• No results found

KTH Electrical Engineering Evaluation of a new definition for a Multi-Infeed Short Circuit Ratio

N/A
N/A
Protected

Academic year: 2021

Share "KTH Electrical Engineering Evaluation of a new definition for a Multi-Infeed Short Circuit Ratio"

Copied!
54
0
0

Loading.... (view fulltext now)

Full text

(1)

KTH Electrical Engineering

Evaluation of a new definition for a Multi-Infeed Short Circuit Ratio

Master of Science Thesis by Mercedes Sánchez Illanas

XR-EE-ES 2007:005

KTH Electrical Engineering

Electrical Power Systems

(2)

Acknowledgements

This thesis work is part of my Master of Science degree and is carried out at the School of Electrical Engineering, Division of Electrical Power Systems, Royal Institute of Technology (KTH) in Stockholm in cooperation with ABB HVDC, Sweden.

Firstly, I would like to thank Professor Lennart Söder, the Head of the Division and my examiner Dr Mehrdad Ghandhari for letting me perform my work in this Division.

I wish to express my gratitude to my supervisor Paulo Fischer De Toledo of ABB HVDC for the inspiration, support, advice, and sharing his expertise and deep knowledge related to the design and operation of HVDC. This thesis work would not have been carried out without his contribution.

I am thankful to Dr Valerijs Knazkins, my supervisor at KTH for the given support and encouragement.

Finally, I would like to thank all my colleagues in the Division of Electrical Power Systems for their support and advice during these six months that we have shared.

Stockholm, March 2007

Mercedes Sánchez Illanas

(3)

Abstract

A detailed methodology and consistent results related to the evaluation and validation of the Multiple Infeed Short Circuit Ratio as an index of the system strength in a particular point for Double Infeed HVDC systems are presented in this thesis. The evaluation will be carried out by comparing the critical MESCR with respect to the critical Short Circuit Ratio for a Single Infeed HVDC system. These critical values represent the weakest AC-network that connected to the inverter is able to keep the system stability after a disturbance. These stability limits are obtained by studying the risk of voltage instability.

The results presented in this work conclude that the validation is positive and the stability limit can be set in 1.3.

(4)

Table of contents

1 Introduction 3

2 The HVDC transmission concept 5

2.1. General overview 5

2.1.1. Rectifier operation 6

2.1.2. Inverter operation 7

2.2. An HVDC system model: The Cigre Benchmark model 8

2.2.1. The AC networks 9

2.2.2. The HVDC transmission link 9

2.2.3. The transformers 10

2.2.4. The control system 10

2.2.5. The Benchmark model extended to a double infeed HVDC system 12

2.3. Main technical aspects of concern 13

2.3.1. Tendency to voltage instability and voltage collapse 14

3 The Multi-Infeed Short Circuit Ratio 17

3.1. Definitions 17

3.2. Discussion 20

4 Methodology for calculating stability limit in Single and Double

Infeed HVDC models 22

4.1. The Simulation Software: PSCAD 23

4.2. First Task: Obtaining stability limit for the Single Infeed HVDC model 24

4.2.1. Simulation case 27

4.2.2. Procedure 1 27

4.2.3. Procedure 2 28

(5)

4.3. Second Task: Obtaining stability limit for the Double Infeed HVDC

model 29

4.3.1. Symmetrical configuration 29

4.3.2. Asymmetrical configuration 30

4.3.3. Procedure 1 31

4.3.4. Procedure 2 32

5 Results and Discussion 33

5.1. Single Infeed HVDC system 33

5.2. Double Infeed HVDC system 36

5.2.1. Symmetrical configuration 36

5.2.2. Asymmetrical configuration 41

5.3. Final discussion 43

6 Conclusions and Forward Researches 46

References 48

Table of Figures 50

(6)

Chapter 1

Introduction

The HVDC power transfer has become the most feasible way to transmit a large amount of power over long distances. The enormous energy demand is increasing the number of interconnections between power systems, leading to complex and risky configurations regarding the appearance of adverse power systems phenomena.

There are some technical aspects related to multiple infeed HVDC links that can severely destabilize the system, especially in critical situations, when the AC-network is weak in comparison with the DC-power supplied by the HVDC station. In fact, this relation provides information concerning the cooperation between both parts into the system performance referred to the prevention or resistance to anomalies such as temporary overvoltages, commutation failures, voltage instability or resonance, among others.

The Short Circuit Ratio (SCR), or Effective Short Circuit Ratio (ESCR), represents the strength of the system as the ratio between the short circuit capacity of the ac-network and the nominal power of the HVDC link. This index is valid for single infeed HVDC systems, but can be extended to multiple infeed HVDC by the so called Multiple Infeed Short Circuit Ratio (MSCR) or Multiple Infeed Effective Short Circuit Ratio (MESCR).

Such indices were introduced in [3].

The scope of this thesis consists of evaluating the definition of Multiple Infeed Short Circuit Ratio in a Double Infeed HVDC system, and validating it as a way to define the

(7)

real strength of a system in a particular point, and thus, estimate the performance like for the single-infeed HVDC case. The validation will be accomplished in the way that the definition involves all the interactions between HVDC stations that could affect the system stability.

The evaluation will be made by determining the critical MSCR and critical SCR related to the risk of voltage instability in the system, and comparing them. Critical MSCR or critical SCR corresponds to the weakest AC system that connected to the inverter of a HVDC station still has stable operating conditions. This evaluation is made by applying small increases in current order in the HVDC stations. Two different procedures were put in practise, since the way to apply these increments to get the most realistic conclusions entails another goal in this thesis.

Results for both procedures and different increment sizes are presented and discussed in this work, obtaining important conclusions which can serve as a starting point for further extended research in this field.

