supply . . . 43

5.2.2.8 Isolated PC interface . . . 44

5.2.2.9 Small parallel rectifier . . . 44

6 Evaluation 45 6.1 Equipment . . . 45

6.2 Low voltage testing . . . 46

6.2.1 Test 1: Aux PSU . . . 46

6.2.2 Test 2: FPGA, ADC and gate-drive function . . . 46

6.2.3 Buck converter control-loop . . . 47

6.3 High voltage testing . . . 47

6.3.1 Test 1: Soft-start circuit . . . 47

6.3.2 Test 2: Buck converter with 230/133 V input . . . 48

6.3.3 Test 3: Buck converter with 400/230 V input . . . 48

6.3.4 Test 4: Full system test with boost engaged, 400/230 V input . . . 48

6.3.5 Test 5: Soft-start with higher delay. . . 49

6.3.6 Test 6: Full system test, no harmonic injection . . . 50

6.4 Test 7 . . . 51

7 Result and discussion 52

8 Improvements 53

(8)

A Formulae 55

A.1 Critical power . . . 55

B Simulation models 57 B.1 PWM generation . . . 57

B.2 Duty cycle limiting . . . 59

B.3 Main model . . . 60

B.4 Variable gain and load model . . . 61

(9)

2.1 Simplified schematic of frequency converter . . . 4

2.2 Single phase rectifier with LC-filter and resistive load. . . 7

2.3 Phase voltage (blue) and input current (red) . . . 7

2.4 Three-phase diode bridge with boost converter output stage . . . 8

2.5 Different conduction modes in switching converters . . . 9

2.6 Single switch DCM rectifier . . . 10

2.7 Average current for M=1.5 and 2 . . . 11

2.8 Simplified view of harmonic injection . . . 14

2.9 Duty cycle variation during half a line period . . . 15

2.10 Phase current with no injection . . . 16

2.11 THD with no injection . . . 16

2.12 Phase current with injection index m = 0.088π . . . 17

2.13 THD with injection index m = 0.088π . . . 17

2.14 Buck converter . . . 18

2.15 DCM boost rectifier with buck output stage . . . 19

3.1 Small signal model of DCM boost rectifier . . . 21

3.2 Duty cycle as a function of output power . . . 23

3.3 Static gain as a function of output power . . . 23

3.4 Fitting curve for Kp . . . 24

3.5 Input current waveform at Po = 750 W . . . 26

3.6 Input current waveform at Po = 1500 W . . . 26

3.7 Input current waveform at Po = 3000 W . . . 26

3.8 Buck converter small signal model . . . 27

4.1 Simplified overview of system layout . . . 31

4.2 Block diagram of variable gain controller. . . 33

4.3 Block diagram of PI controller . . . 34

4.4 Simplified overview of system layout . . . 34

4.5 Converter PC interface . . . 36

5.1 3D view of PCB . . . 37

A.1 DC/DC boost converter . . . 55

B.1 Sawtooth wave, control voltage (dashed) and resulting PWM signal. . . . 57

B.2 PWM module implementation. . . 58

B.3 Duty cycle limiter implementation . . . 59

(10)

2.1 IEC 61000-3-2 harmonic limits . . . 5

3.1 Converter parameters . . . 23

3.2 Test of variable gain controller . . . 25

3.3 Voltage drop at load transients . . . 28

3.4 Voltage regulation at different loads . . . 28

4.1 PC interface control parameters . . . 36

6.1 Test equipment . . . 45

(11)

LAH List Abbreviations Here PCB Printed Circuit Board

IGBT Insulated Gate Bipolar Transistor

MOSFET Metal Oxide Semiconductor Field Effect Transistor ADC Analog to Digital Converter

PSU Power Supply Unit MATLAB Matrix Laboratory

DCM Discontinuous Conduction Mode CrCM Critical Conduction Mode CCM Continuous Conduction Mode PFC Power Factor Correction PF Power Factor

THD Total Harmonic Distortion SMPS Switch Mode Power Supply FPGA Field Programmable Gate Array PWM Pulse Width Modulation

OP-amp OPerational Amplifier

(12)

Introduction

1.1

Introduction

Modern power supplies have many requirements that have to be met. Since the advent of the AC transformer and the switching power supplies that followed much research has been done in order to improve power capacity, power density, efficiency and voltage regulation. In later years there has also been an increase in the research regarding clean power. Clean power in this case does not refer to the method used to produce the power but to the waveform of the input currents.

Passive rectification using diode bridges is a simple way of achieving AC to DC conversion but it introduces large amounts of distortion. This is due to the diodes being reverse biased for a large portion of the line voltage period. The diodes only conduct when the voltage exceeds that of the output filter capacitors which results in pulsed input currents used to charge the capacitor.

In order to alleviate this problem power factor correction (PFC) circuits can be intro-duced. These can be either passive or active. Passive PFC circuits are fairly simple to design but offer poor performance. Active PFC circuitry on the other hand uses a switch-mode power supply (SMPS) either after the rectifier bridge or with the switches integrated into the bridge legs to achieve the desired function. The added circuitry is controlled in such a way that the line current tracks the input voltage making any subsequent circuitry appear as a resistive load to the power source. Another important aspect is that the output voltage can be controlled as opposed to the passive solutions.

(13)

Furthermore, the use of a switched power supply allows for smaller filter components thus increasing the power density. On the other hand, active PFC circuits demand an increased control complexity in order for the desired functionality to be achieved.

1.2

Purpose

The aim of this project is to design and construct a PFC circuit which will power a frequency converter. As it stands today, the frequency converter is powered by single phase AC voltage which is rectified in order to produce the DC voltage used in the system. Syncore Technologies AB would like the system to be powered from three-phase AC in order to increase the available power. The three-phase AC/DC converter will replace the current single phase AC input and rectification circuit and provide the DC link voltage between the three-phase power input and frequency converter. It should also provide PFC functionality.

The PFC converter will be powered by standard 400/230 V 50 Hz three-phase mains and should provide a variable output voltage between 100-500 V. Available power out-put should be 3 kW over the outout-put range but is subject to change with regards to the availability of non-custom commercial components capable of handling the required currents and voltages. Moreover, the control system is to be implemented in an FPGA in order to facilitate later integration with the frequency converter.

The converter should have a power factor of 99% or better and comply with the IEC 61000-3-2 class A standard regarding line current harmonics.

1.3

Methodology

A literature study is conducted in order to build an understanding of available methods for power factor correction. One or two of these methods are then selected with respect to desired functionality and studied further. The circuit chosen for construction is then implemented first in simulation and then in hardware.

(14)

MATLAB and Simulink SimPowerSystems is used for circuit and control simulation. Altium Designer will be used to design the circuit board. For writing and testing VHDL code Quartus II is used.

