Electric Power Systems Research 196 (2021) 107201

Available online 5 April 2021

0378-7796/© 2021 The Author(s). Published by Elsevier B.V. This is an open access article under the CC BY license (http://creativecommons.org/licenses/by/4.0/).

Onshore wind farm - Reliability centered cable routing

Sanja Duvnjak ˇZarkovi´c * , a , Ebrahim Shayesteh b , Patrik Hilber a

a

Department of Electromagnetic Engineering, School of Electrical Engineering and Computer Science, KTH Royal Institute of Technology, Stockholm, Sweden

b

Swedish National Grid, Stockholm, Sweden

A R T I C L E I N F O Keywords:

Distribution system distribution system planning cable routing

wind farm

mixed-integer programming power system reliability

A B S T R A C T

Designing an onshore wind farm is a complex planning process that requires various stages to be completed. The prime focus of this work is to assist planners and experts in finding the optimal cable layout of the onshore wind farm. The optimization algorithm is designed using mixed integer linear programming (MILP). The MILP algo- rithm takes into account system reliability, power transfer capacities and power quality issue. The novelty in this optimization algorithm is to simultaneously minimize cable installation cost and the cost of lost energy pro- duction and therefore maximize the reliability of the system. Additionally, the algorithm supports the optimal selection among different cable options, with different features, prices and capacities. By calculating voltage increase at the point of connection (POC), power quality issue is considered as well. The designed algorithm provides optimal results for four different wind farm layouts. Every layout is tested for three different case scenarios, where different number and type of cables are considered. The results show that more cable options contribute in lowering the total costs. Moreover, cables with higher capacity can help in improving the power quality issue.

1. Introduction

Wind energy has attracted a lot of attention and investments in the last decades. It has been shown that wind farms can yield a great po- tential of wind energy resources, their negative environmental impact is negligible, construction time short, and they have the shortest period of investment return in comparison with other renewables [1].

However, the design of the wind farm is a complex task. It requires a large set of variables to be taken into account and decisions to be made.

Nevertheless, the fundamental aim of every wind farm design is to maximize energy production, minimize capital and operating costs, and stay within the constraints imposed by the site [2]. These constraints are usually associated with maximum installed capacity, site boundaries (such as road, dwellings, etc.), environmental, noise and visual issues, turbine minimum spacing, communication signals.

According to [3], the four main steps in the design of a wind farm are:

selecting the right site, optimizing the location of each turbine, estab- lishing the infrastructure and connecting the farm to the existing elec- trical grid.

Assuming that the site and the best turbine positions have been identified, different papers focused on finding the optimal cable connection among turbines, while minimizing the total cable cost. For

example, in [3], [4], [5], [6], [7] and [8] the same authors focus on improving their algorithm for optimal cable layout within an offshore wind farm. They use a mixed integer linear programming (MILP) in order to solve the inter-array cable routing problem. The original version of this problem consists of connecting all the offshore turbines to one (or more) offshore substation(s), minimizing the total cable cost.

However, they gradually include a number of constraints: the energy leaving a turbine must be supported by a single cable; the maximum energy flow (when all the turbines produce their maximum) in each connection cannot exceed the capacity of the installed cable; different cables, with different capacities and costs can be installed; cable crossing must be avoided; a given maximum number of cables can be connected to each substation; cable losses (dependent on the cable type, the cable length and the current flow through the cable) must be considered. In their model installing the cable with different capacity is based on how many turbines can the cable support (e.g. cable 1 supports three turbines at a cost of 393 € /m while cable 2 supports five turbines at a cost of 540

€ /m). Similar cable capacity constraint is presented in [9] where 2 types of cables are considered: one supporting 5 wind turbines and the other 8.

The aim of the optimization in [9] is to find the minimum cost array cable layout in the offshore wind farm. The optimization is implemented through a hop-indexed integer programming, together with a developed heuristic for computing layouts, which is based on the savings heuristic

* Corresponding author.

E-mail addresses: sanjadz@kth.se (S.D. ˇZarkovi´c), ebrahim.shayesteh@ee.kth.se (E. Shayesteh), hilber@kth.se (P. Hilber).

Contents lists available at ScienceDirect

Electric Power Systems Research

journal homepage: www.elsevier.com/locate/epsr

https://doi.org/10.1016/j.epsr.2021.107201

Received 5 September 2020; Received in revised form 11 March 2021; Accepted 27 March 2021

(2)

for vehicle routing. In [10], a fast heuristic specifically designed for wind farm cable routing problem is presented. This heuristic iteratively improves a cable layout by finding and canceling negative cycles in a suitably defined network. The authors argue that this algorithm gives better solutions on large wind farms compared to a MILP solver. How- ever, on small to medium instances the MILP solver performs better in terms of solution quality.

What the above studies have missed to identify is the power quality issue. Namely, the interconnection of the onshore wind farm to the distribution grid is often regarded as a potential source of power quality disturbances. Thus, regardless of the distribution network configuration, it is very important to investigate the influence of renewables scheduled to be connected to the distribution network and to ensure a required power quality [1].

The framework of technical criteria and requirements when con- necting distributed generation to the MV distribution grid is presented in [11], together with the description of different power quality issues, such as slow (steady-state) voltage variations, fast voltage changes, flicker and harmonic emissions. According to [12], by calculating steady-state voltage variation, it is possible to determine the state or the condition of the distribution system, i.e. is it weak or strong enough to accommodate the new source of power (wind generator).