(8)

Chapter 2

The HVDC transmission concept

The HVDC concept appeared in order to find solutions to some of the weaknesses of the HVAC power transmission. The HVDC power transfer is optimal for long distances, because the bulk of transmitted power is almost unlimited for practical purposes. In addition, an HVDC station is the best solution for linking two power systems working at different frequencies or not synchronized. On the other hand, this kind of installation is essentially more expensive [1].

2.1 General overview

A conventional HVDC station consists of two 12- pulse converters, the rectifier that is the positive pole and the inverter, which constitutes the negative pole, linked each other by a DC line. Both 12-pulse stations are formed by two 6-pulse, line-frequency bridge converters connected by Y-Y and a ∆ –Y transformers. The station is united at each terminal to the AC-network and a set of filters and shunt capacitors banks needed to reduce the current harmonics from the converters and supply the reactive power required by them [2].

(9)

Figure 2.1An HVDC transmission system [2]

2.1.1 Rectifier operation

Assuming that the transformer’s reactance and the voltage drops through the thyristores are negligible, the average rectifier DC-voltage, in a 12-pulse station, follows the equation

6

6 2 cos S

d LL d

V V ωL I

π α π

= − (2.1)

where:

VLL is the RMS line-to-line ac-voltage at the commutation bus.

α

is the firing angle

LS is the ac-side inductance Id is the dc-current

The AC-filters located at the high-voltage side of the HVDC transformers absorbed most of the harmonic currents. Consequently, it is assumed that the fundamental harmonic is just the responsible for both active and reactive power supply to the rectifier, resulting the equations below, which are simplified supposing LS = 0.

(10)

2.7 cos

d LL d

P = V I α (2.2)

2.7 LL dsin

Q= V I α (2.3)

From equations (2.2) and (2.3), we conclude that an HVDC converter acts as a load connected to the grid, and controlled in both magnitude and power factor.

2.1.2 Inverter operation

All equations above can be extended to the inverter, knowing that the firing angle in this case is larger than 90°. Changing the polarity of the voltage with respect to that in the rectifier, the inverter average DC-voltage can be written in terms of the extinction or commutation margin

γ

as follows:

6

6 2 cos S

d LL d

V V ωL I

π γ π

= − (2.4)

and the relation between

γ

and DC-current, as

( )

2 cos cos

2

d S

LL

I L

u V

ω = γ − γ + (2.5)

where u is the overlap angle that represents the time in which more than two thyristors are conducting at the same time in a 6-pulse bridge because of LS. Equation (2.5) shows the functional relationship between the current and the overlapping between the conducting thyristors.

The relation between inverter firing angle, overlap angle and commutation margin is

180° =αi+ + γ u (2.6)

(11)

which explains why the commutation margin is of paramount important for the reliable performance of HVDC stations. It must be large enough to permit thyristors the recovery from conduction to withstand forward blocking voltage. Otherwise, they could prematurely conduct, resulting in a failure in commutation of current between thyristors fail and causing large overcurrents [8].

The active power from equation (2.2) can be rewritten in terms of

γ

, taking into account that, in this case, that power goes from the DC side to the AC side. The reactive power does not change the polarity with respect to the rectifier because this is as well absorbed by the converter. The simplified equations, assuming LS = 0 and u = 0, result:

2.7 cos

d LL d

P = V I γ (2.7)

2.7 LL dsin

Q= V I γ (2.8)

2.2 An HVDC system model: The Cigre Benchmark model

The benchmark model from which all simulations have been run and evaluated in the thesis is based on [4].

Inverter_AC

Ibus

Inverter Rectifier

0.5968 [H]

2.5 [ohm ] 0.5968 [H] 2.5 [ohm ]

26.0 [uF]

Rbus

Rectifier_AC

V A

V A

Figure 2.2. Cigre Benchmark model

(12)

The Benchmark model is a way in which a feasible comparison among different DC controls strategies and recovery performances in HVDC studies can be done. This model was designed in the way some difficulties could appear during a hypothetical performance of the system represented.

2.2.1 The AC networks

The AC network at the inverter side is represented by an R-L-L circuit. The impedance angle is kept at 75° along the whole analysis, even when the SCR is changed. The AC network at the rectifier side is represented by an R-R-L circuit, with an impedance angle of 84°. The SCR at both ends is 2.5. The AC inverter bus must be set in 230kV, and the AC rectifier bus in 345 kV.

0.151 [H]

2160.633 [ohm ] 0.151 [H]

2160.633 [ohm ]

0.151 [H]

2160.633 [ohm ] A

B C

AC network at rectifier side SCR = 2.5

0.0365[H]

0.0365[H] 0.7406[ohm ] 24.81[ohm ] 0.0365[H]

0.0365[H] 0.7406[ohm ] 24.81[ohm ] 0.0365[H]

0.0365[H] 0.7406[ohm ] 24.81[ohm ]

A

B

C

AC network at inverter side SCR = 2.5

Figure 2.3.ac-networks

The AC network is in parallel with a combination of capacitor banks and filters, which provide the converter reactive compensation. The reactive power supplied is the conventional 0.5 per unit of rated dc- power (500MVA).

2.2.2 The HVDC transmission link

The Benchmark model consists of a monopolar HVDC station with two current source converters of 12-pulse each. The DC line is a 500 kV and 1000 MVA cable of around

(13)

2.2.3 The transformers

The model includes tap changer transformers as the junction between AC-networks and converters, which allows a VLL control from the proper HVDC station. However, this control will not be used in this thesis, setting the AC voltage at the commutation buses by changing the Thevenin voltage in both ac-network sources.

2.2.4 The control system

Electrical Sys tem AOI

GMES

VDCI

Inverter Controls CMIC

CORDER

Rectifier Controls CMRC

AOR

Angle Order dc current

measured at rectifier

dc current measured

at inverter Angle Order

dc voltage measured at inverter

current order for rectifier Gamma Angle

measured at inverter

Figure 2.4 The control system

Figure 2.4 shows the outline of the control system in the Benchmark model. Each converter is in control of one of the variables in the link: the DC voltage is controlled by the inverter control and the DC current (or power through the HVDC line) by the rectifier control. Both controls are not independent of each other, as we see from the Vd

- Id characteristic in Figure 2.5.