1.4

Scope and limitations

Some modeling of the chosen converter system will be done in order to obtain necessary information. Advanced modeling and control methods are beyond the scope of this thesis. Instead the control methods employed will be ones suggested and evaluated with successful results in literature. The chosen architecture will be implemented in hardware and the control system in an FPGA environment.

Modelling of the frequency converter is a whole topic in itself and for the sake of sim-plicity it will be treated as a load for the AC/DC converter.

1.5

Thesis outline

Chapter 2 deals with general theory on the topic of AC-DC conversion as well as more detailed analysis of the chosen converter/converters. Chapter 3 details modelling of the converter/converters and the design of the control system. Chapter 4 gives an insight into the choice of digital vs analog control as well as how the control system and other blocks were implemented in code. Chapter 5 describes the process of specifying components and some segments with light theoretical background. Chapter 6 is a review and comparison of live and simulated results.

(15)

Background Theory

2.1

Frequency converter

When there is a need to supply a system with alternating current of a different frequency, a frequency converter is used. The converter utilizes a DC-link voltage and semicon-ductor switches that are controlled with a sinusoidal PWM pattern. By changing the frequency of the control signal the frequency of the output voltage is also changed. Figure 2.1 shows a simplified schematic of a frequency converter. Other common de-nominations are inverter or variable speed drive.

Figure 2.1: Simplified schematic of frequency converter

(16)

2.2

IEC 61000-3-2 Standard

In later years there has been an increase in the adoption of more stringent standards governing the effects of power supplies on the mains network. One of these is the IEC 61000-3-2 standard which provides limits on the levels of harmonic currents imposed by a system which draws up to 16 A per phase. There are several different classes of equipment and the limits referenced here will be the Class A ones for balanced three-phase equipment. Table 2.1 shows the limits for individual harmonics up to the 40th harmonic [1].

Harmonics [n] Limit [A]

3 2.3 5 1.14 7 0.77 9 0.4 11 0.33 13 10.21 15 ≤ n ≤ 39 0.15 x 15/n Even harmonics 2 1.08 4 0.43 6 0.3 8 ≤ n ≤ 40 0.23 x 8/n

(17)

2.3

Passive rectifiers

The most common method of obtaining a DC voltage from an AC source is to use a diode rectifier. The rectifier circuit is commonly followed by an LC-filter which produces a smoother voltage waveform. Although simple and fairly efficient these circuits distort the input current introducing a phase displacement relative to the input voltage as well as harmonics. The harmonics arise from the fact that the diodes only conduct when the input voltage is higher than the output voltage. This creates peak currents centered around the peak of the input voltage. Another drawback of these circuits is that there is no ability to control the output voltage. Figure2.2shows a single phase rectifier circuit with an LC-filter powering a resistive load and Figure2.3 shows the phase voltage and input current waveforms.

The power factor of a circuit is the product between displacement- and distortion power factor where the two parts are defined as:

Displacement PF = P S =

Real power

Apparent power = cos(φ) (2.1)

Distortion PF = q 1 1 + T HD2

i

(2.2)

Resulting in a total power factor of:

PF = cos(φ)q 1 1 + T HD2

i

(2.3)

In equation 2.3 φ denotes the phase displacement between voltage and current. T HDi

is the total harmonic distortion of the input current which is defined as

T HDi=

pP∞ n=2In2

I1

(2.4)

(18)

Figure 2.2: Single phase rectifier with LC-filter and resistive load

Figure 2.3: Phase voltage (blue) and input current (red)

A circuit where the voltage and current are in phase with no distortion has a PF of 100%. In the diode rectifier there is both a phase displacement as well as harmonic currents which results in a decreased power factor. Single-phase rectifiers with LC-filters can give a maximum PF of 90%. Three-phase diode rectifiers offer a better inherent power factor. Although more efficient than the single-phase variant the maximum power factor is still only around 95% and there is no control of the output voltage [3].

(19)

2.4

Active rectifiers

To enable a variable output voltage, common DC/DC converters can be connected to the rectifier output. The addition of a converter improves the voltage regulation and also enables matching with different mains voltages while maintaining desired output voltage.

Figure 2.4: Three-phase diode bridge with boost converter output stage

Figure2.4shows a three-phase rectifier with a boost converter added to the output as an example. Depending on the application a step-up or step-down converter may be used as well as their transformer isolated versions. While solving the problem of variable output voltage these circuits still suffer from distortion of the input current.

PFC rectifiers utilize switching devices to achieve both PFC function and a variable output voltage. These can be of a direct three-phase type or phase modular systems built from three identical single phase circuits. Phase modular systems offer a higher redundancy in case of failure or unbalance somewhere in the system. On the other hand, the cost and complexity is higher and one or several isolated downstream converters is required to fully eliminate undesired interactions between them. This thesis will only deal with direct three-phase systems.

(20)

Like their DC/DC counterparts, three-phase variants can be characterized as buck, boost or buck-boost types. Other types such as the C´uk and transformer isolated versions also exist. Moreoever, the characterization of the different conduction modes is the same.

Figure 2.5: Different conduction modes in switching converters

In Figure 2.5the different conduction modes can be seen where D is the duty cycle and Ts is the switching period. The lower graphs show the inductor current for each mode.

In DCM the current is allowed to reach zero between each switching instant. CrCM, also know as boundary conduction mode, is achieved by turning on the switch as soon as the current reaches zero and in CCM the current remains fairly constant.

2.4.1 The single-switch DCM boost rectifier

A simpler way of achieving PFC function and controllable output voltage is to move the DC side inductance seen in Figure 2.4into each phase as seen in Figure 2.6.

PFC function is achieved by controlling the switch so that each of the inductor currents remain in DCM. In each switching cycle the peak current follows the phase voltage and the average current a sinusoidal envelope. The advantage of this circuit is the simplicity of control and a high switch utilization due to the use of only one switch. A disadvantage is the large peak currents appearing in the circuit due to DCM operation. Furthermore, due to the boost topology the output voltage must be higher than the peak line-to-line input voltage resulting in a higher voltage stress on the semiconductors.

(21)

Figure 2.6: Single switch DCM rectifier Va= Vmsin(ωt) Vb= Vmsin(ωt − 2π 3 ) Vc= Vmsin(ωt − 4π 3 ) (2.5) where Vm= √ 2VRM S

Assuming balanced input the currents in each phase will have the same shape. Over the interval [0,π2] the average current in phase A is given by Equation 2.6 [4]. The results can be extended to cover the range [0, 2π] for all three phases due to symmetrical properties of the input waveforms.

[0 ≤ ωt ≤ π 6] ia= VoD2 2Lfs sin(ωt) √ M 3 − 3 sin ωt [π 6 ≤ ωt ≤ π 3] ia= VoD2 2Lfs M sin(ωt) + 12sin(2ωt −3 ) [√M 3 − 3 sin(ωt +3 )][M − sin(ωt +π6)] [π 3 ≤ ωt ≤ π 2] ia= VoD2 2Lfs M sin(ωt) + sin(2ωt +π 3) [√M 3 + 3 sin(ωt + 2π3 )][M − sin(ωt +π6)] (2.6)

(22)

Here Vois the output voltage, D is the duty cycle, L is the inductance in each phase and

fs is the switching frequency. M is the voltage conversion ratio defined as:

M = Vo 3Vm

(2.7) .