The expected power quality disturbances are usually calculated at the Point of Common Coupling (PCC). PCC is the point at which the effect of the wind farm on the electricity network should be determined [2]. Quite often PCC coincides with the Point of Connection (POC). POC is the point at which responsibility for ownership and operation of the electrical system passes from the wind farm to the electricity network operator [2]. In this paper it is assumed that PCC and POC coincide.

This paper aims to find the optimal cable layout for an onshore wind farm using MILP approach. However, compared to previous studies, the novelty in this algorithm is the reliability assessment of the wind farm.

Beside minimizing cable installation cost, the algorithm aims to mini- mize the cost of lost energy production as well. Cost of lost energy production reflects the impacts of interruption duration, failure rate of the wind turbine, as well as the cost of lost kWh produced by the wind turbine [13]. In the proposed optimization model, cost of lost energy production is the measure of reliability, since it is directly linked to the proposed layout. Based on the suggested outline of the network, the failure rate as well as the cost of lost energy production for every wind

turbine within the farm is updated. The algorithm also takes into ac- count the possibility of installing cables with different capacities and different costs. However, these capacities are based on the maximum current that the cable can withstand and the voltage level of the network. Additionally, the algorithm tends to assess power quality as well. Namely, slow (steady-state) voltage variation at POC is calculated.

This voltage variation happens due to the active power flow on the resistive part of the network impedance and it yields voltage increase at POC (point where wind farm is connected to a distribution network) [11]. To analyze the effectiveness of the algorithm, four different possible positions of POC are considered. The developed method have been tested on an actual distribution model including a wind farm and results are discussed.

This paper is structured as follows: Proposed optimization model is formulated in Section 2. Section 3 reviews the onshore wind farm and presents simulation results. The last section concludes the work.

2. Proposed formulation

Assuming that the wind farm site and the best positions of wind turbines (WTs) have been identified, the optimization model focuses on finding the optimal cable connections among turbines, with the aim to minimize the total cost and maximize the reliability. The optimization is formulated as mixed integer linear programming (MILP).

The main optimization objective is to minimize the total cost which is comprised of cable installation cost and cost of lost energy production, as formulated in (1).

min

xc(i,j)

(

C

CIC

+ C

LEC

)

(1) Cable installation cost C

CIC

is associated with the construction of the potential cable between nodes i and j.

C

CIC

= ∑

N

i=1

N

j=1

C

c=1

x

c

(i, j)⋅C

c

⋅d(i, j)⋅sf (2)

Cost of lost energy production C

LEC

reflects the impacts of interrup- tion duration, failure rate of wind turbine, as well as the cost of lost kWh produced by the wind turbine [13]. In the proposed optimization model, cost of lost energy production is the measure of reliability, since it is Nomenclature

N Number of all nodes in the system L Number of lines in the system C Number of available cables i,j,l,k Node indices

c Cable index

POC Point at which wind farm is connected to the distribution system

Parameters

λ

The failure rate of the cable (f/yr.km) λ init ( i) The initial failure rate of the node i (f/yr) r(i) Repair time at node i (h/f)

sf Safety factor associated with the cable length needed for installation

et(i) Electricity tariff associated with the production of turbine i ( € /kWh)

U Voltage level in feeders (kV)

I c Continuous current carrying capacity of the cable c (A) LC c Power transfer capacity limit of the cable c (kVA) R c Resistance of the cable c (Ω/km)

X c Reactance of the cable c (Ω/km)

C c The installation cost per km of the cable c ( € /km) P(i) Active power of a wind turbine i (kW)

Q(i) Reactive power of a wind turbine i (kVAr) S(i) Apparent power of a wind turbine i (kVA) pf(i) Power factor of a wind turbine i

f(i) Capacity factor of a wind turbine i T Time horizon under study (yr) dr Annual discount rate (%) Variables

x c ( i,j) A binary variable equal to 1 if the cable c is constructed from node i to j, and 0 otherwise

λ N ( i) The final failure rate of node i (f/yr)

λ L ( i,j) The failure rate of the cable between nodes i and j (f/yr) d(i,j) Euclidean distance between nodes i and j (km)

ϵ Voltage increase at POC (%) R Series line resistance at POC (Ω) X Series line reactance at POC (Ω)

LF(i,j) Power transfer between nodes i and j (kW) C CIC Cable installation cost ( € )

C LEC The cost of lost energy production ( € )

(3)

directly linked to the proposed configuration. Based on the suggested outline of the wind farm, the failure rate as well as the cost of lost energy production for every node is updated.

C

LEC

=

T

t=1

1 (1 + dr)

t

⋅ ∑

N

i=1

λ

N

(i)⋅P(i)⋅et(i)⋅r(i)⋅f (i) (3) In this model, more than one cable option is possible. That is, based on the cable’s capacity, optimization proposes an adequate outline.

Number of possible cable options is C (C ∈ {1,2...}). It should be noted that this does not mean that C parallel cables are constructed. Instead, there are C binary decision variables, corresponding to C cables with different costs and capacities, described as follows:

x c ( i,j) =

{ 1, if cable c is constructed from node i to j 0, otherwise

It is important to notice that these binary variables exclude one another, i.e. if one of them is 1, all others are 0 for the same pair of nodes (i, j) (4).