(14)

Figure 2.5 Steady State Vd-Id characteristic [4]

The inverter γ-control represents the line ABCDE. The segments from A to D are the ones that enable the fast system recovery after a fault, a lower risk of commutation failures and almost constant reactive power consumption [11]. To get it, the inverter control just measures its DC voltage and according to the control ramp shown in Figure 2.5 and sends a current order signal to the rectifier control. This mechanism is the so- called “voltage-dependent-current order-limit” [4].

Simultaneously, the control loop increases the γ-signal to reduce the risk of commutation failure due to the high current during the fault. According to all of this, and following equation (2.5), the control provides the suitable inverter firing angle signal. However, at nominal conditions, the inverter control keeps γ fixed at the minimum value required to ensure avoiding commutation failures, which will be in our case 15°. So, the reactive power consumed by the inverter is the minimum allowed, according to equation (2.8).

The rectifier current control has such a high gain that makes its characteristic almost vertical at the input current order. The control loop consists of a measurement of DC current and voltage levels at the rectifier side, getting a modified Id that is compared with the current order given by the inverter control, which, as was mentioned before, is

(15)

not always equal to the input current order. From the difference Id – Id-ref, the rectifier firing angle is formed such that it will be larger or lower whether the difference is positive or negative, respectively. At nominal conditions, the firing angle, α, is set in 17°.

2.2.5 The benchmark model extended to a double infeed HVDC system

The benchmark model for a Double Infeed HVDC system is built up just linking the inverter terminals between two Cigre benchmark models. Within the model, both HVDC stations keep their own control systems.

Electrical Sys tem AOI_1

GMES_1

VDCI_1

Inverter Controls CMIC_1

CORDER_1

Rectifier Controls CMRC_1

AOR_1 Angle Order dc current

measured at rectifier

dc current measured

at inverter Angle Order

dc voltage measured at inverter

current order for rectifier Gamma Angle

measured at inverter

Electrical Sys tem

Rectifier Controls

Inverter Controls AOI_2 GMES_2

VDCI_2

CMIC_2 CORDER_2

CMRC_2

AOR_2 Angle Order dc current

measured at rectifier

dc current measured

at inverter Angle Order

dc voltage measured at inverter

current order for rectifier Gamma Angle

measured at inverter

0.4611[ohm]0.0168[ohm] 0.4611[ohm]0.0168[ohm] 0.4611[ohm]0.0168[ohm]I12_C

NCI_2

NBI_2

NAI_2 I12_B

I12_A

Figure 2.6 The benchmark model for a double infeed HVDC system

(16)

The mutual impedance will vary in absolute value depending on the case to simulate, as we will see later on. However, the angle will be kept constant at 85° for all the cases.

2.3 Main technical aspects of concern

In Single Infeed HVDC systems, the main problems related to the performance are located in current source inverter terminals, especially when they are connected to a low short circuit capacity AC network with respect to the DC power infeed [8]. These aspects of concern can be summarized as follows [6]:

• High temporary overvoltages, followed by a load rejection because of a fault in the transmission network, or due to a commutation failure

• Low frequency resonance at both AC and DC sides because of the system configuration [10]

• Voltage and power instability, caused by a lack in reactive power or a lack in control

• Long restart times after small modification around the operating point, due to control system upsets

• Commutation failures in the inverter, due to voltage disturbance at the AC side, usually phase-to-ground faults

When the number of converters connected to the same AC-network increases, the list of problems is extended to include all those related to the interaction between them, as is detailed in [8]:

• Commutation failures interactions between converters

• Requirements on need for coordination of recovery control

• Coordination of high level controls like power or voltage modulation between HVDC transmission links

• Frequency instability

(17)

2.3.1 Tendency to voltage instability and voltage collapse

The thesis is focussed on the study of the risk of voltage and power instability in HVDC systems. This phenomenon is well-known in power systems and consists of a high and uncontrollable voltage drop after small increases in load or transmitted power.

In HVDC systems, the voltage stability is a problem related to the operation of the inverter when it is connected to a weak AC system. This is due to the inability of the AC system in providing the reactive power needed by the converters to maintain acceptable system voltage.

An increase in reactive power can be triggered just by a small increase in current order with respect to the operating point, leading to a voltage drop. During the system transient, the control system reacts trying to decrease the overcurrent and increase the voltage by increasing rectifier firing angle αR and decreasing inverter αI, respectively (see Figure 2.7). It makes increase the converter power factor, increasing the reactive power demand and dropping the active power, as follows from equations (2.3) and (2.2). If the AC-network is not strong enough, the loading will exceed the system’s maximum capacity, the voltage will sharply drop and the system collapses [8].

This trend is shown by the Maximum Power Curve (Figure 2.8) when the nominal operating point is located in the unstable zone. The stable operating zone is the positive slope in the Id-Pd curve, which is equivalent to a negative slope in the Pd-U curve. We can see that in the unstable zone, an increase in current entails a decrease in voltage and active power.

(18)

0.850 0.900 0.950 1.000 1.050 1.100

y (p.u.)

Rectifier DC Current step

10 100

y

Recifier Alpha Order

100 110 120 130 140 150

y

Inverter Alpha Order

0.850 0.900 0.950 1.000 1.050 1.100

y (p.u.)

Inverter AC Voltage (RMS)

Figure 2.7 Alpha variation just after an increase in the current order

Figure 2.8Maximum power curves: Pd-Uand Id-Pd [5]

From Figure 2.8, we can see, as well, why the power control entails the most critical situation. When the power order increases, the power control acts increasing the current, which leads to a drop in voltage and transmitted power. Consequently, the power control increases the current again, causing the continuous drop in voltage until the system reaches the collapse [5].