The phase current for two voltage gains is plotted in Figure 2.7 for a converter with 400/230 V input, 800 V output, inductance L=150 uH and switching freuqency fs= 40.

A perfect sine wave is plotted with a dashed line for reference.

Figure 2.7: Average current for M=1.5 and 2

If M is kept constant at varying load only the duty cycle changes. Therefore, the magnitude of the current changes but retains its shape. Although the current is close to a sinusoidal shape it still distorted. This distortion is caused mainly by the 5th harmonic as well as higher harmonics to a lesser degree. Due the presence of these harmonics the power output of the DCM boost rectifier is limited to around 6 kW at 800 V output voltage while still complying with the 61000-3-2 limits.

It can be shown through Fourier analysis that the THD of the input current is greatly dependent on M. As the voltage gain is increased the THD is decreased [5]. While increasing M is a straightforward way of lowering THD it is not desirable as it puts further stress on the components.

(23)

2.4.1.1 Variable frequency PWM

Another way of decreasing THD without increasing the voltage gain is by operating the converter in CrCM. A current sensor is added after the rectifier bridge and the switch is turned on the instant the current falls to zero. Operating the converter in CrCM does reduce THD but results in a variable switching frequency which depends on both load and input voltage. Variable switching frequency makes designing filters difficult. Moreoever, the inductor and device selection is complicated [6].

(24)

2.4.2 Harmonic Injection

A fixed switching frequency is preferred as it simplifies the design of the converter. As mentioned in section 2.4.1 this results in a large 5th harmonic in the input currents, limiting the available output power while still remaining in compliance with the 61000-3-2 standard. The higher order harmonics are well below the limits even for power levels above 10 kW [7].

Due to the dominant 5th harmonic, the three-phase input current can be approximated as in Equation 2.8, neglecting higher order harmonics. This equation is valid for fixed frequency and constant duty cycle operation.

ia= I1sin(ωt) − I5sin(5ωt) ib = I1sin(ωt − 2π 3 ) − I5sin(5ωt − 2π 3 ) ic = I1sin(ωt − 4π 3 ) − I5sin(5ωt − 4π 3 ) (2.8)

As the 5th harmonic is the dominant one, it stands to reason that reducing its magnitude will also reduce THD. Moreoever, reducing the level of the 5th harmonic also allows for higher power output while complying with the 61000-3-2 standard.

Several methods for reducing the distortion of the input current have been suggested. In [5] a variable duty cycle is proposed in order to reduce the THD.

d(t) = D[1 + m sin(6ωt + 3π

2 ) (2.9)

Equation2.9shows a duty cycle that is modulated by 6th order harmonic with modula-tion index m. The modulamodula-tion index indicates the amount of modulating signal added to the control signal. By injecting a 6th order with proper modulation index the 5th harmonic in the input current is suppressed. However, at the same time the magnitude of the 7th harmonic is increased although THD is improved. This reduction in the 5th harmonic allows operation at higher power levels.

(25)

To obtain the 6th harmonic the three-phase voltages are fed through a separate rectifier and then filtered. This could potentially lead to an incorrect phase in the injected signal with undesired results.

Another method of harmonic reduction exists that also relies on injecting a modulating signal into the duty cycle. In this method described in [4] the three-phase voltages are also fed through a parallel rectifier and injected into the control signal. Figure2.8 pro-vides a simplified description of the control circuit with the added injection.

Figure 2.8: Simplified view of harmonic injection

In this method there is no need for any filtering of the rectified voltage to obtain the de-sired signal which is naturally synchronized to the three-phase input voltages. However, some form of voltage step down and DC-block capacitor is still needed. However, the injection described in [4] does not include a multiplier and as such the injection does not scale with the load (duty cycle). Therefore the injection in this thesis is a mixture of the two. An analog implementation requires quite a few components including some form of multiplier but in this thesis the control system is digital making the implementation of inversion and multiplier seen in Figure 2.8easier.

Equation2.10shows the modulated duty cycle and Figure2.9shows how the duty cycle varies during half a line period.

D(t) = D[1 + d(t)] d(t) = m π ∞ X n=1 (−1)n6 (6n)2− 1cos (2.10)

(26)

Figure 2.9: Duty cycle variation during half a line period

Looking at Equation2.10it is seen that the modulated duty cycle contains not only the 6th order harmonic but also 12th as well as 18th order harmonics and so on. Compared to injecting only the 6th order harmonics this contributes to a more improved THD. The suggested injection was simulated in MATLAB at full output power with and with-out injection. When using injection the modulation index was set to 0.088π. This results in the ratio between the 7th and 5th harmonic being 0.675.

0.77 A

1.14 A = 0.675 (2.11)

In Equation 2.11 0.77 A denotes the magnitude of the 7th harmonic and 1.14 A the magnitude of the 5th. Both of these magnitudes are exactly the limits imposed by the IEC standard. Keeping this ratio will allow the converter to operate at a higher output power while still meeting the IEC limits.

Figures2.10and2.11show the phase current and THD for the converter with no injection at 3 kW output. The shape of the current is close to the one seen in Figure2.7for M=1.5 and as mentioned before, the 5th harmonic is the dominant one. Using MATLABs built in FFT analysis tool the THD is calculated to be 10.58%.

(27)

Figure 2.10: Phase current with no injection

Figure 2.11: THD with no injection

After adding injection with modulation index m = 0.088π the shape of the current and THD is improved. Figure 2.12 shows the phase current when using injection. While it is not entirely sinusoidal it is much closer than without any injection. As can be seen in Figure 2.13the current still contains a modicum of low frequency harmonics but the 5th harmonic has decreased in magnitude while the 7th has increased. With injection the THD is decreased to 8.72%.

It is worth noting that the IEC-61000-3-2 limits are met both with and without injection. However, regardless of output power, a reduction of THD is beneficial and helps improve the power factor.

(28)

Figure 2.12: Phase current with injection index m = 0.088π

(29)

2.5

The buck converter

The desired output of the whole system ranges between 100 and 500 V. Due to the high output voltage generated by the boost stage to provide PFC function some form of step-down converter is needed. Step-down converters exist in both isolated and non-isolated versions where non-isolated ones use transformers to provide the isolation. Whether isolation is required depends on the application and environment in which the equipment is to be used. Due to the time and cost involved in designing and manufacturing of a transformer suitable for high power applications a non-isolated converter was chosen. Any communications interface built into the system will require isolation so as not to harm connected equipment.

Figure 2.14 shows a schematic of a buck converter along with a simplified diagram of the control-loop. When the switch is in the off-state, the diode provides a path for the current.