C

c=1

x

c

(i, j) ≤ 1 (4)

Initial failure rate λ

init

of every node is given. Every wind turbine has its own failure rate λ

WT

, while the initial failure rate of POC is assumed to be 0.

λ init ( i) =

{ λ WT , node representing wind turbine 0, node representing POC λ

N

(j) = λ

init

(j) + ∑

N

i=1

C

c=1

x

c

(i, j)(λ

N

(i) + λ

L

(i, j)) (5)

λ

L

(i, j) = λ

⋅d(i, j)⋅sf (6)

Equation (5) describes the failure rate of each node. The algorithm is moving downstream, toward the POC, and it updates the failure rate of every node j by summing its initial failure rate λ

init

( j), failure rate of its upstream nodes λ

N

( i) and upstream cables λ

L

( i, j). Therefore, every downstream node j has a higher failure rate than its upstream node i. In the case of fault, all upstream wind turbines from the place of fault will be disconnected; thus, affecting the cost of lost energy. The closer the fault is to the POC, more wind turbines are disconnected and the cost of lost energy is bigger. Consequently, POC yields the highest failure rate.

Failure rate of every cable depends on the distance between nodes i and j, and it is described by (6).

Since (5) involves the multiplication of binary and continuous vari- able, this makes the problem nonlinear. In order to solve optimization problem as MILP, a Big M method is used. Based on this method, a nonlinear product of two variables z = A⋅C

c=1 x c , where A is a contin- uous variable and ∑ C

c=1 x c is a sum of binary variables that exclude each other, is linearized by following equations [14]:

z ≤ M⋅

C

c=1

x

c

(7)

z ≤ A (8)

z ≥ A − (

1 − ∑

C

c=1

x

c

)

⋅M (9)

z ≥ 0 (10)

A is bounded below by zero and above by a Big M.

C

c=1

x

c

(i, i) = 0 (11)

N

j=1

C

c=1

x

c

(i, j) = 1, ∀i ∕ = POC (12)

C

c=1

(x

c

(i, j) + x

c

(j, i)) ≤ 1, i ∕ = j (13)

N

i=1

C

c=1

x

c

(i, POC) ≥ 1 (14)

Equations (11), (12), (13) represent constraints that are ensuring radial supply and hence only one downstream node, without any loops made [15]. Equation (11) ensures that there is no connection leading from and to the same node. In (12) it is assured that every node (except POC) needs to have only one downstream connection. This paper con- siders directional connections, meaning that x(i, j) and x(j, i) are not the same. If there is a connection from node i to node j (i being the upstream node), (13) prevents possible connection from j to i, i.e. creating a loop in the system between nodes i and j. The POC node is assumed to be capable of receiving the power supply from all WT nodes. The link to the POC, i.e. at least one connection upstream of the POC node, is confirmed by (14).

The power transfer capacity of the cables is calculated according to the following formula:

LC

c

= ̅̅̅

√ 3

UI

c

(15)

where U denotes the voltage level in the feeders and I c denotes the current capacity of the cable c. Therefore, every cable type has its own power transfer capacity.

N

j=1

LF(i, j) = P(i) +

N

l=1

LF(l, i), ∀i ∕ = POC (16)

LF(i, j) ≤

C

c=1

x

c

(i, j)⋅LC

c

⋅0.5 (17)

Equation (16) represents power balance at node i. In other words, (16) assures that the output power flow from node i (i.e. the summation of power flow exiting the node i to the downstream node j) is equal to the supply at node i (P(i)) plus the input power flow to node i (i.e. the summation of power flow entering the node i from the upstream node(s) l). Equation (17), on the other hand, guarantees that the power flow at each line is smaller than the power capacity of the line. As suggested by the utility practice, a safety margin of 50% usability of the current ca- pacity is adopted for normal operating conditions [16].

In order to analyze power quality requirements, the maximum steady-state voltage variation ϵ(%) at the POC is evaluated using the following simplified relation [11]:

ϵ ≈ 100 U

2

( R⋅

N

i=1

P(i) + X⋅

N

i=1

Q(i) )

(18) R and X are series line resistance and reactance at POC, respectively, and they depend on the cable type (every cable type c has its own electrical parameters, R

c

and X

c

).

R =

N

i=1

N

j=1

( ∑

C

c=1

R

c

⋅x

c

(i, j) )

⋅d(i, j) (19)

X =

N

i=1

N

j=1

( ∑

C

c=1

X

c

⋅x

c

(i, j) )

⋅d(i, j) (20)

(4)

3. Case study 3.1. Test system

The effectiveness of the MILP approach is tested using an actual onshore wind farm in Sweden. The wind farm consists of 13 wind tur- bines and 4 possible POCs, which geographical coordinates are known.

Based on these coordinates, Euclidean distances between turbines are estimated (Appendix A). To address the real terrain between the tur- bines, these Euclidean distances are multiplied with a safety factor, sf.

According to the utility practice [16], sf is assumed to be 1.7. Graphical representation of wind turbine layout is presented in Figure 1.

As already explained, taking into consideration the existing wind turbine layout, the idea of this paper is to find the optimal cable layout of the wind farm, while minimizing cable installation cost and cost of lost energy production.