(19)

DC links theoretically have just a thermal constraint to transmitted power, but this is not the case if they are controlled by power electronics and included in the power system. The maximum transmitted power is fixed by both the AC-network capacity and γmin at inverter γ-control [5].

(20)

Chapter 3

The Multi-Infeed Short Circuit Ratio

In the previous chapter, we saw that the most critical performance situation occurs in those points where the AC-network has a low short circuit capacity compared with the DC power infeed. This strength of the network is represented, in single infeed HVDC systems, by the Short Circuit Ratio (SCR), which identifies a system according to its performance in a particular point.

When two or more converters are connected to the same ac-network, the Multi-Infeed Short Circuit Ratio (MSCR) at a particular bus pretends to be an extension of the SCR and supply a normalized information about the real strength of the system in that point regardless the number of converters connected, since the effects of the interactions between them are already within the MESCR definition. The validation of this statement is one of the key goals of the thesis. Presently, the definitions of SCR and MSCR will be given and analyzed in this chapter.

3.1 Definitions

The equivalent circuit shown in the figure below is the most common way to represent the inverter side in single infeed HVDC systems. Z1 is the impedance of the ac-network and B1 represents filters and shunt capacitors banks [3].

(21)

Figure 3.1 Simplified model of an HVDC connected to an AC network [3]

The definition of Short Circuit Ratio is

SC dN

SCR S

= P

(3.1)

where:

S

SC is the short circuit capacity at the commutation bus.

P

dN is the nominal power at the HVDC link.

S

SC is equal to

1

1

Z

in per unit when the DC-nominal power and ac nominal voltage at the commutation bus are the bases, resulting the definition of SCR as follows:

1

SCR 1

= Z

(3.2)

The Effective Short Circuit Ratio is the SCR including the reactive compensation at the commutation bus.

SC c

dN

S Q

ESCR P

= −

(3.3)

with

Q

c denoting the reactive shunt compensation. This definition is better in order to provide a more realistic strength of the system since the destabilizing effect of shunt capacitors is already included.

(22)

Figure 3.2 Simplified model for 2-HVDC systems

Figure 3.3 Simplified model for 3-HVDC systems

From Figure 3.2 and Figure 3.3, the Multi-Infeed Short Circuit Ratio is defined by

, 1

1

m

n k

dc n m

m

MSCR

P z

=

=

∑ ⋅

(3.4)

where:

k the number of HVDC terminal stations.

P

dN the nominal power of the HVDC station m in p.u.

zn,m the term of the ZBUS located in the row n and column m, in p.u.

Including the compensation in the admittance matrix, we get the Multi-Infeed Effective Short Circuit Ratio.

, 1

1

m

n k

dc en m m

MESCR

P z

=

=

∑ ⋅

(3.5)

We must observe that the MESCR definition is applicable as well to Single-Infeed systems just making the mutual impedances tend to infinite.

(23)

3.2 Discussion

In order to evaluate the reliability of MESCR to define the strength of the system in a particular point, it is necessary to have a look at those effects that take place when two or more HVDC converters are linked:

• A disturbance in a converter can be alleviated by the proper control and all the converters connected to it. This interaction depends on the strength of the grids connected to them and the strength of the links to the considered converter.

• A converter is affected by a disturbance in any other converter connected to it.

This interaction depends on the strength of the grids connected to them and the strength of the link between the considered converters.

From the interpretations of ZBUS, we know that the element located in the nth row and mth column represents the sensitivity of bus n to load variations in bus m. The larger this term is, the larger the influence of the converter m in the converter n is. Obviously, this term becomes larger when the mutual impedance between m and n is lower and the self impedance in m greater.

At the same time, this zn,m value is multiplied by the rating power of the mth converter.

This pretends to put on weight the influence of m over n, since a disturbance in m is more critical if the load at that point is larger, implying a larger influence over n.

According to everything mentioned above, we can conclude that the first effect of the interaction between converters is represented by the term ,

dcn en n

P ⋅ z

and the second by

, 1

m

k

dc en m m

m n

P z

=

∑ ⋅

in the equation (3.5).

(24)

Since the different aspects related to the interaction between converters seem to be included in the MESCR definition, this should be a good tool to measure the real strength of a system in a particular point. The next step is to prove it empirically, which constitutes the target of the subsequent chapters.

(25)

Chapter 4

Methodology for calculating stability limit in Single and Double Infeed HVDC models

The thesis is aimed at evaluating the definition of Multiple Infeed Short Circuit Ratio.

To do this, an attempt will be made to get the stability limit in terms of MESCR for a double infeed HVDC system, and compare it to the one obtained previously for the single infeed HVDC case in terms of ESCR. If both values are sufficiently close to each other, it will be possible to conclude that MESCR is able to provide a normalized strength of a system in a particular point, since all the influences between converters are already included within the definition.

In Chapter 2, some aspects of concern related to HVDC systems were mentioned. In order to get the most realistic stability limit, the study of every problem should be carried out. The primary focus in this thesis is placed on the risk of voltage instability at the inverter side, which is the most critical side due to the risk of commutation failures associated. Consequently, the methodology followed here is to explore the behaviour of the system from a nominal operating point to a region where the system will reach voltage collapse, and this is possible by increasing the current order, as was mentioned in Section 2.3.1.

(26)

If we want to evaluate MESCR by comparing the trend towards voltage instability in different systems, we must be sure that no other phenomenon induces the instability.

Therefore, obtaining the best procedure that ensures it constitutes another goal in this thesis. Actually, the design and proper implementation of this procedure has required the most labour-intensive part of this project. Two different procedures were put in practise. These methods are detailed in the following sections and the conclusions related to which of them can be considered the most suitable will be treated later on during the discussion.