Figure 2.14: Buck converter

A disadvantage of the buck converter is its pulsating input current and need for isolated gate-drive due to the high-side switch. However, because of the switch lying directly in the current path, current limiting can be implemented without additional components as opposed to the boost converter.

Whereas the boost front-end depends on DCM operation for PFC function the buck-converter can be run in any of the conduction modes. CCM was selected to reduce peak

(30)

currents and simplify control-loop design [2]. In CCM, the duty cycle is load-independent and can described by Equation 2.12.

D = Vout Vin

(2.12)

2.6

Complete system

Figure 2.15: DCM boost rectifier with buck output stage

Figure 2.15 shows a diagram of the complete system. In the diagram the two control loops are omitted to provide a clear picture of the circuit. Other external circuitry such as auxiliary power supply and communications are also omitted. Each converter has its own loop where one controls the bus voltage, Vbus, which provides PFC function along

with the harmonic injection. The buck converter control loop provides control over the output voltage Vo.

(31)

Modeling and Simulation

This chapter details how the converters are modeled and controlled.

3.1

Modeling

Small signal modeling is an important tool in understanding and controlling converters. From the models transfer functions can be obtained which give a view of the converter behavior with respect to component values and load conditions. When modelling systems which contain converters in series there are some aspects which need to be taken into consideration. A buck-boost converter needs to be modeled as whole due to the fact that there is no capacitor decoupling the two stages. The boost-buck converter on the other hand can be seen as two separate converters. Viewing the buck converter as effectively being a variable impedance to the boost converter, the two converters can be modeled separately, which is done in this project.

There exists several ways of modelling power converters. Among these approaches is state space averaging described in [8]. Each switching state has its own state space de-scription. These are then averaged with respect to duty cycle and the transfer functions are obtained. Although a valid way of modeling power converters it gives less insight into the function of the actual circuit. A better and more intuitive way is to model only non-linear elements such as the switch, leaving any time-invariant components as they are. The resulting model can then be understood through ordinary circuit analysis.

(32)

3.1.1 Boost converter small signal model

AC/DC converters can be modeled as DC/DC converters on the assumption that the switching frequency is much larger than the line frequency. Between each switching instance the change in input voltage is small enough so the converter sees what is ap-proximately a DC voltage. In [9] a small signal model is developed for the single switch DCM boost rectifier. Here the circuit is first modeled as two boost converters in parallel, each with an inductance three times that of the inductance lying in each phase of the DCM rectifier. These converters are then modelled as one converter with a set of equiv-alent parameters. The resulting model can be seen in Figure 3.1 with the equivalent parameters given in equation3.1.

Figure 3.1: Small signal model of DCM boost rectifier

gi = M (M − 1) ro go = M (M − 1)ro gf = 2M ro ko = −2Vo dro (3.1)

The equivalent boost inductor is given by Le= 1.5L and the input voltage for the model

(33)

VinRM S = s π 3 Z π3 0 V2 abd(ωt) = s π 3 Z π3 0 V2 mcos2(ωt) d(ωt) = s 3 2+ 9√3 8π = 1.46Vm (3.2)

From this equivalent circuit a control-to-output transfer function e.g. the effects of variation in duty cycle on the output can be calculated. This is done with regular circuit analysis and results in the following transfer function,

Gvd(s) = 2(M − 1)Vo (2M − 1)d (1 + s sz1) (1 + s sp1) (1 − s sz2) (1 + s sp2) (3.3)

where the poles and zeroes are calculated as seen in Equation 3.4

sp1 = 2M − 1 (M − 1)roC sp2 = (M − 1)ro M3L e sz1 = 1 rCC sz2 = ro M2Le (3.4) ro = Vo2 Po (3.5)

As mentioned before, the load resistance ro is seen as a variable impedance imposed by

the buck converter depending on the load. ro can be calculated for any load using the

boost converter output voltage and total power consumption resulting in Equation3.5. M = Vo/VinRM S is the voltage gain and d is the duty cycle.

Looking at the static gain of the control-to-output transfer function one can see that it is load dependent. From Equation A.5 it is apparent that the duty cycle decreases as the load decreases. The duty cycle and static gain as a function of load are plotted in figures 3.2 and 3.3 respectively for a converter with parameters seen in Table 3.1. Bus

(34)

voltage refers to the boost converter output voltage. Please refer to Appendix B for a more in-depth description of component choices.

Parameter Value Input voltage 400/230 V / 50 Hz Bus voltage 800 V Output voltage 400 V Power output 3 kW Boost inductance 150 uH Bus capacitance 1200 uF Buck inductor 560 uH Output capacitor 680 uF Switching frequency 40 kHz

Table 3.1: Converter parameters

Figure 3.2: Duty cycle as a function of output power

(35)

In Figure3.3it can be seen that as the load decreases the static gain approaches infinity. Another problem seen in the transfer function is the pole sp1. Like the static gain it is

also load dependent and as the load decreases it approaches the imaginary axis. This causes a large phase delay at low frequency. The other pole and zeroes stay far away from the imaginary axis regardless of load.

3.1.2 Boost converter control-loop

Due to the operation of the converter only a single control-loop is needed. A voltage controller ensures both voltage regulation and PFC function. On the other hand, due to the load dependence seen in the static gain and a pole, a controller with fixed parameters will not offer optimum performance over the whole load range. However, since the control of the system is to be implemented in a digital environment a non-linear controller can be designed fairly easily.

As an example of the problem with the static gain, using a P-type controller designed for full load is not be sufficient if the load changes. As the load decreases the output voltage will increase, potentially leading to failure somewhere in the circuit. To solve this problem a variable P-type controller is proposed. Controllers where the dynamics are changed depending on operating parameters are often called gain scheduling controllers. First, the value of the static gain at full load is divided by the gain at successively lower loads resulting in the curve seen in Figure 3.4.

Figure 3.4: Fitting curve for K

p

Then, a value for the proportional term in the controller, Kp, is obtained through trial

(36)

provided an output voltage with a very small overshoot and static error. By multiplying the value for Kp at full load with the values from the fitting curve in Figure 3.4 a

load-varying gain is obtained.

A simulation was done in order to verify the function of the variable gain controller. In this simulation the load starts at 25% of full load and doubles at evenly spaced times until reaching full load. As the load increases, Kp changes to the appropriate value

obtained through fitting. The results can be seen in Table3.2and all values were taken after the controller had stabilized the voltage between load steps. For a view of the simulation model please refer to sectionB.4 in Appendix C.

Po (W) Kp Static Error (%) THD (%) PF (%)

750 4 + 0.2 13.19 99.14 1500 5.66 - 0.08 10.34 99.47 3000 8 - 0.3 8.71 99.62

Table 3.2: Test of variable gain controller

For all loads the static error is very small and the controller performance can be con-sidered good. Although voltage regulation is satisfactory at different loads the THD increases as the load is decreased. This results in a lower power factor although the value stays above the desired 99%.