Usually, the turbines are interconnected by a medium voltage (MV) electrical network, in the range 10–35 kV. In most cases this network consists of underground cables, but in some locations overhead lines on wooden poles are adopted [2]. In this model, turbines are inter- connected by a 33kV underground cable network. Table 1 presents the typical technical data for the Three Core Armoured Copper Conductors [17]. The prices for different cable types are obtained from Swedish Energy Market Inspectorate (Energimarknadsinspektionen) [18]. These prices cover catalogue price for the indicated cable (with specified size and voltage level) but also installation, work and some unforeseen costs, such as blasting, stones, crossing obstacles. Failure rate of the cable λ

is considered to be 0.02 f/km.year [19].

The medium voltage electrical network consists of radial feeders since there is no economic justification for providing ring arrangements (unlike industrial power networks) [2]. Therefore, a fault in a cable or a turbine will result in all upstream turbines on that feeder being disconnected.

The turbine generator voltage is normally classed as low (below 1000 V, and quite often it is 690 V). Therefore, it is necessary for each turbine to have an associated switchgear and a transformer to step up to medium

voltage. Suitably, many turbines now include a transformer and switching equipment as a part of the turbine supply. Therefore, the turbine terminal voltage is a medium tension and can be connected directly to the farm network. [2]

In this work, considered turbine generator is taken from the Siemens catalogue [20]. Rated power of a turbine P(i) is 3.465MW, power factor of a generator pf(i) is 0.925 CAP-0.925 IND throughout the power range, while the capacity factor f(i) is 34%.

Based on the following equations, reactive power of the turbine Q(i) is derived:

S

2

(i) = P

2

(i) + Q

2

(i) (21)

pf (i) = P(i)

S(i) (22)

Q(i) = P(i)⋅

̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅

1 pf

2

(i) − 1

(23) In practical situations, (18) will yield a voltage increase, due to active power flow on resistive part of the network impedance. For this reason, slightly inductive power factor values are usually preferred (Q<0) [11]. In this model, the voltage increase ϵ should not be bigger than 3% (Ellevio, 2019).

Reliability data for wind turbines are taken from [21] (Sweden, Elforsk/ Vindstat). Initial failure rate of a turbine λ WT ( i) is 0.4 f/year, while the restoration time r(i) is 130h. The electricity tariff et(i) asso- ciated with the production of the onshore turbine in Sweden is obtained from International Renewable Energy Agency [22] and is considered to be 0.039 € /kWh. The time horizon T under study is 25 years, based on the expected life time of the onshore wind farm [23]. The annual dis- count rate dr is 8%.

The proposed simulation for MILP is formulated in GAMS software using CPLEX solver and performed in Windows 10, on an Intel (R) Core (TM) i7-6600U CPU 2.60GHz with 16GB RAM.

Fig. 1. Existing Layout of Wind Turbines and POCs.

Table 1 Cable parameters

Cable type c 1 2 3

Nominal cross-sectional area [mm

2

] 3x240 3x150 3x300 R

c

[Ω / km] (Maximum AC resistance@ 90

C) 0.0978 0.1590 0.0788 X

c

[Ω /km] (Reactance @50Hz) 0.109 0.118 0.105 I

c

[A] (Continuous current carrying capacity) 435 335 490 C

c

[ € /km] (Price of the cable) 63 049 59 197 67 509

Table 2

Optimal Solution Results - Cable Type 1

Cable Type 1 POC

1

POC

2

POC

3

POC

4

Total Cost [ € ] 1 450 377 1 504 431 1 484 622 1 366 965 Cost of Lost Energy [ € ] 517 936 517 541 517 936 544 752 Cable Installation Cost [ € ] 932 441 986 890 966 686 822 213 Total Cable Length [m] 8 699 9 207 9 019 7 671 Voltage Increase [%] 1.908 2.02 1.978 1.683

Table 3

Optimal Solution Results - Cable Type 1&2

Cable Type 1&2 POC

1

POC

2

POC

3

POC

4

Total Cost [ € ] 1 420 682 1 477 463 1 456 870 1 322 632 Cost of Lost Energy [ € ] 517 936 517 541 517 936 544 752 Cable Installation Cost [ € ] 902 746 959 922 938 934 777 880 Total Cable Length [m] 8 699 9 207 9 019 7 671 Voltage Increase [%] 2.987 2.999 2.986 3.000

Table 4

Optimal Solution Results - Cable Type 1&2&3

Cable Type 1&2&3 POC

1

POC

2

POC

3

POC

4

Total Cost [ € ] 1 411 608 1 474 090 1 441 192 1 319 478

Cost of Lost Energy [ € ] 571 660 597 953 571 660 544 436

Cable Installation Cost [ € ] 839 948 876 137 869 531 775 042

Total Cable Length [m] 8 047 8 341 8 309 7 525

Voltage Increase [%] 2.862 2.974 2.893 2.992

(5)

3.2. Simulation results

The simulation includes the comparison of four different wind farm layouts. Each layout has a different point of connection (POC) while the number and positions of wind turbines are fixed. For each possible layout, there are 3 case scenarios depending on the type(s) of cable(s) included in the simulation. First case considers installation of the cable type 1, the second case installation of types 1 and 2, while the third scenario includes types 1, 2 and 3 together. The presented algorithm can easily support even more types of cables. However, in order to efficiently represent the potential of the algorithm, this study focuses on 3 cable

types.

The results of compared optimization studies including system reli- ability, power transfer capacities and power quality for all three cases are presented in Tables 2, 3 and 4. Wind farm outlines proposed by MILP for all 4 layouts under 3 case scenarios are presented in Figures 2a - 4 d.