Before going into detail through the methodology employed to calculate the stability limits, it is interesting to introduce briefly the simulation tool.

4.1 The Simulation Software: PSCAD

The software used for running the simulations is PSCADv4.2.0. PSCAD is a general- purpose time domain simulation tool for studying transient behaviour of electrical networks. This seamlessly integrated visual environment supports all aspects of conducting a simulation including circuit assembly, run-time control, analysis, and reporting [7].

PSCAD includes an extensive library of models including all aspects of AC and DC power systems and controls. The analysis and design of any power system is possible, since a graphical user interface, and control tools are available for that. If a model not included in this master library is required, there exists the option in the software to create an own new one using the built-in graphical Component Workshop.

The software includes some project-examples. Having a look at those, we find out the file HVDCCigre. Within it, the project called Cigre_Benchmark.psc can be loaded. This model is the basis for the one employed in this thesis. The extended version differs from the other basically in the control system, more sophisticated since it includes the

“voltage-dependent-current-order-limit”. Also, it incorporates new input controls and

(27)

measurement points required to induce the disturbances for a complete study of the system stability.

Figure 4.1 Cigre Benchmark model Figure 4.2 Cigre Benchmark model, extended version

From the extended version, it is possible to simulate not only in time domain but frequency domain too, in order to obtain Bode and Nyquist plots for the study of the stability in steady state conditions.

4.2 First task: Obtaining stability limit for the Single Infeed HVDC model

The task consists of obtaining the minimum value of the SCR at the inverter bus for which a single infeed HVDC system keeps being stable after an increase in current order.

It should be noted that detection of the voltage collapse phenomenon is not a trivial task. This is because in some cases the control system is able to manage the situation and recover the steady state conditions. To circumvent this difficulty, the voltage instability will be checked by measuring the overshoot in the rectifier dc-current just after the increase in current order. We will consider the system as tending to voltage instability when the overshoot exceeds a value of 100%. That is, if the incremental

(28)

value of the actual current transiently reaches the value of 10% for a current order increment of 10%, then the overshoot is 100%. This limit is just a criterion to calculate the stability limit in this project, where the scope is focused on evaluating the MESCR definition rather than obtaining an accurate stability limit. In order to get a more realistic stability limit, the maximum overshoot may be fixed according to values permitted in the real life applications.

0.850 0.900 0.950 1.000 1.050

y (p.u.)

Rectifier DC Current step

Figure 4.3 Overshoot below 100%

0.850 0.900 0.950 1.000 1.050

y (p.u.)

Rectifier DC Current step

Figure 4.4 Overshoot close to 100%

0.850 0.900 0.950 1.000 1.050

y (p.u.)

Rectifier DC Current step

Figure 4.5 Voltage collapse

According to everything mentioned above, the stability limit is established by applying the following steps.

(29)

Figure 4.6 Flowchart of obtaining stability limit for the Single Infeed HVDC model

The stability limit will be the SCR for which, having the system an overshoot close to 100% (Figure 4.4), during the following decreasing of SCR it collapses (Figure 4.5).

We will apply two increases in current, one of a 10% and another softer of 5%, obtaining two different stability limits for each of them. But we must be aware of the risk of commutation failures that an increase in current involves. In order to ensure the study of just the trend to voltage instability in the system, the increase in current order is carried out using two different procedures that will be detailed later on in this section.

Rectifier Inverter

SCR = 2.5 SCR = 2.5 ESCR = 2 ESCR = 2

Shunt Capacitors Qc=0.5

INCREASE CURRENTORDER (procedure 1 or 2)

MEASURE OVERSHOOT

DECREASE INVERTER SCR IN 0.1

If is ≤ 100%

(30)

4.2.1 Simulation case

In the Cigre benchmark model, from Section 2.2, the strength of the AC-networks is set up in a SCR of 2.5 or ESCR of 2 (remember that Qc is 0.5 per unit) at both rectifier and inverter sides.

To build up the remaining simulation cases, we will need to vary the SCR at the inverter side. Taking into account that the inverter AC-network is represented by an R- L-L circuit and assuming that we keep the impedance angle in 75° for all the cases, the equation (3.5) evidences that we just need to multiply each element of the grid’s impedance by the same constant to change the SCR at the inverter bus. The constant is defined by the following ratio:

2.5

ρ = SCR

. (4.1)

4.2.2 Procedure 1

To increase the current avoiding commutations failures at the same time, we should make the increase from a lower value than the nominal operating point. In this way, the overlap angle will not grow so much and, thus, the drop of the commutation margin will not be so risky.

There are two procedures to apply such a step up in current. The first one is schematically shown below in Figure 4. 7.

(31)

Figure 4. 7: Flowchart of Procedure 1

In this procedure, the overshoot is measured just after the current order is reset to 1 per unit.

4.2.3 Procedure 2

The procedure 2 differs from the procedure 1 in the initial steady state conditions that are directly set up with current order lower than 1pu:

Figure 4.8: Flowchart of Procedure 2

INITIAL STEADY STATE CONDITIONS:

Id = 1 pu Ud = 1 pu

α = 17°

γ = 15°

-10% STEP DOWN IN CURRENT ORDER DURING 1sec.

-5% STEP DOWN IN CURRENT ORDER DURING 1sec.

INITIAL STEADY STATE CONDITIONS:

Id = 0.9 pu Ud = 1 pu

α = 17°

γ = 15°

INITIAL STEADY STATE CONDITIONS:

Id = 0.95 pu Ud = 1 pu

αα αα = 17°°°°

γγγγ = 15°°°°

STEP UP IN CURRENT ORDER TO 1pu

(32)

4.3 Second task: Obtaining stability limit for the Double Infeed HVDC model

The task consists of obtaining the minimum value of MESCR at a particular inverter bus for which a double infeed HVDC system preserves its stability after an increase in current order.