Looking at the static error the difference in voltage gain between loads is very small. With this in mind the only change in converter operation should be a decrease in duty cycle along with the decreasing load. According to section2.4.1, page11, the duty cycle only affects the magnitude and not the shape of the input current. Furthermore, the decreasing duty cycle means a lower control signal and the harmonic injection should scale along with a decrease in this signal. As such, the reason for an increase in THD with decreasing load is not easily determined. Looking at Vmin simulation it is seen that

at 750 W of output power it amounts to 325.5 V. At full load it amounts to 317.9 V. For low and full load M becomes 1.42 and 1.45 respectively according to Equation2.7. The smaller M at low load could be a reason for the increased THD although the difference is very small.

(37)

Figure 3.5: Input current waveform at P

o= 750 W

Figure 3.6: Input current waveform at Po= 1500 W

(38)

3.1.3 Buck converter small signal model

Modelling the buck-converter is done in a similar way to the boost converter. The time-invariant elements are the same but the switch is modeled in a different way due to the assumed CCM operation of the circuit. Instead of a set of equivalent resistive elements the switch and diode is modeled by a fictive transformer which passes both AC and DC voltages. Duty cycle dependent voltage and current sources are added on the appropriate sides of the transformer as well. Figure 3.8 shows the model of the buck converter [2].

Figure 3.8: Buck converter small signal model

Like in the boost converter model the control-to-output transfer function can be ob-tained through circuit analysis. The buck converter transfer function can be seen in Equation 3.6where D is the duty cycle.

Gvd(s) = Vo D 1 1 +s 0 + ( s ω0) 2 (3.6)

The quantities Q and ω0 are defined in Equation 3.7.

Q = Rr C L ω0 = 1 √ LC (3.7)

(39)

There is a certain load dependence in this transfer function also. However, assuming CCM operation, the load only affects the placement of the poles. Furthermore, even though the duty cycle changes with the output voltage as seen in Equation 2.12 the static gain remains constant. This is easily proven through simple analysis. The static gain is defined in Equation3.6 as Vo/D. Moreover, D is defined as Vo/Vin where Vin in

this case is the boost converter output voltage Vbus Substituting the expression for D

into the one for static gain one obtains a static gain which equals a static gain which equals Vin= Vbus. As the boost converter output/bus voltage is to be kept constant the

static gain should also remain constant. Of course, some fluctuations during operation occur but in the steady state they should be small and can be considered negligible.

3.1.4 Buck converter control-loop

To control the buck-converter output voltage a PI-type controller was chosen. The proportional and integral gains Kp and Ki were adjusted in simulation to obtain good

reference following at full load. After that the same simulation as in section 3.1.2 was run where the load is increased at evenly spaced times. This was to investigate how the controller handles the load steps and what kind of voltage drops might be encountered. These voltage drops are the effect of the capacitor having to supply the load current while the controller adjusts to the sudden change in load. In Table3.3∆Po denotes the

change in output power between the three different loads. ∆t denotes the time elapsed between a load transient and the output voltage regaining the desired value.

Po (W) ∆t (s) Voltage drop (V)

750 7 5.2

1500 5 2.8

Table 3.3: Voltage drop at load transients

Po (W) Static error (%)

750 ∼ 0 1500 ∼ 0 3000 ∼ 0

(40)

As is seen in Table3.3 the largest voltage drop occurs when the load is increased from 750 to 1500 W. A 5.2 V drop in comparison to 400 V is not a problem and neither is 2.8 V. During all loads the controller followed the reference with no observable static error. The only difference between the different loads is an increase voltage ripple which is to be expected when the load increases.

(41)

FPGA

This chapter describes the implementation of the digital control system in an FPGA environment.

4.1

Overview

Control of power converters can be realized by either analog or digital circuits. Analog control loops do not require any sampling but are susceptible to variations in compo-nents. Moreover, tuning of the analog circuits is tedious as components need to be replaced.

Digital control loops implented in a DSP or in this case, an FPGA, offer easier tuning of parameters. Furthermore, the parameters can be changed while the system is online. Monitoring of converter performance as well as safety functions such as current limiting can also be implemented in code. A disadvantage is the need to sample the signals used in the control loops. When using an FPGA this requires the addition of an external ADC.

In this project the control system is implemented on a DE0-Nano development board. The same board was also used to control the frequency converter previously designed by Syncore. On the board is an FPGA from the Cyclone IV family made by Altera along with headers for connecting to peripheral devices. Figure 4.1 shows a simplified overview of the connection between power conversion circuits and control logic.

(42)

Figure 4.1: Simplified overview of system layout

4.2

Fixed point representation

The physical signals are converted by the ADC and sent to the FPGA via serial interface. Although a parallel interface is also possible it was not used because of a lack of input pins on the FPGA. Once converted, the signals are in 16-bit two’s complement format. The MSB denotes the sign of the sampled data with 1 being negative and vice versa. All the lower bits contain info about the magnitude of the signal.

In order to re-obtain the signals sampled by the ADC the data is converted into a fixed point format known as Qm.n. A Qm.n number is also a sort of two’s complement number but includes fractional bits along with the sign and integer bits . This was done to gain a higher resolution but also have the signal magnitudes resemble the ones in control-loops used in simulation.

A Qm.n format number is defined by the quantities m and n where m denotes the amount of integer bits and n the fractional bits. The number of bits equals m+n+1 as the sign bit is also included. The range and resolution of a Qm.n number is defined in Equation 4.1.

(43)

Range : [−2−m

, 2m− 2−n

] Resolution : 2−n

(4.1)

Q15.16 (32-bit) format was chosen in this project as a simple design choice. The resolu-tion of a Q15.16 number is an order of magnitude higher than the LSB from the ADC and the range is more than enough for any signal that might occur in the control-loops. Other formats were explored during work but Q15.16 seemed to give results closest to the ones in simulation. The range and resolution of a Q15.16 number can be seen in Equation 4.2.

Range : [−32768 , 32767.9] Resolution : 1.5259 · 10−5

(44)

4.3

Block description

This section describes the more important blocks responsible for primary functions in the system. Blocks implemented for reading from ADC, communications interface and PWM signal generation are omitted.

4.3.1 Variable gain controller

Figure 4.2: Block diagram of variable gain controller

Figure 4.2shows a block schematic of the variable gain controller. The output voltage, in this case the 800 V bus voltage, is subtracted from the reference voltage to create an error signal. Furthermore, the buck output voltage and current is multiplied to indicate at what power the system is operating. This product is sent to a look-up table which selects the appropriate gain depending on the output power. The error is then multiplied by the selected gain and the product, Vctrl, is sent to the mixer.