The purpose of 4 POCs is to recognize the best possible layout of the wind farm. This is quite beneficial in the planning phase since it helps in lowering the expenses. It can be seen in Figure 5a that in all three cases outline with POC 4 gives the lowest total cost. Consequently, cable installation cost and total cable length are the lowest in the layout with POC 4 (Figures 5b, 5 d).

Fig. 2. Wind Farm Layouts with Cable Type 1.

Table 5

Optimal Solution Results - Cable Type 2

Cable Type 2 POC

1

POC

2

POC

3

POC

4

Total Cost [ € ] 1 484 246 + 2.33% 1 525 730 + 1.42% 1 539 544 + 3.69% 1 370 132 + 0.23%

Cost of Lost Energy [ € ] 491 724 -5.06% 491 324 -5.06% 491 724 -5.06% 464 760 -14.68%

Cable Installation Cost [ € ] 992 521 + 6.44% 1 034 406 + 4.81% 1 047 820 + 8.39% 905 371 + 10.11%

Total Cable Length [m] 9 862 + 13,36% 10 278 + 11,63% 10 412 + 15,45% 8 996 + 17,28%

Voltage Increase [%] 4.509 +136% 4.699 +132% 4.760 +140% 4.113 +144%

Table 6

Optimal Solution Results - Cable Type 3

Cable Type 3 POC

1

POC

2

POC

3

POC

4

Total Cost [ € ] 1 495 199 + 3,09% 1 555 291 + 3,38% 1 525 268 + 2,74% 1 408 091 + 3,01%

Cost of Lost Energy [ € ] 571 660 + 10,37% 597 953 + 15,54% 571 660 + 10,37% 544 436 -0,06%

Cable Installation Cost [ € ] 923 539 -0,95% 957 337 -2,99% 953 607 -1,35% 863 654 + 5,04%

Total Cable Length [m] 8 047 -7,49% 8 341 -9,40% 8 309 -7,87% 7 525 -1,89%

Voltage Increase [%] 1.181 -37.78% 1.231 -39.06% 1.226 -38.02% 1.110 -34.05%

(6)

Fig. 3. Wind Farm Layouts with Cable Type 1&2.

Fig. 4. Wind Farm Layouts with Cable Type 1&2&3.

(7)

Configuration for every layout is the same in the first (with cable type 1) and second case scenario (with cable types 1&2). However, in the second case, the algorithm seizes the opportunity to install cable type 2 wherever possible, which has lower capacity but it is also cheaper than cable type 1. Therefore, cable installation costs are lower in the second case than in the first. However, since the outline does not change, there are no differences in total cable length and cost of lost energy production.

With the possibility to install cable type 3, which is the most expensive but it has the biggest capacity (third case scenario), the optimization proposes outlines with longer feeders that have the ability to support more turbines. Generally, for every layout, total cable length is the smallest in the third case. However, the cost of lost energy pro- duction is higher than in the first two cases for outlines with POC 1 , POC 2

and POC 3 . Longer feeders increase certain risk - in case the failure happens on a feeder, more turbines on that feeder can be disconnected.

However, the layout with POC 4 is almost the same in all three scenarios, and thus, gives very close values of cost of lost energy.

Regarding the power quality issue, in all cases the voltage increase

This is due to electrical parameters of the cable type 1. Once the cable type 2 is introduced (with higher resistance and reactance), there is a significant rise in the voltage increase at POC. However, combination with the cable type 3 gives slightly better (lower) values. It can be concluded that cables with higher capacity give better overview when it comes to power quality issues. This can be also confirmed by additional experimental results.

To highlight the comparison between different cable types, two

complementary scenarios are considered: installing only cable type 2

and only cable type 3, and they are compared with the first case scenario

(installing only cable type 1). By installing only cable type 2, simulation

for every layout obtains infeasible results. This means that for the given

parameters, one of the constraints can not be satisfied, and that is

maintaining the voltage increase below 3%. By omitting the indicated

constraint, results presented in Table 5 are obtained (next to every nu-

merical value is a percentage indicator that shows if the obtained value

is higher or lower than the value acquired by installing only cable type

1). It can be seen that the power quality is completely violated in this

case. Moreover, when comparing total costs with total costs obtained by

Fig. 5. Results of Comparative Case Studies.

(8)

Fig. 6. Wind Farm Layouts including ”non-cross” constraint.

Fig. 7. Wind Farm Layouts including ”non-cross” constraint.

(9)

cable type 2 is cheaper than cable type 1. The only improvement with cable type 2 is the cost of lost energy, which is on average 7% lower, and the reason for that is the outline with shorter feeders. Since voltage in- crease at POC also depends on the rated power and number of wind turbines within a farm, in order to satisfy the power quality constraint in this scenario, the solution could be either to connect less turbines or to consider turbines with smaller rated power. However, the latter option is not viable, since the purpose of this paper is to find optimal cable layout, assuming that the wind farm site and the best positions of turbines have been identified.

Cable type 3, with the biggest capacity, is beneficial when it comes to power quality (results are presented in Table 6). Namely, voltage in- crease is on average 37% lower when compared with cable type 1.

Moreover, total cable length and installation cost are also lower. How- ever, in this outline longer feeders that can support bigger number of turbines are created, which negatively affects cost of lost energy.

Therefore, total costs are on average 3% higher than in scenario with cable type 1.