The increase in current order will be carried out using both procedures previously mentioned. In this case, we will calculate the stability limit applying tree different steps in current: one of 10 % in just one station, one of 5% in one converter and one of 5% in both stations simultaneously.

In this case, we can vary MESCR by varying

− the self SCR1 at the inverter commutation bus in both converters

− the mutual impedance.

4.3.1 Symmetrical configuration

The symmetrical configuration is that in which the self impedance (or self SCR) of the ac-networks and the rated power are the same in both inverters.

From the equation (3.5), we see that for symmetrical systems, MESCR does not depend on the mutual impedance, keeping always the same value in both buses that is equal to the self ESCR. Then, we will try to check whether the stability limit depends on the mutual impedance or not. To this, it is enough to propose two cases such that the mutual impedance largely differs from each other. The stability limit is obtaining for each case by applying the flowchart in Figure 4.9.

1 When we talk about “self SCR” at the inverter bus we refer to the inverse of the self impedance (in pu) of the AC-network connected to that bus. It is, the SCR at the inverter terminal if the HVDC station is

(33)

Figure 4.9: Flowchart of obtaining stability limit for the double infeed HVDC system. Symmetrical cases

4.3.2 Asymmetrical configuration

There is a numerous variety of combinations of asymmetrical cases among which we must select a few that could cover as many critical situations as possible in order to evaluate the quality of MESCR. These cases will be grouped into two blocks:

A. Fixing the inverter network 1 as a strong network and the inverter network 2 as a weak one. The MESCR increase/decrease by decreasing/increasing the mutual impedance respectively.

B. Fixing the inverter network 1 as a strong network and keeping the mutual impedance constant. The MESCR increase/decrease by increasing/decreasing self ESCR in the inverter network 2 respectively.

HVDC STATION 1 HVDC STATION 2 variable ESCR variable ESCR

Fixed Z12

Shunt capacitors: Qc = 0.5

INCREASE CURRENT ORDER (procedure 1 or 2)

MEASURE OVERSHOOT

DECREASE INVERTER selfESCR IN 0.1 IN BOTH

STATIONS If is ≤ 100%

(34)

To obtain the stability limit for cases within block A and block B, I will follow the flowcharts represented in Figure 4. 10 and Figure 4.11 respectively.

Figure 4. 10: Flowchart of obtaining stability limit for the double infeed HVDC system.

Asymmetrical cases, block A

Figure 4.11: Flowchart of obtaining stability limit for the double infeed HVDC system.

Asymmetrical cases, block B

4.3.3 Procedure 1

Procedure 1, extended to double infeed HVDC systems, is now represented by the following diagram:

HVDC STATION 1 HVDC STATION 2 fixed ESCR variable ESCR

Fixed Z12 Shunt capacitors: Qc = 0.5

INCREASE CURRENT ORDER (procedure 1 or 2)

MEASURE OVERSHOOT

DECREASE selfESCR 2 IN 0.1 pu

If ≤ 100%

HVDC STATION 1 HVDC STATION 2 fixed ESCR fixed ESCR

Variable Z12 Shunt capacitors: Qc = 0.5

INCREASE CURRENT ORDER (procedure 1 or 2)

MEASURE OVERSHOOT

INCREASE MUTUAL IMPEDANCE IN 0.1 pu

If ≤ 100%

(35)

Figure 4.12: Flowchart of procedure 1

4.3.4 Procedure 2

Procedure 2, extended to double infeed HVDC systems, follows the steps below:

Figure 4.13: Flowchart of procedure 2

INITIAL STEADY STATE CONDITIONS:

STATION 1 STATION 2 Id = 1pu Id = 0.9pu

Ud = 1pu Ud = 1pu

α = 17° α = 17°

γ = 15° γ = 15°

INITIAL STEADY STATE CONDITIONS:

STATION 1 STATION 2 Id = 1pu Id = 0.95pu Ud = 1pu Ud = 1pu

α = 17° α = 17°

γ = 15° γ = 15°

INITIAL STEADY STATE CONDITIONS:

STATION 1 STATION 2 Id = 0.95pu Id = 0.95pu Ud = 1pu Ud = 1pu

α = 17° α = 17°

γ = 15° γ = 15°

STEP UP IN CURRENT ORDER TO 1pu

-10% STEP DOWN IN CURRENT ORDER DURING

1sec IN STATION 2

INITIAL STEADY STATE CONDITIONS:

STATION 1 STATION 2 Id = 1pu Id = 1 pu Ud = 1pu Ud = 1pu

α = 17° α = 17°

γ = 15° γ = 15°

-5% STEP DOWN IN CURRENT ORDER DURING

1sec IN STATION 2

-5% STEP DOWN IN CURRENT ORDER DURING

1sec IN BOTH STATIONS

(36)

Chapter 5

Results and Discussion

5.1 Single Infeed HVDC system

From this first analysis, we determine which procedure is the one that provides the safest stability limit. In Figure 5.1 and Figure 5.2, the trend curves show how the overshoot varies with ESCR at the inverter bus. There is one curve for each procedure and increment in current.

0 20 40 60 80 100 120 140 160 180 200

1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2

ESCR

overshoot (%)

PROCEDURE 1 100% limit PROCEDURE 2 stability limit 1 stability limit 2

Figure 5.1 Stability limits with increase in current of 10%

(37)

0 20 40 60 80 100 120 140 160 180 200

1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2

ESCR

overshoot (%)

PROCEDURE 1 100% limit PROCEDURE 2 stability limit 1 stability limit 2

Figure 5.2 Stability limits with increase in current order of 5%

Table 5. 1: Stability limits for the Single Infeed system analysis

Increment in 10% Increment in 5%

Procedure 1 SCR = 2

ESCR = 1.5

SCR = 1.7 ESCR = 1.2

Procedure 2 SCR= 2.2

ESCR = 1.7

SCR = 1.8 ESCR = 1.3

Obviously, for each increment in current order the stability limit is different, being greater for those obtained by the largest increment. Later on, during the double infeed analysis, it will be shown that the step of 10% is not valid for the aim of this thesis.