(45)

4.3.2 PI controller

Figure 4.3: Block diagram of PI controller

In Figure4.3the internal structure of the PI regulator is seen. The error signal is sent to two multipliers where it is multiplied by Kpand Ki respectively. A latch is implemented

that adds the previous integral error KiErrorD for the integrator every time the ADC signals that a new value is coming byt setting Update to 1. The proportional and integral errors are then added together and the result sent to the PWM module controlling the buck converter.

4.3.3 Mixer

Figure 4.4: Simplified overview of system layout

The mixer seen in Figure4.4is responsible for the harmonic injection. Vctrl is sent from

the variable gain controller and multiplied by the modulation index m. This product is then multiplied by the inverted signal coming from a small rectifier which also contains

(46)

a DC block capacitor. The unmodified Vctrl and the mixed signal is added to created

(47)

4.4

PC interface

Figure 4.5: Converter PC interface

A PC interface was written in C# to allow control over converter parameters during operation. The user may change several parameters which are listed in Table 4.1.

Slider Control parameter

Boost voltage Boost stage output voltage Buck Voltage Buck stage output voltage

Boost PWM Frequency Boost converter switching frequency Buck PWM Frequency Buck converter switching frequency Buck Kp Buck feedback propoprtional gain

Buck Ki Buck feedback integral gain

(48)

PCB design

This section details the choice of main power components and low power electronics.

5.1

Layout

Figure 5.1: 3D view of PCB

In Figure5.1the whole PCB can be seen. All high power components were placed in the upper areas of the board with the exception of the buck inductor and output capacitor.

(49)

5.2

Hardware choices

In the converter it was desired that as many components as possible should be surface mounted. Components made to withstand large stresses on the other hand are usually through-hole mounted or in some cases, chassis-mounted. When choosing components for use in the project some components had to be through-hole mounted such as large capacitors and inductors. Chassis-mounted components were preferably avoided because of the associated cost and size. However, if one would want to evaluate or switch to a chassis-mounted component it is easily done even after fabrication as these are connected to the circuit via wires.

5.2.1 High power components

5.2.1.1 Boost inductance

The boost inductance is a critical component in the converter. To ensure DCM operation under all conditions the results from Appendix A.1 can be used. If the inductor is selected so that Pc is always greater than Po the converter will operate in DCM. Due

to the periodic nature of the input voltages the duty cycle, critical power and delivered power will vary with time. In some instant the critical power will be at a minimum and the inductor should be chosen with this in mind.

Assuming balanced input voltages the converter seen in FigureA.1 can be said to have the following input voltage

Vin= max[|Vab(ωt)|, |Vbc(ωt)|, |Vca(ωt)|] (5.1)

which repeats every 60◦

and has a maximum at ωt = n x 60◦

, n = 0, 1, 2... with an equivalent inductor Le equal to 2L. The equivalent inductor stems from the fact that at

each maxima one phase voltage is zero and the other voltages see two inductors in series. When the input voltage reaches the maximum, the duty cycle and in turn the critical power will reach its minimum. Any increase in load this moment will results in the converter operating in CCM. If the inductor is selected so that the converter operates in DCM in these moments and at full load, the converter will always operate in DCM.

(50)

For a 400/230 V input the input voltage reaches its maximum at ωt = 0◦ and 60◦ resulting in Vin= |Vab(0 ◦ )| =√3Vmcos(0◦) = 563.4 V (5.2)

The duty cycle in CCM is D = 1 − Vin/Vo= 0.2958. In order to ensure DCM operation

the critical power should be equal to the maximum load. For a boost output voltage of 800 V, maximum output power Pomax = 3kW and switching frequency fs= 40kHz the

equivalent inductor becomes

Le=

Vo2 2Pomaxfs

D(1 − D)2= 391.2 uH (5.3)

The desired boost inductance is half the equivalent inductance, 195.6 uH. An inductance of 150 uH was selected to provide some margin as well as an increased current handling capability.

5.2.1.2 Bus capacitance

For selecting the bus capacitance between stages equation 5.4 can be used. Here I is the average current flowing between the boost and buck stage calculated by dividing the maximum output power with the bus voltage seen inbetween converters. Since the bus voltage is to be kept at 800 V and full output power is 3 kW this results in an average current of 3.75 A. The term 6ωl comes from the AC component of the rectified voltage

which is of sixfold frequency compared to the line frequency fl which is 50 Hz.

Max voltage ripple ∆v was set to 2 V which can be considered small in relation to the

bus voltage.

C = I 6ωl∆v

ωl= 2πfl

∆v = Desired voltage ripple

(51)

With the specified values for the parameters the calculated value for the bus capacitance is 995 uF. Due to the high voltage and current stress imposed on the bus capacitance the value was scaled up to 1200 uF. Four 1200 uF capacitors connected in series-parallel gives an equivalent of one 1200 uF capacitor but also handles the high voltage and current. Since there is a tolerance to the capacitance in each capacitor some unbalances in voltage over them may occur. Therefore, balancing resistors were also included.

5.2.1.3 Buck inductor

The buck inductor value is usually specified with a certain ripple current in mind. Ripple current is an AC variation around the output current with amplitude ∆iL. Common

values for for the ripple current are typically in the range of 10-30% . With an output current of 7.5 A at 400 V output, 800 V input and an allowed ripple of 20% (1.5A) the required inductor value can be calculated as in equation 5.5[2].

L = (Vin− Vout)D 2∆iLfsw D = Vout Vin = 400 800 = 0.5 ∆iL= 1.5A fsw= 40kHz ⇒ L = 1.7mH (5.5)

Commercially available inductors of this rating are chassis mounted and a choice was made to go with a smaller through-hole mounted inductor. The largest through-hole mounted inductor found at resellers had an inductance of 560 uH. Using equation5.5and solving for ∆iLwith L set to 560 uH the ripple current would amount to approximately

4.5 A or 60% of the output current. This was deemed unacceptable but the desired ripple current can be obtained with the smaller inductor if switching frequency is increased. The boost- and buck converter do not have to operate at the same switching frequency. Due to each converter having its own switch it is possible to set separate switching frequencies in software. Once again, using equation 5.5 with the same parameters as before but solving for fsw , one can see that the desired inductor ripple can be obtained

(52)

5.2.1.4 Buck output capacitor

Another important component in the buck converter stage is the output capacitor. It is responsible for filtering the ripple current in the inductor as well as providing a smooth output voltage. Furthermore, in the event of increased load it should supply the required current while the control system responds to the change.

Cbuck= ∆Vout1 − D Vout 8Lfsw

2 (5.6)

Equation5.6gives a minimum capacitance value for achieving the required voltage ripple. For a switching frequency of 40 kHz , output voltage of 400 V and an accepted ripple voltage of 1 V the minimum capacitance becomes 28 uF. On the other hand, capacitors need to be able to handle the ripple current from the inductor as well. Capacitors that can handle voltages up to 500V need to have their capacitance increased in order to handle larger ripple currents.