3.2.1. Cable crossing

In outlines presented in Figures 2a, 2 b, 2 c, 3 a, 3 b, 3 c, 4 b two cables cross. According to [4], cable crossings should be avoided, as establishing one cable across another is expensive and increases the risk of cable damages. However, in the previous mentioned literature, the

” non-cross” constraint is only added whenever two already established connections cross - it is not part of the original algorithm. Therefore, if two connections (i,j) and (l,k) cross, the following ”non-cross” constraint is considered [4]:

C

c=1

(x

c

(i, j) + x

c

(j, i) + x

c

(l, k) + x

c

(k, l)) ≤ 1 (24) The new layouts with ”non-cross” constraint are presented in Fig- ures 6 and 7. New numerical results are highlighted in Tables 7, 8 and 9.

3.2.2. Neglecting reliability aspect in objective function

As already mentioned, the novelty in this study is the reliability assessment of the wind farm. Moreover, the previous studies have focused on minimization of cable installation cost while neglecting the reliability aspect, i.e. the cost of lost energy. To highlight this paper’s contribution, the simulations are run with modified objective function, i.

e. by minimizing cable installation cost only. Cost of lost energy and total cost are assessed simultaneously. The obtained results are pre- sented in Tables 10, 11 and 12. Next to every numerical value is a percentage indicator that shows if the obtained value is higher or lower than the value acquired by minimizing both cable installation cost and cost of lost energy.

The results show that cable installation cost is on average 9.02%

lower compared to the case when reliability aspect is considered as well.

However, the cost of lost energy is on average 26.88% worse, i.e. higher.

Moreover, the total cost is on average higher by 4.66% in the case with modified objective function. This example helps in emphasizing the importance of reliability assessment when planning the onshore wind farm.

Table 7

Results including ”non-cross” constraint - Cable Type 1

Cable Type 1 POC

1

POC

2

POC

3

POC

4

Total Cost [ € ] 1 451 090 1 512 468 1 495 700 1 366 965

Cost of Lost Energy [ € ] 517 760 517 700 518 156 544 752

Cable Installation Cost [ € ] 933 330 994 768 977 543 822 213

Total Cable Length [m] 8 707 9 281 9 120 7 671

Voltage Increase [%] 1.910 2.036 2.000 1.683

Table 8

Results including ”non-cross” constraint - Cable Type 1&2

Cable Type 1&2 POC

1

POC

2

POC

3

POC

4

Total Cost [ € ] 1 421 102 1 483 069 1 468 208 1 322 632

Cost of Lost Energy [ € ] 517 760 570 978 518 156 544 752

Cable Installation Cost [ € ] 903 342 912 091 950 052 777 880

Total Cable Length [m] 8 707 8 785 9 120 7 671

Voltage Increase [%] 2.999 2.999 2.999 3.000

Table 9

Results including ”non-cross” constraint - Cable Type 1&2&3

Cable Type 1&2&3 POC

1

POC

2

POC

3

POC

4

Total Cost [ € ] 1 411 608 1 476 205 1 441 192 1 319 478

Cost of Lost Energy [ € ] 571 660 571 556 571 660 544 436

Cable Installation Cost [ € ] 839 948 904 649 869 531 775 042

Total Cable Length [m] 8 047 8 592 8 309 7 525

Voltage Increase [%] 2.862 2.999 2.893 2.992

Table 10

Modified Objective Function - Cable Type 1

Cable Type 1 POC

1

POC

2

POC

3

POC

4

Total Cost [ € ] 1 487 701 + 2.57% 1 534 936 + 2.03% 1 515 783 + 2.09% 1 404 297 + 2.73%

Cost of Lost Energy [ € ] 651 018 + 25.69% 624 992 + 20.76% 651 018 + 25.69% 624 592 + 14.65%

Cable Installation Cost [ € ] 836 683 -10.27% 909 943 -7.79% 864 765 -10.54% 779 704 -5.17%

(10)

4. Conclusion

This paper aims to find the optimal cable layout of an onshore wind farm using a MILP approach. The MILP algorithm takes into account sys- tem reliability, power transfer capacities and power quality issue. The novelty in this optimization algorithm is to simultaneously minimize cable installation cost and cost of lost energy production, and dynamically up- date failure rate of every node, while deciding on the network outline.

Additionally, the algorithm supports selection of the optimum cable among different cable options, with different prices and capacities. By monitoring and controlling the voltage increase at POC, power quality issue is considered as well.

To analyze the effectiveness of the algorithm, four different layouts (with different POCs) are considered. Each layout is evaluated for three case scenarios, depending on the type(s) of cable(s) involved in the simulation. It has been shown that the layout with POC 4 in every sce- nario gives the best (lowest) values for total cost. By introducing more cable options, total costs are decreasing for every layout. It has also been shown that cables with bigger capacity contribute to lower values of voltage increase at POC. Additionally, these cables have the ability to support supply from more turbines, creating longer feeders. However, these longer feeders negatively affect system reliability and therefore cost of lost energy production.

The wind farm electrical system must meet local electrical safety requirements, should achieve an optimum balance between costs and reliability and must ensure that the wind farm satisfies the technical requirements of the electricity network operator [2]. The designed

approach successfully implements these requirements and assists plan- ners and experts in the onshore wind farm design.

CRediT authorship contribution statement

Sanja Duvnjak ˇZarkovi´c: Conceptualization, Methodology, Soft- ware, Investigation, Visualization. Ebrahim Shayesteh: Conceptuali- zation, Software, Supervision. Patrik Hilber: Conceptualization, Supervision.