Comparing results from Figure 5.1 and Figure 5.2, it can be concluded that procedure 2 is the one that provides the safest stability limit. The explanation is supported by the different voltage conditions that both procedures present just before the increment in current.

(38)

Figure 5.3 Maximum Power Curves

0.850 0.900 0.950 1.000 1.050 1.100

y (p.u.)

Inverter AC Voltage (RMS) Rectifier DC Current step

0.850 0.900 0.950 1.000 1.050 1.100

y (p.u.)

Inverter AC Voltage (RMS) Rectifier DC Current step

Figure 5.4 In prodecure 1, step down in current order: 10% above and 5% below

Figure 5.3 shows how a step down in current order makes the voltage increase. It entails that the voltage level before the step up is larger in procedure 1 than in procedure 2, where it is 1 pu. Consequently, in procedure 1 it is easier for the system to withstand the voltage drop after the increase in current order. The consequence is that the stability limit obtained by procedure 1 is always larger than the one obtained by procedure 2, as is shown in Table 5. 1.

For increments of 5%, the voltage levels are not so different between procedures and the stability limits are close together as we see from Figure 5.2. But when the step up grows till 10%, the difference between procedures becomes larger.

(39)

0.850 0.900 0.950 1.000 1.050 1.100

y (p.u.)

Rectifier DC Current step

0.850 0.900 0.950 1.000 1.050 1.100

y (p.u.)

Inverter AC Voltage (RMS)

Figure 5.5 Procedure 1, increase in current order with ESCR = 1.5

0.850 0.900 0.950 1.000 1.050 1.100

y (p.u.)

Rectifier DC Current step

0.850 0.900 0.950 1.000 1.050 1.100

y (p.u.)

Inverter AC Voltage (RMS)

Figure 5.6 Procedure 2, increase in current order with ESCR = 1.5

In order to get a better stability limit, we will only use the procedure 2 in the remaining analysis.

5.2 Double Infeed HVDC system

5.2.1 Symmetrical configuration

As was pointed out in the methodology, developing mathematically the MESCR definition for a symmetrical configuration, we see that the index does not depend on the mutual impedance between converters. Consequently, the stability limit should be the same regardless of the junction. In order to check it, two cases summarized in Table 5.2 were studied.

(40)

Table 5.2 Simulation cases for symmetrical Double Infeed HVDC systems

Self ESCR1 = Self ESCR2 Z12

Case 1 Variable 5

Case 2 Variable 0,1

The results are presented in the following graphs:

0%

20%

40%

60%

80%

100%

120%

140%

160%

180%

200%

1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2 2,1 2,2

MESCR2

overshoot

Z12 = 5 pu 100% limit Z12 = 0.1 pu stability limit 1 stability limit 2

Figure 5.7 Stability limit with 10% step in current

(41)

0%

20%

40%

60%

80%

100%

120%

140%

160%

180%

200%

1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2

MESCR2

overshoot

Z12 = 5 pu 100% limit Z12 = 0.1 pu stability limit 1 stability limit 2

Figure 5. 8 Stability limit with 5% step in current in converter 2

0%

20%

40%

60%

80%

100%

120%

140%

160%

180%

200%

1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2

MESCR2

overshoot

Z12 = 5 pu 100% limit Z12 = 0.1 pu stability limit

Figure 5. 9 Stability limit with 5% step in current in both converters

(42)

Table 5.3 Stability limits for the symmetrical case

Z12

10% step in current 2

5% step in current 2

5% step in current in both

5 pu ESCR = 1.5 ESCR = 1.2 ESCR = 1.3

0.1 pu ESCR = 2 ESCR = 1.3 ESCR = 1.3

The results indicate that an increment in 10% is too large to be used to check the risk of voltage instability, because it is likely that this causes at the same time any other kind of problem in the system. This point is further exemplified in the figures below:

0.850 0.900 0.950 1.000 1.050 1.100

y (p.u.)

Rectifier DC Current_1 Rectifier DC Current_2 CO_1

0.0 5.0 10.0 15.0 20.0 25.0

y

Gamma_1 Gamma_2

0.850 0.900 0.950 1.000 1.050 1.100

y (p.u.)

Inverter AC Voltage (RMS)_1 Inverter AC Voltage (RMS)_2

Figure 5. 10 10% Step up for MESC = 1.4229 and Z12 = 5 pu

Figure 5. 10 shows how the system behaves when the link is weak. Here, the disturbance in converter 2 because of the current increment should be almost totally withstood by itself. However, since the stability limit here is 1.5, lower than the one obtained for the single infeed system, the converter 2 is helping to withstand the disturbance as well, regardless of the weak link.

(43)

0.850 0.900 0.950 1.000 1.050 1.100

y (p.u.)

Rectifier DC Current_1 Rectifier DC Current_2 CO_1

0.0 5.0 10.0 15.0 20.0 25.0

y

Gamma_1 Gamma_2

0.850 0.900 0.950 1.000 1.050 1.100

y (p.u.)

Inverter AC Voltage (RMS)_1 Inverter AC Voltage (RMS)_2

Figure 5. 11 10% Step up for MESC = 1.4229 and Z12 = 0.1 pu

When the link is stronger, converter 1 influences converter 2 in a higher way, but the reciprocal is true as well. This means that now converter 1 is more affected by a disturbance in 2, being even the one that becomes instable before (see Figure 5.11).

However, this behaviour could be easily triggered by some other causes, not just by a higher risk of voltage instability in 1. This is because if the strength of the system is identical in both converters, the risk of voltage instability too, and then, when we applied the disturbance in 2, the collapse would appear in 2.