IC rms=

∆iL

12 = 1.3 A (5.7) Equation5.7gives the capacitor ripple current with fswat 40 kHz and previously selected

inductor of 560 uH. A capacitor with 680 uF was selected to accommodate this current with some added margin.

5.2.1.5 Power semiconductors

All the switches and diodes in the system responsible for power conversion need to handle large voltages and currents. The reverse blocking voltage of the semiconductors have the following requirement:

VR= Vbus= 800V (5.8)

For the required current handling an average forward current capability for all semicon-ductors was selected to equal or be larger than the maximum peak current appearing

(53)

in the system. The various currents are obtained through a graphical process detailed in [10]. With the required voltages and currents in mind SiC devices where chosen. Furthermore, these are all of the same package size to facilitate mounting on the same heatsink.

5.2.2 Low power components

5.2.2.1 FPGA

As mentioned in Chapter4the FPGA used in the project is an Altera Cyclone IV housed on the DE0-Nano development board. It was chosen to facilitate later integration with the previously built frequency converter which uses the same board.

5.2.2.2 ADC

An analog-to-digital converter is necessary to sample the required signals for use in the control-loops. In this project an AD7656-1 from Analog Devices is used which is capable of simultaneously sampling six different channels at 250 kS/s (kilosample/s). The sampled 16-bit data is sent to the FPGA via serial interface.

5.2.2.3 Gate Drive

The FPGA output pins do not have sufficient voltage or power to drive the large power transistors used in the converter. To interface with and protect the control circuitry gate drivers are used. The chips contain isolated DC-DC converters boosting the control signal to a level suitable for driving the switches. Another reason for the isolation is the fact that the buck switch is at a potential much higher than that of the FPGA.

On the output of each gate driver is an NPN/PNP transistor pair responsible for buffer-ing the driver output current. Large power transistors have higher gate capacitance and supplying a higher drive current leads to lower switching losses. On the other hand, when driving large inductive loads such as in the buck converter, faster switching leads to higher voltage spikes in the inductor. These could potentially damage the switch and surrounding circuitry.

(54)

5.2.2.4 Voltage sensors

Resistive dividers are used to convert the rectifier, bus and output voltage down to a level appropriate for interfacing with the ADC.

5.2.2.5 Current sensors

Three current sensors are employed on the board. One measures the output current whereas the other two measure buck inductor current and boost switch current. Most important is the output current since it is used in the boost stage control loop. Sensing the output current also enables the implementation of current-limiting the output. The sensors also provide isolation from the high current paths and convert the sensed current into a voltage signal.

5.2.2.6 OP-amp buffers

Two quad operational amplifiers are used to buffer all the sensor signals. This provides a low impedance source for the ADC. Two of the OP-amp outputs are also used as buffers for the signals going from the FPGA to the gate drivers. Should any sensor or drive signal chain fail and impose large voltages or currents in the copper paths the OP-amp buffers also provide a degree of isolation.

5.2.2.7 Auxiliary power supply

To allow the low voltage electronics to operate without having to connect additional cables apart from the three-phase mains a power supply connected to the 800V bus voltage is used. The main converter is of a flyback topology stepping down the voltage to 24 V. Since the transformer in the reference design used is not available two standard transformers were connected with their windings in series.

The lower voltage is further stepped down with buck converters and one LDO regulator to 15, 12, 5 and -5V respectively. Negative voltage is needed for the ADC.

(55)

5.2.2.8 Isolated PC interface

Since the whole board is not isolated connecting to a PC via serial interface could cause serious damage. The serial interface is therefore isolated to enable communication with the FPGA.

5.2.2.9 Small parallel rectifier

There are two three-phase rectifiers on the board. One is responsible for the main power processing while the other is used to extract the rectified voltage AC-waveform. The latter is connected to a resistive divider and a DC-block capacitor which feeds the ADC the required signal for use in the control loop.

(56)

Evaluation

This chapter details all the tests done and a brief explanation of equipment used during testing.

6.1

Equipment

Equipment Description

Terco MV1300 Powerpack Three-phase power supply with fixed/-variable 230/133 V output and 10 A per phase

Terco MV1100 Load resistor Fan-cooled load resistor capable of sink-ing 3.3 kW

Fluke 43 Power Quality Analyzer Digital multimeter capable of directly measuring power factor and THD for single- and three-phase systems

FLIR TG165 IR-thermometer and camera

Table 6.1: Test equipment

Table 6.1 provides information about the equipment used during testing. Apart from the equipment listed in the table, several different multimeters, oscilloscopes and power supplies were used. Furthermore, a PC with Quartus II, MATLAB, the PC interface and a variety of cabling was used.

(57)

6.2

Low voltage testing

6.2.1 Test 1: Aux PSU

The first test was to verify that the transformer-isolated DC/DC converter responsible for 800 V to 24 V conversion worked. Since no 0 ohm resistors had been added to the PCB in order to separate voltage domains for the purpose of testing, a separate board was soldered together. This board had the same output configuration as the one on the main PCB and wires were drawn from the main PCB to the board. After applying 31 volts to the testpoints on the main PCB the voltage was measured to be 24.6 V on the output of the converter. The expected output was 24 V but an error of 0.6 V was considered acceptable.

With the main upstream converter working components were soldered back to the board. Then voltage was applied to the testpoints once again in order to verify function of all downstream DC/DC converters. All smaller converters gave the right voltage with very minor errors and some ringing on the -5 V supply. Ringing is common when using charge-pump type converters.

6.2.2 Test 2: FPGA, ADC and gate-drive function

This test was done mainly to see that the code written for reading from the ADC worked. The code worked perfectly on the first try.

After this test a dummy signal was sent to the output of the PWM-module. The dummy signal was supposed to give a 40 kHz square wave with 50% duty cycle. From the output of the OP-amps used for level-shifting only a triangle wave could be seen. Evidently the OP-amps in question did not have a high enough slew rate and faster ones with the same footprint were ordered. After switching out the OP-amp for a faster one the square wave appeared as it should with a nice shape even at 120 kHz.

One thing discovered during the testing was that the current sensors used had a 2.5 V bias. This was missed by the designer of the board but did not pose a big problem. Code was written that constructs a mean value of 218 samples during start-up when no current flows in any sensor. This is then subtracted from any new values read by the

(58)

ADC. The code worked but still a small error appeared in the value sent to the rest of the system. After investigating the voltage applied to the ADC input it was shown that a small ringing occurs every time the ADC takes a new sample. ADCs often have a capacitor in the input stage and OP-amps do not do well driving capacitive loads. This could be the source of the small error. A solution to the problem is to insert a small resistor in the range of 20-200 ohms between the OP-amp and the ADC input. However, due to the routing of the board this was not possible to do post production.

6.2.3 Buck converter control-loop

With 31 V connected to the testpoints the buck-converter control loop was tested. A command was sent from the PC-interface to the FPGA to slowly ramp up the output voltage in steps of 1 V. The controller performed as it should and differences in speed could be seen clearly when changing parameters such as Kp and Ki. One thing changed

in code after the test was made to handle the fact that the error voltage could become negative.