Declaration of Competing Interest

The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper.

Acknowledgement

The authors thank SweGRIDS, the Swedish Centre for Smart Grids and Energy Storage, for funding the project. Moreover, the authors thank Daniel Fahlgren from Ellevio AB and Carl Johan Wallnerstr¨om from Energimarknadsinspektionen for providing valuable data and practical information for this project.

Appendix A Table 11

Modified Objective Function - Cable Type 1&2

Cable Type 1&2 POC

1

POC

2

POC

3

POC

4

Total Cost [ € ] 1 459 267 +2.72% 1 504 105 +1.80% 1 487 114 +2.07% 1 375 146 +3.97%

Cost of Lost Energy [ € ] 651 018 + 25.69% 624 992 + 20.76% 651 018 + 25.69% 624 592 + 14.65%

Cable Installation Cost [ € ] 808 249 -10.46% 879 112 -8.42% 836 096 -10.95% 750 554 -3.51%

Table 12

Modified Objective Function - Cable Type 1&2&3

Cable Type 1&2&3 POC

1

POC

2

POC

3

POC

4

Total Cost [ € ] 1 577 405 + 11.74% 1 582 009 + 7.32% 1 534 789 + 6.49% 1 455 987 + 10.35%

Cost of Lost Energy [ € ] 810 652 + 41.81% 810 652 + 35.57% 757 288 + 32.47% 757 235 + 39.08%

Cable Installation Cost [ € ] 766 752 -8.71% 771 357 -11.96% 777 501 -10.58% 698 751 -9.84%

Table 13

Distances between nodes

Distance[m] POC

1

POC

2

POC

3

POC

4

WT

1

WT

2

WT

3

WT

4

WT

5

WT

6

WT

7

WT

8

WT

9

WT

10

WT

11

WT

12

WT

13

POC

1

0 - - - 209.1 439.1 1002.0 701.6 1290.0 912.5 963.2 1180.0 1360.0 1490.0 1850.0 1980.0 2360.0

POC

2

- 0 - - 688.0 378.0 630.0 1100.0 1610.0 1170.0 950.0 972.0 1470.0 1400.0 1950.0 1960.0 2430.0

POC

3

- - 0 - 245.0 336.0 1470.0 614.0 1190.0 1000.0 1240.0 1550.0 1500.0 1720.0 1960.0 2180.0 2450.0

POC

4

- - - 0 1370.0 1390.0 1750.0 856.0 323.0 611.0 961.0 1400.0 539.0 1040.0 633.0 1080.0 1060.0

WT

1

209.1 688.0 245.0 1370.0 0 537.8 1180.0 525.1 1120.0 798.3 964.7 1260.0 1290.0 1470.0 1780.0 1940.0 2270.0

WT

2

439.1 378.0 336.0 1390.0 537.8 0 634.1 786.9 1260.0 775.1 629.4 753.8 1120.0 1100.0 1610.0 1640.0 2090.0

WT

3

1002.0 630.0 1470.0 1750.0 1180.0 634.1 0 1370.0 1700.0 1190.0 776.8 481.0 1310.0 1010.0 1710.0 1560.0 2130.0

WT

4

701.6 1100.0 614.0 856.9 525.1 786.9 1370.0 0 613.6 425.6 834.0 1260.0 934.1 1260.0 1360.0 1620.0 1870.0

WT

5

1290.0 1610.0 1190.0 323.0 1120.0 1260.0 1700.0 613.6 0 512.3 970.5 1440.0 709.2 1200.0 962.2 1350.0 1420.0

WT

6

912.5 1170.0 1000.0 611.0 798.3 775.1 1190.0 425.6 512.3 0 485.7 949.4 507.2 838.6 956.3 1200.0 1480.0

WT

7

963.2 950.0 1240.0 961.0 964.7 629.4 776.8 834.0 970.5 485.7 0 479.3 531.5 507.0 994.1 1010.0 1470.0

WT

8

1180.0 972.0 1550.0 1400.0 1260.0 753.8 481.0 1260.0 1440.0 949.4 479.3 0 906.5 551.8 1260.0 1090.0 1660.0

WT

9

1360.0 1470.0 1500.0 539.0 1290.0 1120.0 1310.0 934.1 709.2 507.2 531.5 906.5 0 503.5 510.2 701.9 997.8

WT

10

1490.0 1400.0 1720.0 1040.0 1470.0 1110.0 1010.0 1260.0 1200.0 838.6 507.0 551.8 503.5 0 751.9 560.4 1130.0

WT

11

1850.0 1950.0 1960.0 633.0 1780.0 1610.0 1710.0 1360.0 962.2 956.3 994.1 1260.0 510.2 751.9 0 481.6 502.5

WT

12

1980.0 1960.0 2180.0 1080.0 1940.0 1640.0 1560.0 1620.0 1350.0 1200.0 1010.0 1090.0 701.9 560.4 481.6 0 630.4

WT

13

2360.0 2430.0 2450.0 1060.0 2270.0 2090.0 2130.0 1870.0 1420.0 1480.0 1470.0 1660.0 997.8 1130.0 502.5 630.4 0

(11)

References

[1] D. Jakus, R. Goic, J. Krstulovic, The impact of wind power plants on slow voltage variations in distribution networks, Electric Power Syst. Res. 81 (2) (2011) 589–598.