At the same time, the fact that the stability limit here is larger than the one calculated in the single infeed case (compare Table 5. 1 with Table 5.3) is another argument to support that the tendency to voltage instability cannot be the only reason for the collapse.

For instance, the commutation margin’s drop after the current increment in addition with the higher current set in 1 make this inverter prone to commutation failures. Upsets in control systems at such a high increment in current could cause the behaviour in Figure 5. 11 too.

(44)

Analysing the results for the 5% step, we can see that increasing the current order just in one converter, the stability limit change, depending on the mutual impedance. However, we do not consider that this implies a problem with the MESCR definition. This is because both limits are almost the same and equal to the one obtained for the single infeed case. At the same time, the definition should work well for asymmetrical cases, since it will take into account the mutual impedance (Section 3.2).

When the increase in current is applied in both converters at the same time, the symmetry in the simulation is complete, even in the operating conditions in both stations. It explains that here the mutual impedance does not influence at all, being the stability limit equal to the one obtained for the single infeed HVDC system.

5.2.2 Asymmetrical configuration

As was mentioned in the previous chapter, the cases are selected in such a way that we could cover as many critical situations as possible in order to evaluate the quality of MESCR to define the strength of the system for different extreme cases. The cases are divided into two blocks and presented in Table 5.4.

Table 5.4 Simulation cases for asymmetrical Double Infeed HVDC systems

Self ESCR1 Self ESCR2 Z12

Case A.I 2.5 0.5 Variable

Case A.II 2.5 1 Variable

Case B.I 2.5 Variable 5

Case B.II 2.5 Variable 1

For each case, we obtain the trend curve as in the previous cases. Then they will be grouped in the same graph in order to enhance the proximity between each other.

(45)

0%

20%

40%

60%

80%

100%

120%

140%

160%

180%

200%

1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2

MESCR2

overshoot

Case A.I Case A.II Case B.I Case B.II 100% limit stability limit

Figure 5.12 Stability limit with 5% step in current in converter 2

When the increase is in converter 2, all the cases studied has a trend curve that achieves the 100% overshoot when MESCR in the weak converter is around 1.2. The figure below presents the curves when the increase is applied in both converters. For this case the stability limit is around 1.3.

0%

20%

40%

60%

80%

100%

120%

140%

160%

180%

200%

1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2

MESCR2

overshoot

Case A.I Case A.II Case B.I Case B.II 100% limit stability limit

Figure 5.13 Stability limit with 5% step in current in both converters

(46)

1 1,1 1,2 1,3 1,4

Stability limit

5% Increment in current order in 2 5% Increment in current order in both

Figure 5.14 Comparison between stability limit from both current increments

Table 5. 5 Stability limits for Double Infeed HVDC sytems analysis

5% Step in current in 2 5% Step in current in both

MESCR 1.2 1.3

5.3 Final discussion

In the analysis above, we have outlined and elucidated the procedure to obtain the stability limit regarding risk of voltage and power instability.

From the single infeed HVDC system analysis, we identified procedure 2 was the one that provide the safest stability limit, and proceeded using it.

Checking the results from the symmetrical case in Double Infeed HVDC systems, we realised that by applying an increment in current order of 10% it is likely to induce other failures in the system as control upsets or commutation failures. Then, we discarded this increment because it could not provide me reliable information since we

(47)

For the asymmetrical cases, we selected those that we considered more suitable to mark a tendency. The study provides that for a particular current increment, the stability limit is almost the same in all the simulated cases. It points to MESCR as a valid index to define the strength of a double HVDC system.

The limits from Table 5. 5 are very close together but they are different. This is because the effect of an increment just in one converter seems to be softer than if it is applied in both converters simultaneously. At the same time, it is reasonable to think that a disturbance in a single infeed HVDC system is more critical than if it takes place in a converter linked to a stronger one that could help it to withstand the disequilibrium.

According to everything mentioned before, the conditions of simulation in the single infeed HVDC link analysis should be closer to those in the double infeed HVDC case when we apply a 5% step in both converters at the same time. Comparing trend curves we can see the likeness among them in Figure 5.15.

0%

20%

40%

60%

80%

100%

120%

140%

160%

180%

200%

1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2

MESCR2

overshoot

Case A.I Case A.II Case B.I Case B.II 100% limit stability limit single infeed HVDC

Figure 5.15 Comparison between trend curves with the single infeed HVDC (dashed curve)

(48)

Since the stability limit in both cases is identical, we find enough reasons to state that the MESCR definition is perfectly valid for double infeed HVDC systems, and it provides a normalized strength of the system in a particular node. It entails that all the effects related to the interactions between converters seem to be included within the definition, and this is a good reason to consider that this validation and, thus, the stability limit could be extended to a generic multiple infeed HVDC system regardless the number of stations.

References

Related documents

46 Konkreta exempel skulle kunna vara främjandeinsatser för affärsänglar/affärsängelnätverk, skapa arenor där aktörer från utbuds- och efterfrågesidan kan mötas eller

Byggstarten i maj 2020 av Lalandia och 440 nya fritidshus i Søndervig är således resultatet av 14 års ansträngningar från en lång rad lokala och nationella aktörer och ett

Although the transmission and distribution of electrical power will be prefera- bly made with conventional AC technique, but HVDC transmission would of- fer special advantages for

Ett första konstaterande måste göras här gällande spelvåldsdebatten är att den avgränsade tidsperiod för denna studie (2000 – 2009) inte grundar sig i något startskott

The paper’s main findings show that among the basic economic factors, the turnover within a company has the strongest positive relationship with the company’s level of

Previous research in various domains has found that individual differences in decision-making style are related to behavior (e.g. The measures have been found to have

W hen I was asked to write about Black and Asian Drama in Britain in August 2018, it immediately raised the question of what had happened since I worked on Contemporary Black

Based on a stakeholder needs perspective we argue that the right thing in a sustainability report means reporting in the entire value chain for main sustainability impacts.. Doing