Another thing discovered during the tests was that even with Ki at zero there was still

some form of regulator wind-up. The precise reasons why are unknown and more tests have to be conducted on the matter.

6.3

High voltage testing

6.3.1 Test 1: Soft-start circuit

The first thing to endure any high voltages or currents is the soft-start circuit. Thus, this circuit was tested first without engaging either the boost- or buck-stages. After connecting necessary cabling the main power was connected, applying 400/230 V to the system. All status leds on the board lit up indicating that the Aux PSU was working at a voltage of at least 565 V. 565 V is the peak voltage obtained from the input rectifier when the boost-stage is off.

After disconnecting the power cord the board status LEDs were still on. This is due to the bus capacitors still containing charge after having voltage applied to them. A feature

(59)

on the board not thought of by the designer was that the auxiliary PSU drained the capacitors after pulling the power cord. This provides a measure of safety even though the board was still live for around 30 seconds after power was cut.

6.3.2 Test 2: Buck converter with 230/133 V input

After concluding that the soft-start circuit was operational the buck output stage was tested. The boost function was left off and a power box supplying 230/133 three-phase power was connected to the input. When the soft-start circuit disengaged the output voltage was slowly ramped up using the PC interface. The static error was a constant 0.8 V regardless of output voltage.

Maximum output voltage that was tested in this test was 280 V. This is the DC compo-nent of the rectified input voltage. At 7.5 A of output current this results in an output power of 2.1 kW.

6.3.3 Test 3: Buck converter with 400/230 V input

After testing the buck converter with 230/133 V input, 400/230 V mains was connected to the board. This was to test the buck converter at higher output voltages that are also in the range of the desired ones. A maximum of 490 V output can be obtained with 400/230 V input and no boost function engaged.

At the higher input voltage it seemed that the static error of the regulator increased to about 1.8 V. Moreover, when attempting to go above 400 V e.g. 402 V the regulator did not stop at the desired voltage and instead kept going. This is despite only the P part of the PI regulator being used.

6.3.4 Test 4: Full system test with boost engaged, 400/230 V input

The last test was supposed to have shown whether the boost function and its control loop functioned properly. Before starting this test the system was once again connected to mains in order to ensure everything else was in order. When connecting the mains nothing on the board lit up and mains once disconnected.

(60)

After probing the board with a multimeter it was discovered that both diode pairs in the input rectifier for phases B and C were broken. Furthermore, the boost diode was also broken. This suggests that the soft-start circuit had malfunctioned during start-up. Power was also connected to the 800 V test-points to see if the rest of the system was still functioning. The board lit up but as soon as the relay closed it short-circuited. Everything else turned off and the problem is either that the external power supply current limit turned on or the 24 and 12 V converters have also broken.

New diodes, relays and other components for the 24 and 12 V converters were ordered the next day.

6.3.5 Test 5: Soft-start with higher delay

Because the diodes in phases B and C as well as the boost diode was broken, when the relay closed, the test points for 800 V were short circuited. This was the cause of the system shutting down.

The damaged components were replaced with more powerful and in some cases less expensive versions. Furthermore, the amount of time that the soft-start circuit is active was doubled. At first the active time was 10 seconds which equates to 5 time-constants for the RC-circuit which is formed by the soft-start resistors and the bus capacitors. According to calculations this should be more than enough but in reality there was still a considerable gap between the current and final voltages when the relay closed. The remaining charge needed for the capacitors to attain their final value probably caused a large enough inrush current to damage the diodes. With a soft-start time of 20 seconds the circuit worked without any problems.

Apart from the soft-start circuit nothing else seemed to have broken on the board. However, the previous system failure had tripped the circuit breakers protecting the lab. After rectifying this problem a local circuit breaker and residual-current device was installed to further protect both the user and mains network.

(61)

6.3.6 Test 6: Full system test, no harmonic injection

With the soft-start working again the buck converter was tested again without engaging the boost stage. The output voltage was taken up to 401.6 V with an output current of 3.12 A resulting in an output power of 1.25 kW. Using the power quality analyzer the recorded power factor was 0.54 with a THD of 85.5%. These measurements were made to provide a comparison between power quality with and without PFC function. After engaging the boost stage the output voltage was slowly ramped up in order to ensure that the variable gain controller did in fact function properly. Moreover, no harmonic injection was activated at the time. This was also done in order to provide a reference for system performance with and without harmonic injection. It seemed to apply too much gain too early and the output current read by the ADC was a bit higher than the actual value. The system was powered down and the scaling was changed to provide a value closer to the real one. Furthermore, the overall gain in the variable gain controller was halved to ensure no excessive voltages were applied in the system. With the software changes made, the system was powered up and the output voltage and current slowly ramped up. Output voltage was ramped up to 401.6 V again and the current to 3.3 A indicating an output power of 1.33 kW. The newly made changes resulted in a boost stage output voltage of 711 V over the recorded range of output power.

With the boost engaged and no harmonic injection the power factor had increased to 0.88 and THD decreased to 38.7%. When looking at the power quality analyzer the inductor current showed signs of entering CCM in parts of the mains period. This is undesirable in this type of system and causes a degradation of power quality. It is probable that power quality would have increased even more had the boost output voltage been at the desired 800 V.

Some time during operation the multimeter used for measuring output current started to show nonsensical readings. When going past the first range of 0-3 A on the screen it fluctuated between the 0-3 and 0-10 A ranges. It was assumed that the output current needed to be increased a little to make the multimeter stay in the higher range and show the correct value. The load resistance was decreased a little but the multimeter readings

References

Related documents

actors involved with the provision of bus services perceive their situation where the service now are procured and provided by private companies. The purpose of this study is

Both Brazil and Sweden have made bilateral cooperation in areas of technology and innovation a top priority. It has been formalized in a series of agreements and made explicit

I dag uppgår denna del av befolkningen till knappt 4 200 personer och år 2030 beräknas det finnas drygt 4 800 personer i Gällivare kommun som är 65 år eller äldre i

Detta projekt utvecklar policymixen för strategin Smart industri (Näringsdepartementet, 2016a). En av anledningarna till en stark avgränsning är att analysen bygger på djupa

DIN representerar Tyskland i ISO och CEN, och har en permanent plats i ISO:s råd. Det ger dem en bra position för att påverka strategiska frågor inom den internationella

Samtidigt som man redan idag skickar mindre försändelser direkt till kund skulle även denna verksamhet kunna behållas för att täcka in leveranser som

The case that is used is the city-bus transport provider Karlstadsbuss who provide a high-tech supporting service called Live, which delivers real- time information on bus

Industrial Emissions Directive, supplemented by horizontal legislation (e.g., Framework Directives on Waste and Water, Emissions Trading System, etc) and guidance on operating