[2] P. Gardner, A. Garrad, L. Hansen, A. Tindal, J. Cruz, L. Arribas, N. Fichaux, Wind energy-the facts, part 1 technology, Eur. Wind Energy Assoc. (EWAE) (2009).

[3] M. Fischetti, D. Pisinger, Mathematical optimization and algorithms for offshore wind farm design: an overview, Bus. Inf. Syst. Eng. 61 (4) (2019) 469–485.

[4] M. Fischetti, D. Pisinger, Optimal wind farm cable routing: Modeling branches and offshore transformer modules, Networks 72 (1) (2018) 42–59.

[5] M. Fischetti, D. Pisinger, On the impact of using mixed integer programming techniques on real-world offshore wind parks.. ICORES, 2017, pp. 108–118.

[6] M. Fischetti, M. Monaci, Proximity search heuristics for wind farm optimal layout, J. Heuristic. 22 (4) (2016) 459–474.

[7] M. Fischetti, D. Pisinger, Mixed integer linear programming for new trends in wind farm cable routing, Electronic Note. Discrete Math. 64 (2018) 115–124.

[8] M. Fischetti, D. Pisinger, Optimizing wind farm cable routing considering power losses, Eur. J. Oper. Res. 270 (3) (2018) 917–930.

[9] J. Bauer, J. Lysgaard, The offshore wind farm array cable layout problem: a planar open vehicle routing problem, J. Oper. Res. Soc. 66 (3) (2015) 360–368.

[10] S. Gritzbach, T. Ueckerdt, D. Wagner, F. Wegner, M. Wolf, Towards negative cycle canceling in wind farm cable layout optimization, Energy Inf. 1 (1) (2018) 183–193.

[11] S.A. Papathanassiou, A technical evaluation framework for the connection of dg to the distribution network, Electric Power Syst. Res. 77 (1) (2007) 24–34.

[12] A.F. Agbetuyi, C. Awosope, A. Awelewa, A. Adoghe, I. Odigwe, I. Samuel, Connecting wind turbine generator to distribution power grida preload flow calculation stage, J. Energy Power Eng. 8 (2014) 1811–1815.

[13] S. Ozturk, V. Fthenakis, S. Faulstich, Failure modes, effects and criticality analysis for wind turbines considering climatic regions and comparing geared and direct drive wind turbines, Energies 11 (9) (2018) 2317.

[14] L. Coelho, Linearization of the product of two variables., 2013. URL https://www.

leandro-coelho.com/linearization-product-variables.

[15] H. Ahmadi, J.R. Martí, Mathematical representation of radiality constraint in distribution system reconfiguration problem, Int. J. Electric. Power Energy Syst. 64 (2015) 293–299.

[16] S.D. ˇZarkovi´c, S. Stankovi´c, E. Shayesteh, P. Hilber, Reliability improvement of distribution system through distribution system planning: MILP vs. GA. 2019 IEEE Milan PowerTech, IEEE, 2019, pp. 1–6.

[17] Nexans, 6-36kV Medium Voltage Underground Power Cables, 2009. URL htt ps://www.powerandcables.com/wp-content/uploads/2016/12/Nexans-6-33kV -Medium-High-Voltage-Underground-Power-Cables.pdf.

[18] Energimarknadsinspektionen, 2020. URL https://www.ei.se/.

[19] Y. He, Distribution equipment reliability data, Elforsk, Tech. Rep.07:59, 2007.

[20] Siemens Gamesa Renewable Energy, Siemens Gamesa Onshore Wind Turbine - SG 3.4-132, 2019. URL https://www.siemensgamesa.com/-/media/siemensgamesa /downloads/en/products-and-services/onshore/brochures/siemens-gamesa-onsh ore-wind-turbine-sg-3-4-132-en.pdf.

[21] S. Pfaffel, S. Faulstich, K. Rohrig, Performance and reliability of wind turbines: a review, Energies 10 (11) (2017) 1904.

[22] International Renewable Energy Agency, Weighted-average LCOE of newly commissioned onshore wind project for country, 1984-2019, 2019. URL http s://www.irena.org/Statistics/View-Data-by-Topic/Costs/Wind-Costs.

[23] E. Topham, D. McMillan, Sustainable decommissioning of an offshore wind farm,

Renew. Energy 102 (2017) 470–480.

References

Related documents

Having reliable supplier relationship is one of the main sources for companies’ open innovation strategy, exploring and raising the level of innovativeness. Consequently,

By laser pumping the ground state of the molecule and probing the excited states with core level spectroscopy, one can shed light on the nature of internal electron- ic

In Section 4 we analyze the polynomial identities and prove (Theorem 2) that they imply that the supporting function ρ(ω) must be a quadratic polynomial, which together with the

New figures for electrical energy losses have been calculated, by combining load flow calculations and wind data with park power output from the farm. The final result of the

In the capacity range up to 5,000 passengers per hour and over a track length of up to 5 kilometers, the CABLE Liner ensures maximum mobility in the urban environment. As well

Test cases are designed to represent the effects of downwind/crosswind turbine placement spacing, number of turbines and overall farm layout, ambient turbulence

The buses were defined as PQ-buses, as there was active and reactive power production data and load data for all the wind turbines in the wind farm, but there was missing voltage

– The purpose of stage 1 is to simultaneously minimize cable installation cost, switch installation and mainte- nance cost and customer outage cost, and dynamically update failure